13.7
Part 13.7 ServicesPart 13.7 Services
13.7.1
Application of Part 13.7
2019: 3.12.5
Application of Part 13.7
13.7.2
Insulation of services
2019: 3.12.5.1
The central heating water piping provisions apply to systems designed to heat the building via water, such as a hydronic heating system.
13.7.3
Central heating water piping
2019: 3.12.5.2
must, in all climate zones, have a minimum material R-Value of 0.4.
must have a minimum material R-Value in accordance with (5).
must have a minimum material R-Value in accordance with (6).
Insulation | R-Value |
---|---|
9 mm of closed cell polymer | 0.4 |
13 mm of closed cell polymer | 0.6 |
19 mm of closed cell polymer | 0.9 |
25 mm of closed cell polymer | 1.3 |
25 mm of glasswool | 1.3 |
13.7.4
Heating and cooling ductwork
2019: 3.12.5.3
Insulating material and thickness | R-Value |
---|---|
45 mm glasswool (11 kg/m3) | 1.0 |
70 mm polyester (6.4 kg/m3) | 1.0 |
63 mm glasswool (11 kg/m3) | 1.5 |
90 mm polyester (8.9 kg/m3) | 1.5 |
85 mm glasswool (11 kg/m3) | 2.0 |
Insulating material and thickness | R-Value |
---|---|
38 mm glasswool (22 kg/m3) | 1.0 |
50 mm polyester (20 kg/m3) | 1.1 |
50 mm glasswool (22 kg/m3) | 1.5 |
75 mm polyester (20 kg/m3) | 1.7 |
Insulating material and thickness | R-Value |
---|---|
38 mm glasswool (32 kg/m3) | 1.0 |
50 mm polyester (32 kg/m3) | 1.3 |
50 mm glasswool (32 kg/m3) | 1.5 |
13.7.5
Electric resistance space heating
2019: 3.12.5.4
This clause has deliberately been left blank.
Electric resistance space heating
13.7.5 does not apply in NSW.
An electric resistance space heating system that serves more than one room must have—
13.7.6
Artificial lighting
2019: 3.12.5.5
This clause has deliberately been left blank.
Artificial lighting
13.7.6 does not apply in NSW.
13.7.7
Water heater in a heated water supply system
2019: 3.12.5.6
This clause has deliberately been left blank.
Water heater in a heated water supply system
13.7.7 does not apply in NSW.
A water heater in a heated water supply system must be designed and installed in accordance with Part B2 of NCC Volume Three — Plumbing Code of Australia.
13.7.8
Swimming pool heating and pumping
2019: 3.12.5.7
This clause has deliberately been left blank.
Swimming pool heating and pumping
13.7.8 does not apply in NSW.
13.7.9
Spa pool heating and pumping
2019: 3.12.5.8
This clause has deliberately been left blank.
Spa pool heating and pumping
13.7.9 does not apply in NSW.
Insulation | R-Value |
---|---|
9 mm of closed cell polymer | 0.4 |
13 mm of closed cell polymer | 0.6 |
19 mm of closed cell polymer | 0.9 |
25 mm of closed cell polymer | 1.3 |
25 mm of glasswool | 1.3 |
Insulating material and thickness | R-Value |
---|---|
45 mm glasswool (11 kg/m3) | 1.0 |
70 mm polyester (6.4 kg/m3) | 1.0 |
63 mm glasswool (11 kg/m3) | 1.5 |
90 mm polyester (8.9 kg/m3) | 1.5 |
85 mm glasswool (11 kg/m3) | 2.0 |
Insulating material and thickness | R-Value |
---|---|
38 mm glasswool (22 kg/m3) | 1.0 |
50 mm polyester (20 kg/m3) | 1.1 |
50 mm glasswool (22 kg/m3) | 1.5 |
75 mm polyester (20 kg/m3) | 1.7 |
Insulating material and thickness | R-Value |
---|---|
38 mm glasswool (32 kg/m3) | 1.0 |
50 mm polyester (32 kg/m3) | 1.3 |
50 mm glasswool (32 kg/m3) | 1.5 |