ABCB Housing Provisions
Search the National Construction Code editions
9.2
Part 9.2 Fire separation of external wallsPart 9.2 Fire separation of external walls
9.2.1
External walls of Class 1 buildings
2019: 3.7.2.2
An external wall of a Class 1 building, and any openings in that wall, must comply with 9.2.3 if the wall is less than—
External walls of Class 1 buildings
An external wall of a Class 1 building, and any openings in that wall, must comply with 9.2.3 if the wall is less than—
9.2.2
Measurement of distances
2019: 3.7.2.3
Setback distance is measured at right angles to the boundary.
Setback distance is measured at right angles to the boundary.
Setback distance is measured at right angles to the boundary.
Setback distance is measured at right angles to the boundary.
9.2.3
Construction of external walls
2019: 3.7.2.4
9.2.4
Class 10a buildings
2019: 3.7.2.5
9.2.4(1)(a) ensures that when a Class 10 building is located between an allotment boundary and a Class 1 building or another building on the same allotment, either directly or indirectly, that the Class 1 building be protected by a wall with an FRL.
The intention is to prevent the spread of fire from an allotment boundary (fire source feature) to a Class 1 building via a Class 10a building. Where a Class 10a building is not sited directly and wholly between the allotment boundary and the Class 1 building (see 9.2.5), the potential of fire spreading from the allotment boundary to the Class 1 still exists. Therefore, fire separation would be required.
9.2.4 does not apply to a boundary that adjoins a road or public space such as parklands, lakes, rivers and the like where the construction of buildings is unlikely.
9.2.5
Protection of Class 1 buildings — Class 10a between Class 1 and the allotment boundary
2019: Figure 3.7.2.4
The following methods are acceptable for the protection of a Class 1 building where a Class 10a building is located between or adjacent to a Class 1 building and a boundary alignment that is not a boundary with a road alignment or other public space:
9.2.6
Protection of Class 1 buildings—Class 10a between Class 1 and other buildings on allotment
2019: Figure 3.7.2.5
The following methods are acceptable for the protection of a Class 1 building where a Class 10a building is located between or adjacent to a Class 1 building it is associated with and another building on the same allotment:
9.2.7
Protection of Class 1 buildings—separation of Class 10a buildings on an allotment
2019: Figure 3.7.2.6
The following methods are acceptable for the protection of a Class 1 building where two or more Class 10a buildings on the same allotment are located between and are associated with different Class 1 buildings:
9.2.8
Open carports
2019: 3.7.2.6
A Class 10a carport is exempt from complying with 9.2.4(1) if—
Open carports
A Class 10a carport is exempt from complying with 9.2.4(1) if—
A side of a carport enclosed by a vehicle access door is not considered to be an open side.
9.2.9
Allowable encroachments
2019: 3.7.2.7
Allowable encroachments
A deck is not considered an unroofed terrace and is therefore not permitted as an allowable encroachment under 9.2.9 whether combustible or not.
The term ‘pergola’ is a reference to an unroofed structure.
Explanatory Figure 9.2.9 depicts encroachment of a building on the same allotment, but which is not associated with the building onto which it encroaches.
9.2.10
Roof lights
2019: 3.7.2.8
Combustible roof lights, skylights or the like installed in a roof or part of a roof required to have a non-combustible covering must—
Roof lights depicted in Figure 9.2.10 are combustible.
Roof lights depicted in Figure 9.2.10 are combustible.