Delete subclause S20C4(4) and insert VIC S20C4(4) as follows:
(4) In a Class 9c building provided with a smoke detection system—
- if the building accommodates more than 20 residents, manual call points must be installed in paths of travel so that no point on a floor is more than 30 m from a manual call point; and
- indication of the zone where the smoke detection system has actuated must be achieved by one of the following:
- Option 1—
- remote automatic indication of each zone must be given in each smoke compartment; and
- indication of (A) must be indicated on remote annunciator panels with alpha-numeric displays with a minimum of 20 characters of 9 mm minimum height.
- Option 2—
- indication of the zone where the smoke detection system has actuated must be communicated via a suitable interface with the fire indicator panel to a portable remote communication device; and
- at least one such portable remote communication device per smoke compartment must be provided to staff nominated by the owner or operator and properly instructed as to the duties and responsibilities involved; and
- the portable remote communication device may be a pager with alpha-numeric display or portable telephone handset with capability of receiving alpha-numeric display.