NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

5

Specification 5 Fire-resisting construction

Specification 5 Fire-resisting construction

This Specification contains requirements for the fire-resisting construction of building elements.

To clarify that Specification 5 contains requirements for fire-resisting construction of building elements.

S5C1 Scope

Note that Specification 5 applies only to the Deemed-to-Satisfy Provisions of the BCA. If a Performance Solution is used to satisfy a relevant Performance Requirement, it is not necessary to comply with Specification 5.

Parts C2, C3, C4, D2, D3, G2, G3 and I1 of the BCA also contain requirements for building elements to be fire-resisting and to have a fire-resistance level (FRL).

General requirements

(1) A part of a building element is exposed to a fire-source feature if any of the horizontal straight lines between that part and the fire-source feature, or vertical projection of the feature, is not obstructed by another part of the building that—

  1. has an FRL of not less than 30/–/–; and
  2. is neither transparent nor translucent.

(2) A part of a building element is not exposed to a fire-source feature if the fire-source feature is—

  1. an external wall of another building that stands on the allotment and the part concerned is more than 15 m above the highest part of that external wall; or
  2. a side or rear boundary of the allotment and the part concerned is below the level of the finished ground at every relevant part of the boundary concerned.

(3) If various distances apply for different parts of a building element—

  1. the entire element must have the FRL applicable to that part having the least distance between itself and the relevant fire-source feature; or
  2. each part of the element must have the FRL applicable according to its individual distance from the relevant fire-source feature.

(4) The requirements of (3) do not override or permit any exemption from S5C3.

To define how a building element may be exposed to a fire-source feature.

S5C2 Exposure to fire-source features

Fire-source feature

Refer to the definition in Schedule 1 on the term “fire-source feature”.

A fire-source feature is a possible fire-source external to the building from which fire could spread into the building. It may be an allotment boundary or another building on the allotment from which fire could spread to the subject building.

S5C2 does not consider a building element to be exposed to a fire-source feature if it is shielded from the fire-source feature by another part of the building which:

  • has an FRL of 30/–/– or more, and is not transparent or translucent;
  • is less than 15 metres above another building on the allotment. Parts of a building more than 15 metres above another building are not deemed to be affected by fire; or
  • is below the level of the finished ground at every relevant part of a side or rear boundary.

Figure S5C2 illustrates some of the exemptions from the exposureto a fire-source feature.

The building element must have an FRL required for the closest part of the element exposed to the fire-source feature (see S5C2(3)(a)).

Alternatively, the building element may have a varying FRL according to the individual distance of each section of the building element from the fire-source feature (see S5C2(3)(b)).

Figure S5C3 illustrates the alternatives for an external loadbearing wall of a Class 5 building required to be of Type A construction.

Figure S5C2: Part of a building not exposed to a fire-source feature

Image
Figure S5C2: Part of a building not exposed to a fire-source feature

(1) Where a part of a building required to have an FRL depends upon direct vertical or lateral support from another part to maintain its FRL, that supporting part, subject to (2), must—

  1. have an FRL not less than that required by other provisions of this Specification; and
  2. if located within the same fire compartment as the part it supports have an FRL in respect of structural adequacy the greater of that required
    1. for the supporting part itself; and
    2. for the part it supports; and
  3. be non-combustible
    1. if required by other provisions of this Specification; or
    2. if the part it supports is required to be non-combustible.

(2) The following building elements need not comply with (1)(b) and (1)(c)(ii):

  1. An element providing lateral support to an external wall complying with S5C24(1)(b) or C2D12.
  2. An element providing support within a carpark and complying with S5C19, S5C22 or S5C25.
  3. A roof providing lateral support in a building—
    1. of Type A construction if it complies with S5C15(a), (b) or (d); and
    2. of Type B and C construction.
  4. A column providing lateral support to a wall where the column complies with S5C6(1) and (2).
  5. An element providing lateral support to a fire wall or fire-resisting wall, provided the wall is supported on both sides and failure of the element on one side does not affect the fire performance of the wall.

To minimise the risk that a building element required to have a fire-resistance level (FRL) will fail during a fire due to the failure of another element required to give it vertical or lateral support.

S5C3 Fire protection for a support of another part

Support of building elements with an FRL

S5C3(1) sets out the requirements for the fire protection of building elements that provide lateral or vertical support to another building element. This is becausea building element with an FRL is usually dependent on the support to maintain its FRL.

Accordingly, S5C3(1) does not apply to elements that support ceilings required to have a fire-protective covering or a resistance to the incipient spread of fire. Nor to an element required to be non-combustible.

Exceptions of building elements

S5C3(2) lists a number of exemptions to S5C3(1)(b) and S5C3(1)(c)(ii).

The lateral support for the types of wall referred to in S5C3(2)(a) is considered unnecessary in these cases, because S5C23(1)(b) allows the use of brick veneer walls, and C2D12 enables the prevention of outward collapse of certain external walls by specifying the connection of panels to the building’s frame.

The inherent fire resistance of the supports included in S5C18S5C21 and S5C24 is considered adequate in the carparks covered by each clause.

S5C3(2) exempts roofs providing lateral support to other building elements. This is because of a concession within S5C14 for Type A construction. In addition, there is no requirement for Type B and C construction, principally because such buildings are generally low rise.

S5C3(2)(d) exempts certain columns, as listed in S5C6, from having an FRL.

Under S5C3(2)(e) a fire wall or fire-resisting wall referred to should not collapse because it is supported by another building element on the other side of the wall.

Figure S5C3:  Plan showing alternative methods of complying with Tables S5C11a to S5C11g

Image
Figure S5C3:  Plan showing alternative methods of complying with Tables S5C11a to S5C11g

(1) A lintel must have the FRL required for the part of the building in which it is situated.

(2) A lintel need not comply with (1) if it does not contribute to the support of a fire door, fire window or fire shutter, and—

  1. it spans an opening in—
    1. a wall of a building containing only one storey; or
    2. a non-loadbearing wall of a Class 2 or 3 building; or
  2. it spans an opening in masonry which is not more than 150 mm thick and—
    1. not more than 3 m wide if the masonry is non-loadbearing; or
    2. not more than 1.8 m wide if the masonry is loadbearing and part of a solid wall or one of the leaves of a cavity wall.

To minimise the risk that the failure of a lintel over an opening in a wall required to have a fire-resistance level (FRL) will result in the failure of the wall during a fire.

S5C4 Lintels

A lintel must have the same FRL as the part of the building containing it. This is unless it does not contribute to the support of a fire door, fire window or fire shutter. Otherwise, the failure of the lintel during a fire could cause the collapse of all, or part, of the wall.

S5C4 only applies to a lintel required by the Deemed-to-Satisfy Provisions to have an FRL.

S5C4(2)(a) and (b) contain some concessions for small openings where the failure of the lintel would not result in a major collapse of the wall and lead to the spread of fire to another building.

The method of attaching or installing a finish, lining, ancillary element or service installation to the building element must not reduce the fire-resistance of that element to below that required.

To minimise the risk that the method of attaching or installing a finish, lining, ancillary element or service installation will compromise the fire-resistance of a building element.

S5C5 Method of attachment not to reduce the fire-resistance of building elements

S5C5 prohibits a required FRL of a building part from being reduced by the attachment or installation of facings, finishes, ancillary elements or the installation of ducting or any other service.

The reason for controlling this is due to the potential for changes to the fire performance of a buildingelement via attaching or installing another element.

(1) Steel columns — A steel column, other than one in a fire wall or common wall, need not have an FRL in a building that contains—

  1. only 1 storey; or
  2. 2 storeys in some of its parts and 1 storey only in its remaining parts if the sum of the floor areas of the upper storeys of its 2 storey parts does not exceed the lesser of—
    1. 1/8 of the sum of the floor areas of the 1 storey parts; or
    2. in the case of a building to which one of the maximum floor areas specified in Table C3D3 is applicable — 1/10 of that area; or
    3. in the case of a building to which two or more of the maximum floor area specified in Table C3D3 is applicable — 1/10 of the lesser of those areas.

(2) Timber columns — A timber column may be used in a single storey building if—

  1. in a fire wall or common wall the column has an FRL not less than that listed in Table S5C11d, S5C21d or S5C24c as appropriate; and
  2. in any other case where the column is required to have an FRL in accordance with Table S5C11a, S5C11c, S5C11g, S5C21a, S5C21c, S5C21g, S5C24a or S5C24b, it has an FRL of not less than 30/–/–.

(3) Structures on roofs — A non-combustible structure situated on a roof need not comply with the other provisions of this Specification if it only contains—

  1. lift motor equipment; or
  2. one or more of the following:
    1. Hot water or other water tanks.
    2. Ventilating ductwork, ventilating fans and their motors.
    3. Air-conditioning chillers.
    4. Window cleaning equipment.
    5. Other service units that are non-combustible and do not contain flammable or combustible liquids or gases.

(4) Curtain walls and panel walls — A requirement for an external wall to have an FRL does not apply to a curtain wall or panel wall which is of non-combustible construction and fully protected by automatic external wall-wetting sprinklers.

(5) Balconies and verandahs — A balcony, verandah or the like and any incorporated supporting part, which is attached to or forms part of a building, need not comply with Table S5C11c, S5C11g, S5C21c, S5C21g, S5C24b or S5C24e if—

  1. it does not form part of the only path of travel to a required exit from the building; and
  2. in Type A construction—
    1. it is situated not more than 2 storeys above the lowest storey providing direct egress to a road or open space; and
    2. any supporting columns are of non-combustible construction.

To permit the use of certain building practices known to provide acceptable levels of fire safety.

S5C6 General concessions

The concessions contained in S5C6(1) allow a steel column to not have an FRL in one and, in some cases, two storey buildings.

The basis for this concession is the low rise of such buildings. In many cases, the columns form the legs of a portal frame, with the roof being non-fire rated. In such a case, there would be little benefit in fire rating the column when the roof beams are not rated.

Because of the importance of the structural integrity of a common wall or fire wall in limiting the spread of fire, the concession for steel columns providing lateral support does not apply.

The concessions contained in S5C6(2) permit a reduced FRL in timber columns in single storey buildings. One method of determining the FRL of a timber column is to use the charring rate of the type of timber in the column.

The structures on a roof referred to in S5C6(3) are not likely to lead to the spread of fire, especially as they are required to be non-combustible. The intent of S5C6(3)(b)(v) is to specify that the concession does not apply to structures that contain units that in turn contain flammable or combustible liquids and gases.

The curtain walls referred to in S5C6(4) must be non-combustible and protected by an external wall-wetting sprinkler system. When such construction is used, protection is provided from fire spreading to the subject building. For the term “curtain wall”, see Schedule 1. For the purposes of this provision, glass is regarded as non-combustible.

Balconies, verandahs and the like do not generally add a significant fire load to a building. Therefore, they are not required to be in compliance with Tables S5C11c, S5C11g, S5C21c, S5C21g, S5C24b or S5C24e. This is provided that occupants are not put at risk during an evacuation because the only means of egress is by way of the balcony, verandah or the like.

Also, if the building is of Type A construction, for the concession to apply the balcony, verandah or the like must be situated at a low level of the building and have non-combustible supports.

(1) This Clause does not apply to a Class 9b building that is a spectator stand or audience viewing area accommodating more than 100 persons as calculated according to D2D18.

(2) A mezzanine and its supports need not have an FRL or be non-combustible provided—

  1. the total floor area of all the mezzanines in the same room does not exceed 1/3 of the floor area of the room or 200 m2, whichever is the lesser; and
  2. the FRL of each wall and column that supports any other part of the building within 6 m of the mezzanine is increased by the amount listed in Table S5C7.
Table S5C7 Increased FRLs — Construction surrounding mezzanines
Level otherwise required for any FRL criterion (mins) Increase in level to not less than (mins)
30 60
60 90
90 120
120 180
180 240
Table Notes

The increase in level applies to each FRL criterion (structural adequacy, integrity or insulation) relevant to the building element concerned.

To provide concessions for small mezzanines.

S5C7 Mezzanine floors: Concession

The S5C7 concession does not apply to certain Class 9b buildings, as specified in S5C7(1). The concession only applies to certain small mezzanines, as specified in S5C7(2).

If it complies with the conditions specified in S5C7(2), a mezzanine and its support may be constructed from materials that do not have an FRL and/or are combustible.

Table S5C7 requires an increase in each FRL criterion of each wall or column that supports any other part of the building, and is within 6 metres of the mezzanine. There is no case in which a building element, with an increased fire rating, requires an FRL greater than 240 minutes.

Increasing the FRLs surrounding a mezzanine which is combustible, or which does not have an FRL, recognises the increased fire load that exists within both the mezzanine and the storey as a whole. This recognises the fire load limiting effect of the minimum area requirement in S5C7(2)(a).

(1) Shaftsrequired to have an FRL must be enclosed at the top and bottom by construction having an FRL not less than that required for the walls of a non-loadbearing shaft in the same building.

(2) The provisions of (1) need not apply to—

  1. the top of a shaft extending beyond the roof covering, other than one enclosing a fire-isolated stairway or ramp; or
  2. the bottom of a shaft if it is non-combustible and laid directly on the ground.

To minimise compromising the fire-resisting performance of a shaft.

S5C8 Enclosure of shafts

Shaft enclosures required to be fire-resisting must be completely fire-separated from all other portions of the building by building elements that have the appropriate fire-resistance.

S5C8 complements other requirements for the walls of shafts by requiring that shafts be enclosed at the top and bottom by fire rated construction.

S5C8 grants exemptions for the top and bottom of shafts in cases where the likelihood of fire entering the shaft is unlikely. This occurs when the top of the shaft is the top of the building (see S5C8(2)(a)), or the bottom of the shaft is laid on the ground (see S5C8(2)(b)).

(1) If a Class 2 building contains not more than 4 storeys of which—

  1. one storey is Class 7 used solely for the purpose of parking motor vehicles or for some other purpose that is ancillary to a Class 2; and
  2. the remaining storeys are of Class 2,

the carpark storey is regarded as Class 2 only for the purpose of determining the relevant fire-resisting requirements of this Specification.

(2) If a Class 3 building or a building of Class 2 and 3 contains not more than 3 storeys of which—

  1. one storey is Class 7 used solely for the purpose of parking motor vehicles or for some other purpose that is ancillary to the other storeys; and
  2. the remaining storeys are of Class 2 or 3,

the carpark storey is regarded as Class 2 or 3 only for the purpose of determining the relevant fire-resisting requirements of this Specification.

To allow the use of residential levels of fire protection to be used for carparks in certain Class 2 and Class 3 buildings.

S5C9 Carparks in Class 2 and 3 buildings

Part A6 classifies a storey used for carparking as Class 7. The fire risks of a single storey carpark in a low-rise Class 2 or Class 3 building are not as substantial as they are in other carparks attached to other classifications, so a concession is suitable. This concession is based upon the assumption that the carpark associated with the Class 2 or 3 building will be for the exclusive use of the building occupants and that the carpark would represent a low fire risk.

The sole purpose of this concession is to allow the carpark and/or ancillary use storey to be regarded as a Class 2 or Class 3 building, as applicable, for the purposes of determining the fire resistance requirements of Specification 5.

This concession applies to buildings which are otherwise wholly Class 2, wholly Class 3 or a mix of Class 2 and 3 and:

  • the storey to which the concession is to applyis used only for carparking, or an ancillary purpose such as storage of normal household items (see S5C9(1)(a) and (2)(a));
  • in the case of Class 2 buildings, contain no more than 4 storeys (see S5C9(1)); and
  • in the case of Class 3 buildings or buildings that are a mix of Class 2 and 3, contain no more than 3 storeys(see S5C9(2)).

The reason for the concession applying to an additional storey in Class 2 buildings is that the residents of these buildings are long term and are usually aware of the building layout and exit routes. This concept is consistent with D2D4.

The S5C9 concession does not apply if the building contains any other classification of building.

(1) In a Class 3 building protected with a sprinkler system complying with Specification 17 and used as a residential care building, any FRL criterion prescribed in Tables S5C11a, S5C11d, S5C11e, S5C11f, S5C11g, S5C21a, S5C21d, S5C21e, S5C21f, S5C21g, S5C24a, S5C24c or S5C24d

  1. for any floor and any loadbearing wall, may be reduced to 60, except any FRL criterion of 90 for an external wall must be maintained when tested from the outside; and
  2. for any non-loadbearing internal wall, need not apply if—
    1. it is lined on each side with standard grade plasterboard not less than 13 mm thick or similar non-combustible material; and
    2. it extends—
      1. to the underside of the floor next above; or
      2. to the underside of a ceiling lined with standard grade plasterboard not less than 13 mm thick or a material with at least an equivalent level of fire protection; or
      3. to the underside of a non-combustible roof covering; and
    3. any insulation installed in the cavity of the wall is non-combustible; and
    4. any construction joint, space or the like between the top of the wall and the floor, ceiling or roof is smoke sealed with intumescent putty or other suitable material.

(2) The concession described at (1) does not apply to fire-protected timber building elements.

To allow concessions for the fire protection of certain building elements in residential care buildings when a suitable sprinkler system is used to achieve an adequate level of occupant safety.

S5C10 Residential care building: Concession

“Residential care building” is defined in Schedule 1.

This concession is a response to concerns expressed by aged care organisations and health authorities in regards to the impact of certain regulatory requirements on the design and operation of aged care hostels and nursing homes.

The requirements for fire separation of individual sole-occupancy units (including self-closing doors) in aged care hostels was considered to impose unwarranted development costs.

Fire compartmentation and the installation of door closers was considered to be impractical in the daily use of an aged care facility. Self-closing fire doors are too heavy and difficult to operate by frail, elderly people. In a number of cases this resulted in the doors being wedged open, thus negating the fire separation.

The limitation of the Class 1b concessions to buildings having an area of 300 m2 or less and 12 occupants or less (see A6G2) meant that those concessions could not be used for many aged care hostels. The concessions in S5C10 are considered to be reasonable for the larger aged care hostels. In some States or Territories it is not acceptable for a Class 1b building to be used to house elderly people or other people who require special care.

The concession contained in S5C10(1)(a) applies to the requirements for floors and loadbearing walls as set out in Tables S5C11a, S5C11d, S5C11e, S5C11f, S5C11g, S5C21a, S5C21d, S5C21e, S5C21f, S5C21g, S5C24a, S5C24c and S5C24d—. The concession, allowing a reduction in FRLs, is limited to where the wall is an internal wall. An external wall is not subject to this concession.

The concession contained in S5C10(1)(b) for non-loadbearing internal walls allows a reduction in FRLs subject to several conditions outlined in S5C10(1)(b). The conditions outlined in S5C10(1)(b) must be achieved for the concession to apply. These conditions require walls to:

  • be lined with 13 mm standard grade plasterboard, or a non-combustible material equivalent to 13 mm standard grade plasterboard (see S5C10(1)(b)(i)); and
  • extend to the underside of the floor above, a ceiling lined with standard grade plasterboard not less than 13 mm thick or equivalent fire protective material,or a non-combustible roof covering. The wall height requirement aims to create a smoke proof wall. This aim requires that joints and the like be sealed to prevent the spread of smoke through potential cracks and openings (see S5C10(1)(b)(ii)).

S5C10(1)(b)(iii) requires that any insulation in a cavity in a non-loadbearing internal wall must be non-combustible. This is to limit the spread of fire by way of the wall cavity.

The mandatory use of non-combustible materials prohibits the lining of non-loadbearing internal walls with timber panelling. This does not restrict the use of timber mouldings and the like.

In addition to the above concessions for load bearing and non-load bearing walls, doors in a Class 3 building must still comply with the requirements of C4D12, and walls must still comply with the requirements of Part F5.

Other provisions relating to residential care buildings are contained throughout the BCA. These include:

  • C4D12, regarding construction bounding sole-occupancy units and public corridors;
  • S20C7(c), regarding warning systems; and
  • Specification 17, regarding sprinkler systems.

Type A Fire-Resisting Construction

(1) In a building required to be of Type A construction—

  1. each building element listed in Tables S5C11a, S5C11b, S5C11c, S5C11d, S5C11e, S5C11f and S5C11g, and any beam or column incorporated in it, must have an FRL not less than that listed in those Tables for the particular class of building concerned; and
  2. any internal wall required to have an FRL with respect to integrity and insulation must extend to—
    1. the underside of the floor next above; or
    2. the underside of a roof complying with Table S5C11g; or
    3. if under S5C15 the roof is not required to comply with Table S5C11g, the underside of the non-combustible roof covering and, except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or
    4. a ceiling that is immediately below the roof and has a resistance to the incipient spread of fire to the roof space between the ceiling and the roof of not less than 60 minutes; and
  3. a loadbearing internal wall and a loadbearing fire wall (including those that are part of a loadbearing shaft) must be constructed from—
    1. concrete; or
    2. masonry; or
    3. subject to (2), fire-protected timber; or
    4. any combination of (i) to (iii); and
  4. the FRLs specified in Table S5C11c for an external column apply also to those parts of an internal column that face and are within 1.5 m of a window and are exposed through that window to a fire-source feature.

(2) For the purposes of (1)(c)(iii), fire-protected timber may be used, provided that—

  1. the building is—
    1. a separate building; or
    2. a part of a building—
      1. which only occupies part of a storey, and is separated from the remaining part by a fire wall; or
      2. which is located above or below a part not containing fire-protected timber and the floor between the adjoining parts is provided with an FRL not less than that prescribed for a fire wall for the lower storey; and
  2. the building has an effective height of not more than 25 m; and
  3. the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification 17; and
  4. any insulation installed in the cavity of the timber building element required to have an FRL is non-combustible; and
  5. cavity barriers are provided in accordance with Specification 9.

(3) For the purposes of Table S5C11a and Table S5C11b, external wall includes any column and other building element incorporated within it or other external building element.

Table S5C11a Type A construction: FRL of loadbearing parts of external walls
Distance from a fire-source feature FRL (in minutes): Structural adequacy/ Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Less than 1.5 m 90/90/90 120/120/120 180/180/180 240/240/240
1.5 to less than 3 m 90/60/60 120/90/90 180/180/120 240/240/180
3 m or more 90/60/30 120/60/30 180/120/90 240/180/90
Table S5C11b Type A construction: FRL of non-loadbearing parts of external walls
Distance from a fire-source feature FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Less than 1.5 m –/90/90 –/120/120 –/180/180 –/240/240
1.5 to less than 3 m –/60/60 –/90/90 –/180/120 –/240/180
3 m or more –/–/– –/–/– –/–/– –/–/–
Table S5C11c Type A construction: FRL of external columns not incorporated in an external wall
Column type FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Loadbearing 90/–/– 120/–/– 180/–/– 240/–/–
Non-loadbearing –/–/– –/–/– –/–/– –/–/–
Table S5C11d Type A construction: FRL of common walls and fire walls
Wall type FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Loadbearing or non-loadbearing 90/90/90 120/120/120 180/180/180 240/240/240
Table S5C11e Type A construction: FRL of loadbearing internal walls
Location FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Fire-resisting lift and stair shafts 90/90/90 120/120/120 180/120/120 240/120/120
Bounding public corridors, public lobbies and the like 90/90/90 120/–/– 180/–/– 240/–/–
Between or bounding sole-occupancy units 90/90/90 120/–/– 180/–/– 240/–/–
Ventilating, pipe, garbage, and like shafts not used for the discharge of hot products of combustion 90/90/90 120/90/90 180/120/120 240/120/120
Table S5C11f Type A construction: FRL of non-loadbearing internal walls
Location FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Fire-resisting lift and stair shafts –/90/90 –/120/120 –120/120 –/120/120
Bounding public corridors, public lobbies and the like –/60/60 –/–/– –/–/– –/–/–
Between or bounding sole-occupancy units –/60/60 –/–/– –/–/– –/–/–
Ventilating, pipe, garbage, and like shafts not used for the discharge of hot products of combustion –/90/90 –/90/90 –/120/120 –/120/120
Table S5C11g Type A construction: FRL of other building elements not covered by Tables S5C11a to S5C11f
Building element FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Other loadbearing internal walls, internal beams, trusses and columns 90/–/– 120/–/– 180/–/– 240/–/–
Floors 90/90/90 120/120/120 180/180/180 240/240/240
Roofs 90/60/30 120/60/30 180/60/30 240/90/60

To specify the fire-resistance level (FRL) and other requirements for building elements in Type A construction.

S5C11 Type A fire-resisting construction — fire-resistance of building elements

Tables S5C11a to S5C11g set out the required FRLs of building elements in a building required to be of Type A construction. The required FRL depends on whether the element is loadbearing or non-loadbearing, if the element comprises or is incorporated in an external wall, and its distance from any fire-source feature.

When using Tables S5C11a to S5C11g, it should be noted that S1C6 permits the deletion of the structural adequacy criteria of an FRL for non-loadbearing elements. The reason for this is that if such an element fails during a fire, there will be no flow-on collapse of other elements. See definition of ‘loadbearing’ in Schedule 1 to assist in understanding this provision.

The surface of an occupiable outdoor area located on a roof should be treated as a floor for the purposes of Specification 5.

S5C11(1)(a) requires building elements to achieve at least the FRLs set out in Tables S5C11a to S5C11g.

S5C11(1)(a) only applies to the building elements listed in Tables S5C11a to S5C11g, and any beams or columns incorporated in such building elements.

S5C11(1)(b) requires internal walls to extend to a barrier to stop or limit the spread of fire over the top of the wall. S5C11(1)(b) only applies to internal walls required to have an FRL with respect to integrity and insulation. This is consistent with the intent that the walls are only required to extend to the underside of a floor or roof, etc when the wall is required to perform a fire separating function.

S5C11(1)(c) requires loadbearing internal walls and loadbearing fire walls (in both cases, including those which are part of a loadbearing shaft) to be of concrete, masonry or constructed from fire-protected timber (however, fire-protected timber has certain limitations).

Internal columns can be exposed to a fire-source feature through a window in an external wall. S5C11(1)(d) requires such a column within 1.5 metres of a window to have the same FRL as an external column.

A floor need not comply with Table S5C11g if—

  1. it is laid directly on the ground; or
  2. in a Class 2, 3, 5 or 9 building, the space below is not a storey, does not accommodate motor vehicles, is not a storage or work area, and is not used for any other ancillary purpose; or
  3. it is a timber stage floor in a Class 9b building laid over a floor having the required FRL and the space below the stage is not used as a dressing room, store room, or the like; or
  4. it is within a sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building; or
  5. it is an open-access floor (for the accommodation of electrical and electronic services and the like) above a floor with the required FRL.

To allow certain floors to not have a fire-resistance level (FRL).

S5C12 Type A fire-resisting construction — concessions for floors

S5C12 grants floors a number of concessions from the FRL requirement. The reason for each of the concessions is listed below:

  • there is no fire load below a floor laid directly on the ground,(see S5C12(a));
  • there is a low fire load if the space below a Class 2, 3, 5 or 9 building is not a storey or does not contain the listed elements, (see S5C12(b));
  • the space belowa stage would generally have a low fire load because it cannot be used as a dressing room, storage area, or the like. A fire in the storey below would not affect the stage because it is over a floor with the required FRL. In addition, the stage would not have a room below which might have a high fire load, (see S5C12(c));
  • the floor is within a residential sole-occupancy unit. This is because resistance to the spread of fire between sole- occupancy units only is required. The levels connected are within the one sole-occupancy unit and the spread of fire from one sole-occupancy unit to another would not be affected by the construction of an internal floor without the required FRL, (see S5C12(d)); and
  • no fire separation is required for an open-access floor as a fire in the storey below could not affect the area because it is over a floor with the required FRL, see S5C12(e).

If a floor in a Class 5 or 9b building is designed for a live load not exceeding 3 kPa—

  1. the floor next above (including floor beams) may have an FRL of 90/90/90; or
  2. the roof, if that is next above (including roof beams), may have an FRL of 90/60/30.

To allow a floor or roof in a Class 5 or Class 9b building to have a reduced fire-resistance level (FRL) if it is above a storey with a lower fire load.

S5C13 Type A fire-resisting construction — floor loading of Class 5 and 9b buildings: Concession

Generally, Class 5 and Class 9b buildings have a comparatively low fire load which can be further reduced if the structural carrying capacity of the floor (“live load” or “imposed action”) is restricted because there will be a lower likelihood of the building containing a high level of stored combustible materials. AS 1170.1 and AS/NZS 1170.1 allows certain areas within office (Class 5) and assembly (Class 9b) buildings to have design floor loads of 3 kPa.

In essence, the lower the structural carrying capacity of the storey’s floor, the lower the fire load. This lower fire load in turn permits a reduced FRL for the floor or roof above such a storey.

The philosophy of fire protection in this provision is that the fire load of a storey controls the FRL of the floor or roof above it. This is because a fire on one storey will affect the level above to a greater degree than itself.

S5C13(a) sets out the concession for a floor above, and S5C13(b) sets out the concession for the roof above.

A roof superimposed on a concrete slab roof need not comply with S5C11 as to fire-resisting construction if—

  1. the superimposed roof and any construction between it and the concrete slab roof are non-combustible throughout; and
  2. the concrete slab roof complies with Table S5C11g.

To allow a non-combustible non-fire-rated roof to be superimposed on a concrete slab roof.

S5C14 Type A fire-resisting construction — roof superimposed on concrete slab: Concession

S5C14 allows a concession for a roof of non-fire-resisting construction to be superimposed above a concrete slab roof. Such roofs are usually used for weather protection reasons.

S5C14(a) states that the superimposed roof and any supporting members must be non-combustible. 

S5C14(b) states that the concrete slab roof must comply with Tables S5C11g

If compliance is achieved with the conditions outlined in S5C14, a concession is reasonable because a fire is unlikely to break through the concrete roof slab.

A roof need not comply with Table S5C11g if its covering is non-combustible and the building—

  1. has a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 installed throughout; or
  2. has a rise in storeys of 3 or less; or
  3. is of Class 2 or 3; or
  4. has an effective height of not more than 25 m and the ceiling immediately below the roof has a resistance to the incipient spread of fire to the roof space of not less than 60 minutes.

To allow the roofs of certain buildings not to have a fire-resistance level (FRL).

S5C15 Type A fire-resisting construction — roof: Concession

The roofs of certain types of buildings can be required to have an FRL to limit the spread of fire from the roof to another building, or from another building to the roof. S5C15 grants a number of concessions by which certain roofs need not have an FRL, provided the roof covering is non-combustible.

In S5C15(a), the BCA assumes that the specified sprinkler system will control any fire prior to it breaking through the roof.

In S5C15(b), the BCA assumes buildings with a rise in storeys of 3 or less will comprise a comparatively low fire risk. Most buildings with a rise in storeys of 3 or less are permitted to be of Type B or Type C construction.

In S5C15(c), the BCA assumes that Class 2 and Class 3 buildings have a relatively low fire load compared to other classifications, and recognises that the potential size of a fire in Class 2 and Class 3 buildings is limited by the bounding construction of the sole-occupancy units. This concession does not apply where another classification forms part of the storey immediately below the roof (e.g. a restaurant, which is Class 6).

S5C15(d) assumes that the incipient spread of fire resistant ceiling will stop or limit the spread of fire to the roof space or roof of the building for sufficient time for it to be brought under control.

If a roof is required to have an FRL or its covering is required to be non-combustible, roof lights or the like installed in that roof must—

  1. have an aggregate area of not more than 20% of the roof surface; and
  2. be not less than 3 m from—
    1. any boundary of the allotment other than the boundary with a road or public place; and
    2. any part of the building which projects above the roof unless that part has the FRL required of a fire wall and any openings in that part of the wall for 6 m vertically above the roof light or the like are protected in accordance with C4D5; and
    3. any roof light or the like in an adjoining sole-occupancy unit if the walls bounding the unit are required to have an FRL; and
    4. any roof light or the like in an adjoining fire-separated section of the building; and
  3. if a ceiling with a resistance to the incipient spread of fire is required, be installed in a way that will maintain the level of protection provided by the ceiling to the roof space.

To permit roof lights or the like in a roof that is required to either have an FRL or have a non-combustible covering.

S5C16 Type A fire-resisting construction — roof lights

The roofs of certain types of building can be required to have an FRL, or to be of non-combustible construction, to limit the spread of fire from the roof to another building. This is particularly the case with a high rise building. S5C16 specifies the requirements for such roof lights.

The requirements of S5C16 aim to minimise the risk that fire will spread by way of roof lights:

  • from another building on an adjoining allotment;
  • to an adjoining sole-occupancy unit; or
  • to an adjoining fire compartment or fire-separated part of the building.

S5C16 facilitates this aim by minimising the:

  • roof area which can be comprised of roof lights (see S5C16(a));
  • distance a roof light is from an allotment boundary (see S5C16(b)(i));
  • distance a roof light is from unprotected parts of the building which are higher than the roof (see S5C16(b)(ii));
  • distance a roof light is from roof lights or the like in adjoining sole-occupancy units, if the bounding walls are required to have an FRL (see S5C16(b)(iii)); and
  • distance a roof light is from any roof light or the like in adjoining fire-separated parts of the building (see S5C16(b)(iv)).

In some cases, the BCA requires incipient spread of fire resistant ceilings to stop or limit the spread of a fire to the roof space.

S5C16(c) requires that roof lights be installed in a manner which will maintain the requisite level of protection. This is an example of a “performance-type” provision within the Deemed-to-Satisfy Provisions. This is because a ceiling that has resistance to the incipient spread of fire is tested in the horizontal plane.

If roof lights are installed in a building, it may be necessary to install part of the ceiling in the vertical plane to connect the roof light with the ceiling below. Where this occurs, it may be necessary for a building proponent to provide evidence to an appropriate authority that the method proposed will meet the requirements of S5C16(c).

However, in this case, if the material is installed on a vertical plane yet complies in all other respects with the tested prototype, it is unlikely that the ceiling’s fire performance will be affected.

For a building with an effective height of not more than 25 m and having a roof without an FRL in accordance with S5C15, in the storey immediately below that roof, internal columns other than those referred to in S5C11(1)(d) and internal walls other than fire walls and shaft walls may have—

  1. in a Class 2 or 3 building: FRL 60/60/60; or
  2. in a Class 5, 6, 7, 8 or 9 building—
    1. with rise in storeys exceeding 3: FRL 60/60/60; or
    2. with rise in storeys not exceeding 3: no FRL.

To allow lower fire-resistance levels (FRLs) for internal columns and walls which only support a non-fire-resisting roof.

S5C17 Type A fire-resisting construction — internal columns and walls: Concession

In the storey immediately below the roof, under circumstances specified in S5C17, it is permissible to reduce or (in some cases) delete the FRL of:

  • columns, other than those in that are:
    • within 1.5 metres of a window;
    • face that window; and
    • exposed to a fire-source feature through that window; and
  • internal walls, other than fire walls and shaft walls.

S5C17 does not negate the need for internal columns to have the same FRL as an external column (set out in S5C11(1)(d)) where that internal column is:

  • within 1.5 metres of a window;
  • faces that window; and
  • exposed to a fire-source feature through that window.

In an open spectator stand or indoor sports stadium, the following building elements need not have the FRL specified in Tables S5C11a, S5C11b, S5C11c, S5C11e and S5C11g:

  1. The roof if it is non-combustible.
  2. Columns and loadbearing walls supporting only the roof if they are non-combustible.
  3. Any non-loadbearing part of an external wall less than 3 m—
    1. from any fire-source feature to which it is exposed if it has an FRL of not less than –/60/60 and is non-combustible; or
    2. from an external wall of another open spectator stand if it is non-combustible.

To allow lower fire-resistance levels (FRLs) for building elements in open spectator stands and indoor sports stadiums.

S5C18 Type A fire-resisting construction — open spectator stands and indoor sports stadiums: Concession

The S5C18 concession is based on the BCA’s overall assumption that there is generally a lower risk to the occupants of open spectator stands and indoor sports stadiums than in other buildings. The reasons for this concession are that:

  • an open spectator stand generally has a low fire load, even though it may have a high population, particularly during an event, and is open at the front, facilitating the ventilation of smoke and heat; and
  • in most indoor sports stadiums large areas are usually inaccessible to the public (being taken up as part of the sporting events) and the finishes are generally spartan.

See Schedule 1 for definition of “open spectator stand”.

(1) Notwithstanding S5C11, a carpark may comply with this clause if it is an open-deck carpark or is protected with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and is—

  1. a separate building; or
  2. a part of a building—
    1. which only occupies part of a storey, and is separated from the remaining part by a fire wall; or
    2. which is located above or below another classification, and the floor separating the classifications complies with C3D10; or
    3. which is located above another Class 7 part of the building not used for carparking, and the floor separating the parts complies with Table S5C11g for a Class 7 part other than a carpark; or
    4. which is located below another Class 7 part of the building not used for carparking, and the floor separating the parts complies with this clause.

(2) For the purposes of this clause, a carpark

  1. includes—
    1. an administration area associated with the functioning of the carpark; and
    2. where the carpark is sprinklered, is associated with a Class 2 or 3 building and provides carparking for separate sole-occupancy units, each carparking area with an area not greater than 10% of its floor area for purposes ancillary to the sole-occupancy units; but
  2. excludes—
    1. except for (a), any area of another classification, or other part of a Class 7 building not used for carparking; and
    2. a building or part of a building specifically intended for the parking of trucks, buses, vans and the like.

(3) For building elements in a carpark as described in (1) and (2), the following minimum FRLs are applicable:

  1. External wall:
    1. Less than 3 m from a fire-source feature to which it is exposed:
      1. Loadbearing: 60/60/60.
      2. Non-loadbearing: –/60/60.
    2. 3 m or more from a fire-source feature to which it is exposed: –/–/–.
  2. Internal wall:
    1. Loadbearing, other than one supporting only the roof (not used for carparking): 60/–/–.
    2. Supporting only the roof (not used for carparking): –/–/–.
    3. Non-loadbearing: –/–/–.
  3. Fire wall:
    1. From the direction used as a carpark: 60/60/60.
    2. From the direction not used as a carpark: as required by Table S5C11d.
  4. Columns:
    1. Supporting only the roof (not used for carparking) and 3 m or more from a fire-source feature to which it is exposed: –/–/–.
    2. Steel column, other than one covered by (i) and one that does not support a part of a building that is not used as a carpark
      1. 60/–/–; or
      2. an ESA/M of not greater than 26m2/tonne.
    3. Any other column not covered by (i) or (ii): 60/–/–.
  5. Beams:
    1. Steel floor beam in continuous contact with a concrete floor slab—
      1. 60/–/–; or
      2. an ESA/M of not greater than 30m2/tonne.
    2. Any other beam: 60/–/–.
  6. Fire-resisting lift and stair shaft (within the carpark only): 60/60/60.
  7. Floor slab and vehicle ramp: 60/60/60.
  8. Roof (not used for carparking): –/–/–.

(4) For the purposes of sub-clause (3):

  1. ESA/M means the ratio of exposed surface area to mass per unit length.
  2. Refer to Specification 17 for special requirements for a sprinkler system in a carpark complying with (3) and located within a multi-classified building.

To allow lower fire-resistance levels (FRLs) for building elements in open-deck or sprinklered carparks.

S5C19 Type A fire-resisting construction — carparks

S5C19 is based on experimental research carried out at the BHP Research Laboratories. The research included full-scale fire tests on open-deck and enclosed carparks, and was supplemented by extensive overseas testing.

The research showed that the S5C19 FRLs will not lead to an unsafe situation or structural failure of a building element in an open-deck carpark, or an enclosed carpark, which is sprinkler protected.

See Schedule 1 for definition of “carpark”. S5C19(2) refines this definition when the expression is used in S5C19.

Inclusions

S5C19 concessions include:

  • a building which solely comprises a carpark (see S5C19(1)(a));
  • the carpark section of a building which, in part, has another use, and where the carpark and that use are fire-separated as required in S5C19(1)(b)(i) to (iv) (regardless of the classification of that use, or whether that use is next to, above or below the carpark) (see S5C19(1)(b));
  • any administrative area associated with the carpark, such as ticket selling and fee collection areas (see S5C19(2)(a)(i)); and
  • in a sprinkler protected carpark, small areas ancillary to a Class 2 or Class 3 building, such as part of the carpark used for normal ‘household’ storage (see S5C19(2)(a)(ii)).

Exclusions

S5C19 concessions exclude:

  • any area of another Class (see S5C19(2)(b)(i));
  • another Class7 use (i.e. other than carparking) (see S5C19(2)(b)(i)); and
  • an area “specifically intended” for the parking of vehicles such as trucks, buses, vans and the like (see S5C19(2)(b)(ii)).

S5C19, while using a refined definition of “carpark”, also use the undefined expression “carparking”. This word specifically refers to the parking of cars. This is also the intention of refining the definition of “carpark” as expressed by the use of the words “specifically intended” in S5C19(2)(b)(ii).

The purpose of refining this definition, which is to limit the concessions in S5C19(3) to areas used for the parking of lighter vehicles (that is, vehicles other than commercial trucks, vans, buses and the like), rather than simply limiting them to areas used for the parking of cars only.

Accordingly, it would seem contrary to the purpose of this clause to exclude from the refined definition and the word “carparking” such vehicles as motor bikes, van-like family vehicles, non-commercial panel vans, and smaller non- commercial utilities.

S5C19(3) permits building elements to have either a specified FRL or a specified surface area to mass ratio. In relation to columns and beams, S5C19(3) does not require them to have an FRL if they have the specified surface area to mass ratio. Some authorities refer to this ratio as the “heat sink effect”,in that the lower the exposed surface area to mass ratio, the lower will be the member temperature for a given fire.

The concession of S5C19(3) relating to columns, only applies to columns of any material which support a roof which is not used for carparking, and located 3 metres or more from a fire-source feature to which they are exposed.

The concession of S5C19(3)(d)(ii) only applies to steel columns which support a roof which is used for carparking, and/or located less than 3 metres from a fire-source feature to which they are exposed. This concession is not applicable if the steel columns support any other part of the building which is not used as a carpark.

In the S5C19(3)(h) relating to roofs, there is a concession for roofs that are not used for carparking.

A roof used for carparking must comply with any relevant requirements of S5C19 (e.g. those relating to floor slabs).

Examples

The concession of S5C19(3)(d)(ii) does not apply if the column supports a part of the building specifically intended for the parking of trucks, buses,vans, and the like.

(1) In a Class 2 or 3 building with a rise in storeys of not more than 3—

  1. notwithstanding C2D10(1) and (2) and C3D7, timber framing may be used for—
    1. external walls; and
    2. common walls; and
    3. the floor framing of lifts pits; and
    4. non-loadbearing internal walls which are required to be fire-resisting; and
    5. non-loadbearing shafts, except shafts used for the discharge of hot products of combustion; and
    6. spandrels or horizontal construction provided for the purposes of C3D7; and
  2. notwithstanding S5C11(1)(c), for loadbearing internal walls and loadbearing fire walls
    1. timber framing may be used; and
    2. non-combustible materials may be used; and
  3. notwithstanding S5C3(1)(c), timber framing may be used for a part of a building that provides support to a part of a building constructed of timber framing or non-combustible material in accordance with (a) and (b).

(2) A Class 2 or 3 building having a rise in storeys of not more than 4 may have the top three storeys constructed in accordance with (1) provided—

  1. the lowest storey is used solely for the purpose of parking motor vehicles or for some other ancillary purpose; and
  2. the lowest storey is constructed of concrete or masonry including the floor between it and the Class 2 or 3 part of the building above; and
  3. the lowest storey and the storey above are separated by construction having an FRL of not less than 90/90/90 with no openings or penetrations that would reduce the fire-resisting performance of that construction except that a doorway in that construction may be protected by a –/60/30 self-closing fire door.

(3) In a Class 2 or 3 building complying with (1) or (2) and fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17, any FRL criterion prescribed in Tables S5C11a, S5C11d, S5C11e, S5C11f and S5C11g

  1. for any floor and any loadbearing wall, may be reduced to 60, except any FRL criterion of 90 for an external wall must be maintained when tested from the outside; and
  2. for any non-loadbearing internal wall, need not apply if—
    1. it is lined on each side with 13 mm standard grade plasterboard or similar non-combustible material; and
    2. it extends—
      1. to the underside of the floor next above; or
      2. to the underside of a ceiling with a resistance to the incipient spread of fire of 60 minutes; or
      3. to the underside of a non-combustible roof covering; and
    3. any insulation installed in the cavity of the wall is non-combustible; and
    4. any construction joint, space or the like between the top of the wall and the floor, ceiling or roof is smoke sealed with intumescent putty or other suitable material; and
    5. any doorway in the wall is protected by a self-closing, tight fitting, solid core door not less than 35 mm thick.

To allow low-rise Class 2 and 3 buildings which are required to be of Type A construction to be constructed with timber framing and/or non-combustible materials.

S5C20 Type A fire-resisting construction — Class 2 and 3 buildings: Concession

S5C20 results from research undertaken by the National Association of Forest Industries and Forest and Wood Products Australia, which have been confirmed by overseas studies.

S5C20 provides a concession to S5C11(1)(c) and also to the combustibility requirements of C2D10(1), (2) and C3D7 to allow, subject to specified conditions, the use in certain Class 2 and 3 buildings, timber framing instead of an alternative structural support system using non-combustible materials, concrete, or masonry.

In addition to timber framing, S5C20(1)(a)(ii) allows the use of non-combustible materials (such as steel) for fire walls and internal walls required to be fire resisting, instead of concrete or masonry as required by S5C11(1)(c).

For the purposes of this concession “framing” includes bracing components. However, a cladding element (despite providing nominal bracing) cannot be considered “framing” for the purposes of this concession.

S5C20(2) allows the top three storeys of a four storey Class 2 or 3 building to be constructed with timber framing and/or non-combustible materials if they are located above a single storey used for vehicle parking (note that the limitation in S5C19 by use of the word “carparking” does not apply here) and ancillary purposes. These ancillary purposes include such items as individual storerooms, laundries, and the like.

To achieve this concession, the lowest carparking storey (including the floor/ceiling between the carpark and the storey above) must be constructed of concrete or masonry, and have the FRLs specified in Tables S5C11a to S5C11g, or reduced by S5C20(3). The floor between the carpark and the storey above must not contain penetrations or openings that would reduce the fire-resisting performance of the floor. The exception to this is a door which is permitted to be a –/60/30 self- closing fire door.

Under the S5C9 concession, the vehicle parking storey can be classified as a Class 2 or 3 building for the purpose of determining the relevant fire-resisting requirements of Specification 5.

The basis of the S5C20(2) concession is that the concrete or masonry floor of the first storey above the lowest carparking storey will provide adequate fire separation. S5C20 does not require smoke detectors or sprinklers in the lowest carparking storey because a fire occurring in it should not pose an unacceptable risk to occupants evacuating from the upper three storeys.

Compliance must still be achieved with the other requirements of Specification 5 and otherparts of the BCA, including the relevant FRLs listed in Tables S5C11a to S5C11g, and any relevant requirements of E1D4.

Subject to the conditions listed, including the installation of a sprinkler system, S5C20 allows:

  • a reduction of the FRL of loadbearing walls (see S5C20(3)(b)); and
  • the deletion of the FRL for non-loadbearing internal walls (see S5C20(3)(b)).

Reference to S17C2 indicates one of the technical standards that the sprinkler system may comply with is AS 2118.4— Automatic fire sprinkler systems—Residential. This Standard has been specifically developed to provide a degree of life safety and property protection for occupants of low-rise Class 2 and 3 buildings. If the storey used as carpark requires sprinklers by E1D4, then the carpark is considered a Class 7 building for the purposes of applying Specification 17 (see E1D4).

S5C20(3)(b) allows non-loadbearing internal walls to have no FRL. The concession is subject to the requirement that the internal walls be lined on each side with 13 mm standard grade plasterboard or non-combustible materials with a similar fire-resisting performance. This means that all doors from sole-occupancy units to corridors, when applying these concessions, must be smoke proof doors. Self-closing solid core doors satisfy this requirement (see Specification 12).

The S5C20(3)(b)(ii) provision regarding the height of a non-loadbearing wall, to which this concession is applied, aims to create a smoke proof wall, hence the requirement for sealing any cracks and openings against the spread of smoke.

The S5C20(3)(b)(iii) requirement that only non-combustible insulation can be used in a cavity in a non-loadbearing wall, to which this concession is applied, aims to limit the spread of fire by way of the cavity.

Type B Fire-Resisting Construction

(1) In a building required to be of Type B construction—

  1. each building element listed in Tables S5C21a, S5C21b, S5C21c, S5C21d, S5C21e, S5C21f and S5C21g, and any beam or column incorporated in it, must have an FRL not less than that listed in the Tables for the particular class of building concerned; and
  2. if a stair shaft supports any floor or a structural part of it—
    1. the floor or part must have an FRL of 60/–/– or more; or
    2. the junction of the stair shaft must be constructed so that the floor or part will be free to sag or fall in a fire without causing structural damage to the shaft; and
  3. any internal wall which is required to have an FRL with respect to integrity and insulation, except a wall that bounds a sole-occupancy unit in the topmost (or only) storey and there is only one unit in that storey, must extend to—
    1. the underside of the floor next above if that floor has an FRL of at least 30/30/30; or
    2. the underside of a ceiling having a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
    3. the underside of the roof covering if it is non-combustible and, except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or
    4. 450 mm above the roof covering if it is combustible; and
  4. a loadbearing internal wall and a loadbearing fire wall (including those that are part of a loadbearing shaft) must be constructed from—
    1. concrete; or
    2. masonry; or
    3. subject to (2), fire-protected timber; or
    4. any combination of (i) to (iii); and
  5. in a Class 5, 6, 7, 8 or 9 building, in the storey immediately below the roof, internal columns and internal walls other than fire walls and shaft walls, need not comply with Tables S5C21e, S5C21f and S5C21g; and
  6. in a Class 2 or 3 building, except where within the one sole-occupancy units, or a Class 9a health-care building or a Class 9b building, a floor separating storeys or above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, must—
    1. be constructed so that it is at least of the standard achieved by a floor/ceiling system incorporating a ceiling which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
    2. have an FRL of at least 30/30/30; or
    3. have a fire-protective covering on the underside of the floor, including beams incorporated in it, if the floor is combustible or of metal; and
  7. in a Class 9c building a floor above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor must—
    1. be constructed so that it is at least of the standard achieved by a floor/ceiling system incorporating a ceiling which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
    2. have an FRL of at least 30/30/30; or
    3. have a fire-protective covering on the underside of the floor, including beams incorporated in it, if the floor is combustible or of metal.

(2) For the purposes of (1)(d)(iii), fire-protected timber may be used, provided that—

  1. the building is—
    1. a separate building; or
    2. a part of a building—
      1. which only occupies part of a storey, and is separated from the remaining part by a fire wall; or
      2. which is located above or below a part not containing fire-protected timber and the floor between the adjoining parts is provided with an FRL not less than that prescribed for a fire wall for the lower storey; and
  2. the building has an effective height of not more than 25 m; and
  3. the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification 17; and
  4. any insulation installed in the cavity of the timber building element required to have an FRL is non-combustible; and
  5. cavity barriers are provided in accordance with Specification 9.

(3) For the purposes of Table S5C21a and Table S5C21b, external wall includes any column and other building element incorporated within it or other external building element.

Table S5C21a Type B construction: FRL of loadbearing parts of external walls
Distance from a fire-source feature FRL (in minutes) Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Less than 1.5 m 90/90/90 120/120/120 180/180/180 240/240/240
1.5 to less than 3 m 90/60/30 120/90/60 180/120/90 240/180/120
3 m to less than 9 m 90/30/30 120/30/30 180/90/60 240/90/60
9 m to less than 18 m 90/30/– 120/30/– 180/60/– 240/60/–
18 m or more –/–/– –/–/– –/–/– –/–/–
Table S5C21b Type B construction: FRL of non-loadbearing parts of external walls
Distance from a fire-source feature FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Less than 1.5 m –/90/90 –/120/120 –/180/180 –/240/240
1.5 m to less than 3 m –/60/30 –/90/60 –/120/90 –/180/120
3 m or more –/–/– –/–/– –/–/– –/–/–
Table S5C21c Type B construction: FRL of external columns not incorporated in an external wall
Distance from a fire-source feature FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Loadbearing column — less than 18 m 90/–/– 120/–/– 180/–/– 240/–/–
Loadbearing column — 18 m or more –/–/– –/–/– –/–/– –/–/–
Non-loadbearing column –/–/– –/–/– –/–/– –/–/–
Table S5C21d Type B construction: FRL of common walls and fire walls
Wall type FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Loadbearing or non-loadbearing 90/90/90 120/120/120 180/180/180 240/240/240
Table S5C21e Type B construction: FRL of loadbearing internal walls
Location FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Fire-resisting lift and stair shafts 90/90/90 120/120/120 180/120/120 240/120/120
Bounding public corridors, public lobbies and the like 60/60/60 120/–/– 180/–/– 240/–/–
Between or bounding sole-occupancy units 60/60/60 120/–/– 180/–/– 240/–/–
Table S5C21f Type B construction: FRL of non-loadbearing internal walls
Location FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Fire-resisting lift and stair shafts –/90/90 –/120/120 –/120/120 –/120/120
Bounding public corridor, public lobbies and the like –/60/60 –/–/– –/–/– –/–/–
Between or bounding sole-occupancy units –/60/60 –/–/– –/–/– –/–/–
Table S5C21g Type B construction: FRL of other building elements not covered by Tables S5C21a to S5C21f
Building element FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Other loadbearing internal walls and columns 60/–/– 120/–/– 180/–/– 240/–/–
Roofs –/–/– –/–/– –/–/– –/–/–

To specify the fire-resistance level (FRL) and other requirements of building elements in Type B construction.

S5C21 Type B fire-resisting construction — fire-resistance of building elements

Tables S5C21a to S5C21fg set out the required FRLs of building elements in a building required to be of Type B construction. The required FRL depends on whether the element is loadbearing or non-loadbearing, if the element comprises or is incorporated in an external wall, and its distance from any fire-source feature to which it is exposed.

Although a roof is an external building element that can be exposed to a fire-source feature, it is not required to comply with the FRLs specified under the heading of external wall in Table S5C21a and Table S5C21b. The FRLs required for a roof are contained under the heading of roofs near the bottom of Table S5C21f.

When using Tables S5C21a to S5C21f, it should be noted that Clause S1C6 of Specification 1 permits the deletion of the structural adequacy criterion of an FRL for non-loadbearing elements. The reason for this is that if such an element fails during a fire, there will be no flow-on collapse of other elements. See Schedule 1 for the definition of “loadbearing”.

Generally speaking, Type B construction differs from Type A construction by allowing lower FRLs for external walls, generally not requiring roofs and floors to have an FRL, and not requiring FRLs for ventilation, garbage, and similar shafts.

These differences are based on the lower rise in storeys allowed by Table C2D2; and the smaller size of Type B construction buildings allowed by Table C3D3.

The BCA requires the floors of buildings required to be of Type B construction to have an FRL in Class 2 and Class 3 buildings, if the floor supports different sole-occupancy units (see S5C21(1)(f)), in Class 9a buildings as part of the fire compartments required by C3D6(1) and in Class 9c buildings as part of the fire compartments required by C3D6(3).

S5C21(1)(a) requires building elements to achieve at least the FRLs set out for them in Tables S5C21a to S5C21g. S5C21(1)(a) only applies to the building elements listed in Tables S5C21a to S5C21g, and any beams or columns incorporated in such building elements.

S5C21(1)(b) requires stair shafts which support floors or structural parts of floors to either have a specified FRL, or be constructed at the junction of the shaft and floor (or part of floor), so that if the floor falls or collapses (fully or partly) during a fire, the shaft will not be damaged.

S5C21(1)(c) requires internal walls to extend to a barrier to stop or limit the spread of fire over the top of the wall. Such a requirement is not considered necessary when a sole-occupancy unit occupies the whole of the top storey. This concession applies to buildings of Type B construction. S5C21(1)(c) only applies to internal walls required to have an FRL with respect to integrity and insulation. This is consistent with the intent that the walls are only required to extend to the underside of a floor or roof, etc when the wall is required to perform a fire separating function.

S5C21(1)(d) requires loadbearing internal walls and loadbearing fire walls (in both cases, including those which are part of a loadbearing shaft) to be of concrete, masonry or constructed from fire-protected timber (however, fire-protected timber has certain limitations).

Under S5C21(1)(e), internal columns and internal walls need not comply with Tables S5C21ato S5C21g if they are:

  • in a Class 5–9 building;
  • in the storey immediately below the roof; and
  • not fire walls or shaft walls.

S5C21(1)(f) does not apply if the storeys being separated are within a sole-occupancy unit of a Class 2 or 3 building, because it is likely that the two levels are connected by a non-fire-isolated stairway.

The primary reason for the S5C21(1)(f) fire separation requirement is that in a building fire, the highest degree of risk is attached to such people as the very young, people with disabilities, the elderly, and those who are asleep.

Table S5C21e requires internal walls bounding a stair required to be rated to have an FRL of 60/60/60. The reason for this is because although Table C2D2 only allows buildings of Type C construction to have a maximum rise is storeys of 2, such buildings may include a basement which is not included in the calculation of rise in storeys. If a stairway in the building connects say a basement with two other storeys, in accordance with D2D4, a fire-isolated exit would be required. Table S5C21e then sets out the required FRL for the walls of the stairway.

Examples

Buildings, which must comply with S5C21(1)(f), include:

  • A Class 2 building (which includes flats, apartments, etc).
  • A Class 3 building (which includes hotels, motels,etc).
  • The residential part of a school.
  • Accommodation for the aged, children or people with disabilities.
  • A residential aged care building.
  • A Class 9a building (which includes hospitals, etc).
  • A Class 9b building, such as schools, theatres, and the like.

(1) Notwithstanding S5C21, a carpark may comply with this clause if it is an open-deck carpark or is protected with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and is—

  1. a separate building; or
  2. a part of a building, and if occupying only part of a storey, is separated from the remaining part by a fire wall.

(2) For the purposes of this clause, a carpark

  1. includes—
    1. an administration area associated with the functioning of the carpark; and
    2. where the carpark is sprinklered, is associated with a Class 2 or 3 building and provides carparking for separate sole-occupancy units each carparking area with an area not greater than 10% of its floor area for purposes ancillary to the sole-occupancy units; but
  2. excludes—
    1. except for (a), any area of another classification, or other part of a Class 7 building not used for carparking; and
    2. a building or part of a building specifically intended for the parking of trucks, buses, vans and the like.

(3) For building elements in a carpark as described in (1) and (2), the following minimum FRLs are applicable:

  1. External walls:
    1. Less than 3 m from a fire-source feature to which it is exposed:
      1. Loadbearing: 60/60/60.
      2. Non-loadbearing:–/60/60.
    2. 3 m or more from a fire-source feature to which it is exposed: –/–/–.
  2. Internal walls:
    1. Loadbearing, other than one supporting only the roof (not used for carparking): 60/–/–.
    2. Supporting only the roof (not used for carparking): –/–/–.
    3. Non-loadbearing: –/–/–.
  3. Fire walls:
    1. From the direction used as a carpark: 60/60/60.
    2. From the direction not used as a carpark: as required by Table S5C21d.
  4. Columns:
    1. Supporting only the roof (not used for carparking) and 3 m or more from a fire-source feature to which it is exposed: –/–/–.
    2. Steel column, other than one covered by (i) and one that does not support a part of a building that is not used as a carpark
      1. 60/–/–; or
      2. an ESA/M of not greater than 26 m2/tonne.
    3. Any other column not covered by (i) or (ii): 60/–/–.
  5. Beams:
    1. Steel floor beam less than 3 m from a fire-source feature in continuous contact with a concrete floor slab—
      1. 60/–/–; or
      2. an ESA/M of not greater than 30 m2/tonne.
    2. Any other beam less than 3 m from a fire-source feature: 60/–/–.
    3. Any beam 3 m or more from a fire-source feature: –/–/–.
  6. Lift shaft: –/–/–.
  7. Fire-resisting stair shaft (within the carpark only): 60/60/60.
  8. Roof, floor slab and vehicle ramp: –/–/–.

(4) For the purposes of (3), ESA/M means the ratio of exposed surface area to mass per unit length.

To allow lower fire-resistance levels (FRLs) for building elements in open-deck or sprinklered carparks.

S5C22 Type B fire-resisting construction — carparks

S5C22 is based on experimental research carried out at the BHP Research Laboratories. The research included full scale fire tests on both open-deck and enclosed carparks, and was supplemented by extensive overseas testing.

The research carried out on this matter showed that the S5C22 FRLs will not lead to an unsafe situation or structural failure of a building element in an open-deck carpark, or an enclosed carpark which is sprinkler protected.

See Schedule 1 for definition of “carpark”. S5C22(2) refines this definition when the expression is used in S5C22.

Inclusions and exclusions

S5C22 concessions include:

  • a building which solely comprises a carpark;
  • the carpark section of a building which elsewhere has another use;
  • any administrative area associated with the carpark, such as ticketselling and fee collection areas; and
  • in a sprinkler protected carpark, small areas ancillary to a Class 2 or Class 3 building, such as part of the carpark used for normal “household” storage.

S5C22 concessions exclude:

  • any area of another class;
  • another Class 7 use (i.e. other than carparking); and
  • an area “specifically intended” for the parking of vehicles such as trucks, buses, vans and the like.

S5C22, while using a refined definition of “carpark”, also use the undefined expression “carparking”. This word specifically refers to the parking of cars. This is also the intention of refining the definition of “carpark” as expressed by the use of the words “specifically intended” in S5C22(2)(b)(ii).

However, in applying these provisions, it is important to consider the purpose of refining this definition, whichis to limit the concessions in S5C22 to areas used for the parking of lighter vehicles — that is, vehicles other than commercial trucks, vans, buses and the like — rather than simply limiting them to areas used for the parking of cars only.

Accordingly, it would seem contrary to the purpose of this clause to exclude from the refined definition and the word “carparking” such vehicles as motor bikes, van-like family vehicles, non-commercial panel vans, and smaller non- commercial utilities.

Regarding certain types of column and beam, S5C22 permits them to have either a specified FRL or a specified surface area to mass ratio. In other words, in relation to these columns and beams, S5C22 does not require them to have an FRL if they have the specified surface area to mass ratio. Some authorities refer to this ratio as the “heat sink effect”, in that the lower the exposed surface area to mass ratio, the lower will be the member temperature for a given fire.

The concession for columns in S5C22(3)(d) applies to columns of any material which support a roof which is not used for carparking, and located 3 metres or more from a fire-source feature to which they are exposed.

The concession in S5C22(3)(d) only applies to steel columns that support a roof which is used for carparking, and/or located less than 3 metres from a fire-source feature to which they are exposed.This concession is also applicable where steel columns support any other part of the building that is not used as a carpark.

For the purposes of this clause,the usual definition of “carpark” is specifically amended (see S5C22(2)).

S5C19 provisions restricting the roof concession to those roofs that are not used for carparking does not apply to S5C22.

The differences between S5C22 and S5C19 are based on the lower rise in storeys allowed for Type B construction buildings by Table C2D2.

Examples

The concession of S5C22(3)(d) in the columns section of S5C22(3) does not apply if the column supports a part of the building specifically intended for the parking of trucks, buses, vans, and the like.

(1) In a Class 2 or 3 building with a rise in storeys of not more than 2—

  1. notwithstanding C2D10(1) and (2), timber framing may be used for—
    1. external walls; and
    2. common walls; and
    3. the floor framing of lifts pits; and
    4. non-loadbearing internal walls which are required to be fire-resisting; and
    5. non-loadbearing shafts, except shafts used for the discharge of hot products of combustion; and
  2. notwithstanding S5C21(1)(d), for loadbearing internal walls and loadbearing fire walls
    1. timber framing may be used; and
    2. non-combustible materials may be used; and
  3. notwithstanding S5C3(1)(c), timber framing may be used for a part of a building that provides support to a part of a building constructed of timber framing or non-combustible material in accordance with (a) and (b).

(2) A Class 2 or 3 building having a rise in storeys of not more than 2 may have the top storey constructed in accordance with (1) provided—

  1. the lowest storey is used solely for the purpose of parking motor vehicles or for some other ancillary purpose; and
  2. the lowest storey is constructed of concrete or masonry including the floor between it and the Class 2 or 3 part of the building above; and
  3. the lowest storey and the storey above are separated by construction having an FRL of not less than 90/90/90 with no openings or penetrations that would reduce the fire-resisting performance of that construction except that a doorway in that construction may be protected by a –/60/30 self-closing fire door.

(3) In a Class 2 or 3 building complying with (1) or (2) and fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17, any FRL criterion prescribed in Tables S5C21a, S5C21d, S5C21e, S5C21f and S5C21g; and —

  1. for any loadbearing wall, may be reduced to 60, except any FRL criterion of 90 for an external wall must be maintained when tested from the outside; and
  2. for any non-loadbearing internal wall, need not apply, if—
    1. it is lined on both sides with 13 mm standard grade plasterboard or similar non-combustible material; and
    2. it extends—
      1. to the underside of the floor next above if that floor has an FRL of at least 30/30/30 or is lined on the underside with a fire-protective covering; or
      2. to the underside of a ceiling with a resistance to the incipient spread of fire of 60 minutes; or
      3. to the underside of a non-combustible roof covering; and
    3. any insulation installed in the cavity of the wall is non-combustible; and
    4. any construction joints, spaces and the like between the top of the wall and the floor, ceiling or roof is smoke sealed with intumescent putty or other suitable material.

To allow low-rise Class 2 and 3 buildings which are required to be of Type B construction to be constructed with timber framing and/or non-combustible materials.

S5C23 Type B fire-resisting construction — Class 2 and 3 buildings: Concession

S5C23 results from research undertaken by the National Association of Forest Industries and Forest and Wood Products Australia, which have been confirmed by overseas studies.

S5C23 provides a concession to S5C21(1)(d) and also to the combustibility requirements of C2D10(1) and (2) to allow, subject to specified conditions, the use in certain Class 2 and 3 buildings, timber framing instead of an alternative structural support system using non-combustible materials, or concrete, or masonry.

In addition to timber framing, S5C23(1) allows the use of non-combustible materials (such as steel) for fire walls and internal walls required to be fire-resisting, instead of concrete or masonry as required by S5C21(1)(d).

For the purposes of this concession “framing” includes bracing components. However, a cladding element (despite providing nominal bracing) cannot be considered “framing” for the purposes of this concession.

Table C2D2 limits Class 2 and 3 buildings of Type B construction to a rise in storeys of two. For this reason S5C23 only applies to two storey Class 2 and 3 buildings, and no concession is allowed for a two storey timber framed building above a concrete or masonry lower storey, as is allowed in the case of Type A construction buildings by S5C20.

S5C23(2) allows a 2 storey Class 2 or 3 building to be constructed with timber framing and/or non-combustible materials if the lowest storey is used for vehicle parking (note that the limitation in S5C22 by use of the word “carparking” does not apply here) and ancillary purposes. These ancillary purposes include such items as individual storerooms, laundries, and the like.

To achieve this concession, the lowest carparking storey (including the floor/ceiling between the carpark and the storey above) must be constructed of concrete or masonry, and have the FRLs specified in Tables S5C21a, S5C21d, S5C21e, S5C21f and S5C21g. The floor between the carpark and the storey above must not contain penetrations or openings that would reduce the fire-resisting performance of the floor. The exception to this is a doorway which is permitted to be protected by a –/60/30 self-closing fire door.

Under the S5C9 concession, the carparking storey can be classified as a Class 2 or 3 building for the purpose of determining the relevant fire-resisting requirements of Specification 5.

Subject to the conditions listed, including the installation of a sprinkler system, S5C23(3) allows a reduction of the FRL of loadbearing elements, and the deletion of the FRL for non-loadbearing elements.

Reference to Clause S17C2 of Specification 17 indicates one of the technical standards that the sprinkler system may comply with is AS 2118.4 — Automatic fire sprinkler systems — Residential. This Standard has been specifically developed to provide a degree of life safety and property protection for occupants of low-rise Class 2 or 3 buildings (see E1D4).

S5C23(3)(b)(i) allows non-loadbearing internal walls to not have an FRL. The concession is subject to the requirement that the internal walls be lined on each side with 13 mm standard grade plasterboard or non-combustible materials.

The S5C23(3)(b)(ii) provision regarding the height of a non-loadbearing wall to which this concession is applied aims to create a smoke proof wall, hence the S5C23(3)(b)(iv) requirement for sealing any cracks and openings againstthe spread of smoke.

The S5C23(3)(b)(iii) requirement that only non-combustible insulation can be used in a cavity in a non-loadbearing wall to which this concession is applied aims to limit the spreadof fire by way of the cavity.

There is no specific concession to permit the use of solid core doors in Type B construction buildings, unlike that in S5C20(3)(b)(v), this is because they are already permitted in Type B construction (see C4D12).

The result of S5C23 is that a designer proposing to use the BCA Deemed-to-Satisfy Provisions to design a two storey Class 2 or 3 building of Type B construction has three basic options:

  • design in accordance with other provisions applicable to buildings of Type B construction which, under C2D10(1)and (2) and S5C20(1)(d) would exclude the use of timber external walls, common walls, loadbearing internal walls, fire walls and non-loadbearing internal walls required to be fire-resisting;
  • use timberand/or non-combustible materials in accordance with S5C23; or
  • comply with C2D6 and design for Type C construction, which places no limitations on the use of timber.

Type C Fire-Resisting Construction

(1) In a building required to be of Type C construction—

  1. a building element listed in Tables S5C24a, S5C24b, S5C24c, S5C24d and S5C24e and any beam or column incorporated in it, must have an FRL not less than that listed in those Tables for the particular Class of building concerned; and
  2. an external wall that is required by Table S5C24a to have an FRL need only be tested from the outside to satisfy the requirement; and
  3. a fire wall or an internal wall bounding a sole-occupancy unit or separating adjoining units must comply with Specification 6 if it is of lightweight construction and is required to have an FRL; and
  4. in a Class 2 or 3 building, an internal wall which is required by Table 5C24c or S5C24d to have an FRL must extend—
    1. to the underside of the floor next above if that floor has an FRL of at least 30/30/30 or a fire-protective covering on the underside of the floor; or
    2. to the underside of a ceiling having a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
    3. to the underside of the roof covering if it is non-combustible, and except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or
    4. 450 mm above the roof covering if it is combustible; and
  5. in a Class 2 or 3 building, except where within the one sole-occupancy unit, or a Class 9a health-care building, or a Class 9b building, a floor separating storeys, or above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor, must—
    1. have an FRL of at least 30/30/30; or
    2. have a fire-protective covering on the underside of the floor including beams incorporated in it and around the column, if the floor or column is combustible or of metal; and
  6. in a Class 9c building a floor above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor, must—
    1. have an FRL of at least 30/30/30; or
    2. have a fire-protective covering on the underside of the floor including beams incorporated in it and around the column, if the floor or column is combustible or of metal.

(2) For the purposes of Table S5C24a and Table S5C24b, external wall includes any column and other building element incorporated within it or other external building element.

Table S5C24a Type C construction: FRL of parts of external walls
Distance from a fire-source feature FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Less than 1.5 m 90/90/90 90/90/90 90/90/90 90/90/90
1.5 to less than 3 m –/–/– 60/60/60 60/60/60 60/60/60
3 m or more –/–/– –/–/– –/–/– –/–/–
Table S5C24b Type C construction: FRL of external columns not incorporated into an external wall
Distance from a fire-source feature FRL (in minutes): structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Less than 1.5 m 90/–/– 90/–/– 90/–/– 90/–/–
1.5 to less than 3 m –/–/– 60/–/– 60/–/– 60/–/–
3 m or more –/–/– –/–/– –/–/– –/–/–
Table S5C24c Type C construction: FRL of common walls and fire walls
Wall type FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Loadbearing or non-loadbearing 90/90/90 90/90/90 90/90/90 90/90/90
Table S5C24d Type C construction: FRL of internal walls
Location FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Bounding public corridors, public lobbies and the like 60/60/60 –/–/– –/–/– –/–/–
Between or bounding sole-occupancy units 60/60/60 –/–/– –/–/– –/–/–
Bounding a stair if required to be rated 60/60/60 60/60/60 60/60/60 60/60/60
Table S5C24e Type C construction: FRL of roof
Location FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part Class 5, 7a or 9 Class 6 Class 7b or 8
Roofs –/–/– –/–/– –/–/– –/–/–

To specify the fire-resistance level (FRL) and other requirements of building elements in a building required to be of Type C construction.

S5C24 Type C fire-resisting construction — fire-resistance of building elements

Tables S5C24a to S5C24e set out the required FRLs of building elements in a building required to be of Type C construction. If the element comprises or is incorporated in an external wall, the required FRL depends on distance from any fire-source feature to which it is exposed.

Although a roof is an external building element that can be exposed to a fire-source feature, it is not required to comply with the FRLs specified under the heading of external wall in Tables S5C24a to S5C24e. The FRLs required for a roof are contained under the heading of roofs near the bottom of the table.

When using Tables S5C24a to S5C24e, it should be noted that Specification 1 permits the deletion of the structural adequacy criteria of an FRL for non-loadbearing elements. The reason for this is that if such an element fails during a fire, there will be no flow-on collapse of other elements. See Schedule 1 for definition of “loadbearing”.

Generally speaking, Type C construction differs from Type B construction by allowing lower FRLs for external walls which are located more than 1.5 metres from a fire-source feature, and only requiring a maximum FRL of 90 minutes for any criterion. Table C3D3 bases these differences on the lower rise in storeys allowed by Table C2D2, and the smaller size of Type C buildings allowed.

No building element in a building required to be of Type Cconstruction is required to be non-combustible, or of concrete or masonry.

S5C24(1)(a) requires building elements to achieve at least the FRLs set out for them in Tables S5C24a to S5C24e. S5C24(1)(a) only applies to the building elements listed in Tables S5C24a to S5C24e, and any beams or columns incorporated in such building elements.

Where Tables S5C24a to S5C24e require an external wall to have an FRL, S5C24(1)(b) requires that the wall only need be tested from outside to meet the FRL criteria. This allows the use of brick veneer construction where the brick has the required FRL.

Where a fire wall and the specified internal walls are of lightweight construction they must comply with Specification 6. S5C24(1)(d) requires internal walls that are required to have an FRL to extend to a barrier to stop or limit the spread of fire over the top of the wall.

The concession contained in S5C21(1)(c) for Type B construction with respect to the height of the wall when a sole- occupancy unit occupies the whole of the top storey does not apply to Type C construction.

To protect building occupants of Class 2, 3 and 9 buildings from fire spread between storeys, S5C24(1)(e) establishes the minimum fire separation between storeys in such buildings. This requirement takes into account the special risks that can exist in such buildings.

This requirement also relates to the fire separation of Class 2, 3 and 9 buildings from a carpark or storage area. S5C24(1)(e) does not apply if the storeys being separated are within a sole-occupancy unit of a Class 2 or Class 3 building, because it is likely that the two levels are connected by a non-fire-isolated stairway and would therefore not be required to be fire separated.

The primary reason for the S5C24(1)(e) and (f) fire separation requirement is that in a building fire, the highest degree of risk is attached to such people as the very young, people with disabilities, the elderly, and those who are asleep.

Examples

Buildings that must comply with S5C24(1)(e) include:

A Class 2 building (which includes flats, apartments, etc). A Class 3 building (which includes hotels, motels, etc).

The residential part of a school.

Accommodation for the aged, children or people with disabilities. A residential aged care building.

A Class 9a building (which includes hospitals, etc).

A Class 9b building, such as schools, theatres, and the like.

(1) Notwithstanding S5C24, a carpark may comply with this clause if it is an open-deck carpark or is protected with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and is—

  1. a separate building; or
  2. a part of a building, and if occupying only part of a storey, is separated from the remaining part by a fire wall.

(2) For the purposes of this clause, a carpark

  1. includes—
    1. an administration area associated with the functioning of the carpark; and
    2. where the carpark is sprinklered, is associated with a Class 2 or 3 building and provides carparking for separate sole-occupancy units, each carparking area with an area not greater than 10% of its floor area for purposes ancillary to the sole-occupancy units; but
  2. excludes—
    1. except for (a), any area of another classification, or other part of a Class 7 building not used for carparking; and
    2. a building or part of a building specifically intended for the parking of trucks, buses, vans and the like.

(3) For building elements in a carpark as described in (1) and (2), the following minimum FRLs are applicable:

  1. External walls:
    1. Less than 1.5 m from a fire-source feature to which it is exposed:
      1. Loadbearing: 60/60/60.
      2. Non-loadbearing: –/60/60.
    2. 1.5 m or more from a fire-source feature to which it is exposed: –/–/–.
  2. Internal walls: –/–/–.
  3. Fire walls:
    1. From the direction used as a carpark: 60/60/60.
    2. From the direction not used as a carpark: 90/90/90.
  4. Columns:
    1. Steel column less than 1.5 m from a fire-source feature
      1. 60/–/–; or
      2. ESA/M not greater than 26 m2/tonne.
    2. Any other column not less than 1.5 m from a fire-source feature: 60/–/–.
    3. Any other column not covered by (i) or (ii): –/–/–.
  5. Beams:
    1. Steel floor beam, less than 1.5 m from a fire-source feature, in continuous contact with a concrete floor slab—
      1. 60/–/–; or
      2. an ESA/M of not greater than 30 m2/tonne.
    2. any other beam: 60/–/–.
    3. more than 1.5 m from a fire-source feature: –/–/–.
  6. Roof, floor slab and vehicle ramp: –/–/–.

(4) For the purposes of (3), ESA/M means the ratio of exposed surface area to mass per unit length.

To allow lower fire-resistance levels (FRLs) for building elements in open-deck or sprinklered carparks.

S5C25 Type C fire-resisting construction — carparks

S5C25 is based on experimental research carried out at the BHP Research Laboratories. The research included full scale fire tests on both open-deck and enclosed carparks, and was supplemented by extensive overseas testing.

The research carried out on this matter showed that the S5C25 FRLs will not lead to an unsafe situation or structural failure of a building element in an open-deck carpark, or an enclosed carpark which is sprinkler protected.

See Schedule 1 for definition of “carpark”. S5C25(2) refines this definition when the expression is used in S5C25.

Inclusions and exclusions

The S5C25 concessions include:

  • a building which solely comprisesa carpark;
  • the carpark section of a building which elsewhere has another use;
  • any administrative area associated with the carpark, such as ticket selling and fee collection areas; and
  • in a sprinkler protected carpark, small areas ancillary to a Class 2 or Class 3 building, such as part of the carpark used for normal ‘household’ storage.

The S5C25 concessions exclude:

  • any area of another Class;
  • another Class 7 use (i.e. other than carparking); and
  • an area “specifically intended”for the parking of vehicles such as trucks, buses, vans and the like.

S5C25, while using the refined definition of “carpark”, also use the undefined expression “carparking”. This word specifically refers to the parking of cars.  This is also the intention of refining the definition of “carpark” as expressed by the use of the words “specifically intended” in S5C25(2)(b)(ii).

However, in applying these provisions, it is important to consider the purpose of refining this definition, which is to limit the concessions in S5C25 to areas used for the parking of lighter vehicles (that is, vehicles other than commercial trucks, vans, buses and the like), rather than simply limiting them to areas used for the parking of cars only.

Accordingly, it would seem contrary to the purpose of this clause to exclude, from the refined definition and the word “carparking”, such vehicles as motor bikes, van-like family vehicles, non-commercial panel vans, and smaller non- commercial utilities.

Regarding certain types of columns and beams, S5C25 permits them to have eithera specified FRL or a specified surface area to mass ratio . In other words, in relation to these columns and beams, S5C25 does not require them to have an FRL if they have the specified surface area to mass ratio. Some authorities refer to this ratio as the “heat sink effect”, in that the lower the exposed surface area to mass ratio, the lower will be the member temperature for a given fire.

In the section of S5C25(3) relating to columns:

  • the concession of (d)(i) applies only to steel columns that are located less than 1.5 metres from any fire-source feature; and
  • the concession of (d)(ii) applies only to columns of any material which are located less than 1.5 metres from any fire- source feature.

Columns of any material that do not qualify for the (d)(i)and (ii) concessions are subject to (iii).

Roofs that do not qualify for the roof concession in S5C25 must comply with the requirements of Specification 5 for roofs of other buildings.

S5C19 provisions restricting the roof concession to those roofs that are not used for carparking does not apply to S5C25.

The differences between S5C25 and S5C22 are based on the lower rise in storeys allowed for Type C buildings by Table C2D2.