This Part contains additional requirements for premises used for electro-plating, electro-polishing, anodising or etching.
Deemed-to-Satisfy Provisions
TAS I14D1 Application of Part
2019: TAS H116.1
Application of Part
TAS I14D2 Floors
2019: TAS H116.2
The floor of every plating area must be—
Floors
TAS I14D3 Height of plating area
2019: TAS H116.3
Every part of a plating area must be not less than 2.7 m in height—
Height of plating area
TAS I14D4 Air space
2019: TAS H116.4
In every plating area there must be not less than 14 m3 of air space for each person employed and, in the calculation of such space, the height taken into account must not exceed 4.2 m.
Air space
TAS I14D5 Ceiling construction
2019: TAS H116.5
The ceiling of a plating area must be so constructed as to prevent, so far as is practicable, atmospheric contaminants from escaping into rooms or work places, situated above the level of the ceiling.