NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
31
Specification 31 Fire and smoke control systems in buildings containing atriumsThis Specification sets out the requirements for the design and operation of systems of fire and smoke control in buildings containing an atrium.
To clarify that Specification 31 includes the requirements for fire and smoke control systems in buildings with an atrium.
Specification 31 includes the requirements for fire and smoke control systems in buildings containing an atrium.
Where a sprinkler system is required, it must be installed in the whole building, not just that part in which the atrium is located.
A sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 must be installed in every building containing an atrium, except where varied or superseded by this Specification.
To set out the general requirements for the installation of a suitable sprinkler system in a building containing an atrium.
Generally, a sprinkler system must comply with Specification 17. S31C3 to S31C6 sets out additional requirements for sprinklers in a building containing an atrium.
If any conflict exists between Specification 17 and S31C3 to S31C6, then S31C3 to S31C6 take precedence.
To set out the roof protection requirements for a building containing an atrium.
S31C3 requires smoke extraction through the roof, or near the top of the atrium. It is therefore important that the roof remains in place during a fire and does not allow the re-circulation of smoke. To achieve this, G3D6 requires the roof:
When the roof is required to have an FRL, G3D6(a) does not allow the use of the concessions contained in S5C14, S5C15 or S5C16 for the roof of the atrium.
The sprinkler protection requirement only applies to a roof located in an area where a fire could affect its integrity. The distances stated in S31C3(a) and (b) differ because of the different fire loads assumed in the different Classes of building. The heights of the atrium roof have been selected as those beyond which a smoke plume produced by a typical fire would no longer be hot enough to damage an unprotected roof.
The sprinkler heads need only be arranged to give a wetting effect to both the underside of the roof membrane and any part of the supporting structure.
The higher temperature rating of the sprinkler heads is to make sure they do not falsely discharge due to the potentially higher normal temperatures under an atrium roof, especially if a glass or translucent roof is used (as is common practice).
S31C3 requires smoke extraction through the roof, or near the top of an atrium. The smoke extraction is required to be by mechanical exhaust or by smoke and heat vents.
Figure S31C3 illustrates the alternative protection of an atrium roof.
Figure S31C3: Alternative protection for atrium roof
To set out fire protection requirements for atrium floors (i.e. at the lowest level of the atrium).
Because of the height of the roof in an atrium, the sprinklers protecting it are unlikely to be effective at the lowest level of the atrium. Additional sprinklers are therefore normally required to protect that level, as this area is normally a large open space, and is potentially the primary source of a major fire. Adequate protection of the floor often requires the use of sidewall sprinkler heads, as required by S31C4(a). S31C4(a) requires a “performance-type” decision as to the types of sprinklers (sidewall and overhead) and their combination.
Because of the additional fire hazard associated with atriums, S31C4(b) requires the use of quick response sprinkler heads.
Although a “quick response” sprinkler head can activate at the same temperature as a “normal” sprinkler head, its reaction time is much shorter and it has different discharge characteristics. Therefore, S17C5 requires that the sprinkler system be designed specifically for the use of these heads.
To set out fire protection requirements for glazed walls to an atrium.
S31C5(1) sets out the requirements for sprinkler protection of glazed bounding walls. These requirements are illustrated in Figure S31C10.
Under S31C5(2), the location of the sprinkler heads must allow full wetting of the glazing without wetting an adjacent head. Consequently, water should run down the window, cooling the glass and therefore creating a resistance to the spread of fire and/or smoke through the glazed wall by reducing its potential to failure during a fire. It is also important that the adjacent sprinkler head not be wetted, because the cooling effect of the water may delay its activation.
Because of the additional fire hazard associated with atriums, S31C5(3) requires the use of “quick response” sprinkler heads.
Although a “quick response” sprinkler head can activate at the same temperature as a “normal” sprinkler head, its reaction time is much shorter and it has different discharge characteristics.
S31C5(4) sets out the minimum requirements for water discharge rates. S17C5 therefore requires that the sprinkler system be designed specifically for the use of these heads.
S31C5(4) sets out the required water discharge rates on any glazing in a bounding wall. Because the atrium can have a high fire load and large volume, the higher flow rate of 0.25 L/s.m2 is required on the atrium side of the glazing when the wall is not set back from the atrium well.
The importance of the wall sprinklers to glazed walls in a fire is such that S31C5(5) sets out the minimum potential coverage to be provided by such sprinklers, which in turn determines the characteristics of the water supply in terms of pressure and quantity.
The water supply for the wall wetting system referred to in S31C5(5) is additional to the water supply for the other sprinklers in the building.
It is assumed that the size of a fire will be controlled by the sprinkler system installed in the building. The greater height required to be covered by a wall wetting sprinkler system in a Class 6, Class 7 or Class 8 part of a building (see S31C5(5)(a)(ii)) reflects the greater fire load contained in such buildings.
To set out requirements for sprinkler and wall wetting system stop valves.
When referring to sprinkler and wall wettingstop valves, S31C6requires that:
Except where varied or superseded by this Specification, mechanical air-handling systems in a building containing an atrium must comply with AS 1668.1.
To set out the general requirements for the installation of a suitable smoke control system in a building containing an atrium.
As generally required by the BCA, mechanical air-handling systems must comply with AS 1668.1. However, if any conflict exists between AS 1668.1 and Specification 31, the specification takes precedence.
Mechanical air-handling systems serving an atrium must be designed to operate so that during a fire—
To set out mechanical air-handling system requirements for an atrium.
The basic operation of the mechanical air-handling system during a fire is to limit the spread of smoke. To achieve this it must:
The intent of the details contained in S31C8(d) and (f) is to create a negative air pressure on the fire floor or in the fire affected compartment, so that air and any entrained smoke is drawn to it. This creates positive pressure on non-fire floors, so as to prevent the migration of smoke to non-fire floors while exhausting smoke from a fire affected floor.
To set out how a smoke control system serving an atrium is to be activated.
A smoke exhaust system serving an atrium must be designed on the basis of—
To set out the design characteristics of a smoke exhaust system serving an atrium.
S31C10 specifies the characteristics on which a smoke exhaust system design must be based, which are:
Figure S31C10 of the BCA must be used to determine the minimum smoke extraction rate from the atrium. The required rate depends on the fire load specified in S31C10(a) and the height of the smoke plume above the floor of the atrium well specified in S31C10(b).
The exhaust rates are based on the need to maintain the smoke plume safely above any egress path.
Notwithstanding S31C10(c), the average upward air velocity in the atrium, due to the required smoke exhaust quantity must—
To enable the movement of smoke to the roof, for venting externally.
If the smoke is allowed to travel up the atrium due to its own buoyancy, in higher atriums it will reach a stage where it will not travel any higher. The reasons for this include:
Accordingly, to make sure the smoke continues to travel up the atrium well, minimum (see S31C11(a)) and maximum (see S31C11(b)) air velocities are specified. The maximum velocity specified in S31C11(b) only applies to an atrium well with a constant plan cross section.
To set out the operational requirements for exhaust fans.
To make sure that exhaust fans operate effectively during a fire, they must be designed to operate for at least 1 hour at a temperature of 200°C (see S31C12(1)).
Under S31C12(2) and (3), to make sure that at least one fan continues to operate during a fire:
Notwithstanding S31C12, automatic vents complying with AS 2665 may be used, except where a Class 6 part of a building adjoins the atrium, in lieu of exhaust fans provided that—
To set out requirements for smoke and heat vents, which are permitted in low-rise atriums.
Smoke and heat vents are permitted in low-rise atriums (i.e. atriums less than 12 metres high), instead of a mechanical smoke extraction system. The reason for the S31C13(a) limit is that 12 metres is considered to be a height to which smoke will travel due to its own buoyancy and still be effectively vented.
S31C13 does not apply where a Class 6 part of a building adjoins the atrium.
S31C13(b) requires that vents be fitted with a manual override switch, for use as necessary by emergency services personnel.
To set out requirements for air flow into an atrium from which smoke-laden air is being extracted.
S31C7 to S31C13 require that smoke-laden air be exhausted from an atrium. S31C14 sets out how this exhausted air is to be made-up (i.e. replaced) in the atrium.
S31C14(1) is a performance criterion that requires make-up air to be provided from outside the atrium at a level at or near the lowest storey of the atrium and non-fire storeys.
To make sure that the area where the bounding walls are set back from the atrium well is kept smoke free, an air velocity of 0.1 m/s is required by S31C14(2). This velocity is consistent with that required through an open door by a fire-isolated stairway pressurisation system which accords with AS 1668.1.
S31C14(3) provides a means of achieving compliance with S31C14(1). It is important that the make-up air assists (and does not disturb) the exhausting of the smoke layer. To achieve this, the make-up air should enter the atrium at as low a level as possible, preferably at the base of the atrium. The make-up air must be provided from:
If a system of ducts is used to supply the make-up air, to make sure the system operates when needed during a fire the ducts must have an FRL of 60/60/60 if they pass through a different fire compartment to the atrium.
To set out the general requirements for the installation of a suitable fire detection and alarm system in a building containing an atrium.
A building’s fire detection and alarm system must, in general, comply with AS 1670.1. However, if any conflict exists between AS 1670.1 and Specification 31, the Specification takes precedence.
Smoke detection within an atrium—
To set out requirements for smoke detectors in an atrium.
S31C16 sets out, in detail, the requirements for smoke detectors within an atrium. The aim of these requirements is to make sure that the smoke detection system operates effectively and false alarms are minimised.
To set out requirements for smoke detectors at return and relief air openings.
S31C17 sets out the requirements for smoke detectors at return and relief air openings.
To set out requirements for alarm systems in a building containing an atrium.
Alarm systems required in a building containing an atrium, must include a manual call point (break-glass) alarm at each door to a fire-isolated exit. The aim of this provision is that a person is able to break the glass setting off the alarm as they evacuate the building, in advance of the automatic activation of the alarm system.
Where a sampling type smoke detection system is provided, a staged alarm must be given. The stages are set out in S31C18(2)(a) to (c). The reason for the staged alarms is to minimise the occurrence of false alarms.
Under S31C18(3), beam and point type smoke detectors (as with a sampling type smoke detection system) must also operate as set out in S31C18(2)(a) to (c), but at the levels set in AS/NZS 1670.1. This provision only applies to beam and point type smoke detectors required by the BCA.
A building containing an atrium must be provided with an emergency warning and intercom system which—
To require that a suitable emergency warning and intercom system is installed in a building containing an atrium.
S31C19 requires the installation of an emergency warning and intercom system in any building containing an atrium. The system must comply with:
The system is a combination of an emergency warning system and an emergency intercom. The main function of an integrated system is:
The operation of the system may be by a number of measures referred to in Specification 31, including the manual call point (break- glass) alarm required by S31C18(1).
To require the installation of a suitable standby power system in a building containing an atrium.
S31C20 only applies where a required path of travel to an exit passes through an atrium (see S31C20(1)).
Under S31C20(1), because of the need to continue the operation of emergency services, a standby power supply is required. This is particularly important because of the increased fire hazard associated with atriums, and the dangers for occupants if they have to evacuate through atriums.
To make sure it operates when needed during a fire, the standby power supply must:
S31C20 is consistent with the protection required for electricity supply systems in C3D14.
S31C20(3) sets out means of achieving compliance with S31C20(1). To make sure that the necessary power to operate the emergency equipment is available during a fire, it requires the standby power to be from one of the listed alternatives.
To minimise the risk of smoke entering a fire-isolated exit in a building containing an atrium.