NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

J5

Part J5 Building sealing

Part J5 Building sealing

Introduction to this Part

This Part contains Deemed-to-Satisfy Provisions for compliance with Part J1. It sets out provisions for the sealing of a building’s glazing, doors, exhaust fans and the like in order to increase thermal comfort for occupants and reduce the energy consumption of any installed air-conditioning systems.

Notes

From 1 May 2023 to 30 September 2023 Section J of NCC 2019 Volume One Amendment 1 may apply instead of Section J of NCC 2022 Volume One. From 1 October 2023 Section J of NCC 2022 Volume One applies.

Notes: New South Wales Section J Energy Efficiency

  1. For a Class 2 building or a Class 4 part of a building, where a relevant development consent or an application for a complying development certificate requires compliance with a BASIX Single Dwelling or Multi Dwelling Certificate issued under Version 3.0 or earlier, NSW Section J of NCC 2019 Volume One Amendment 1 applies.
  2. For a Class 2 building or a Class 4 part of a building, where a relevant development consent or an application for a complying development certificate requires compliance with a BASIX Single Dwelling or Multi Dwelling Certificate issued under Version 4.0 or later, Section J of NCC 2022 Volume One applies.
  3. For a Class 2 building or a Class 4 part of a building, where a relevant development consent or an application for a complying development certificate requires compliance with a BASIX Alterations and Additions Certificate, NSW Section J of NCC 2019 Volume One Amendment 1 applies.
  4. For a Class 3 building or Class 5 to 9 building:
    1. From 1 May 2023 to 30 September 2023 NSW Section J of NCC 2019 Volume One Amendment 1 may apply instead of Section J of NCC 2022 Volume One.
    2. From 1 October 2023 Section J of NCC 2022 Volume One applies.

Notes: Tasmania Section J Energy Efficiency

In Tasmania, for a Class 2 building and Class 4 part of a building, Section J is replaced with Section J of BCA 2019 Amendment 1.

Deemed-to-Satisfy Provisions

(1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements J1P1 to J1P4 are satisfied by complying with—

  1. J2D2; and
  2. J3D2 to J3D15; and
  3. J4D2 to J4D7; and
  4. J5D2 to J5D8; and
  5. J6D2 to J6D13; and
  6. J7D2 to J7D9; and
  7. J8D2 to J8D4; and
  8. J9D2 to J9D5.

NSW J5D1 Deemed-to-Satisfy Provisions2019: J3.0

Delete subclause J5D1(1) and insert J5D1(1) as follows:

(1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements NSW J1P1 to NSW J1P7 are satisfied by complying with—

  1. NSW J2D2; and
  1. NSW J3D2 to J3D10; and
  2. NSW J4D2 to J4D7; and
  3. NSW J5D2 to J5D8; and
  4. NSW J6D2 to J6D13; and
  5. NSW J7D2 to J7D9; and
  6. J8D2 to NSW J8D4; and
  7. J9D2 to J9D5.

(2) Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2G2(3) and A2G4(3) as applicable.

To clarify which provisions of Section J apply to dwellings and which provisions apply to other buildings.

Where a solution is proposed to comply with the Deemed-to-Satisfy Provisions, J2D1 clarifies how compliance with Parts J2 to J9 achieves compliance with J1P1 to J1P4.

Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2G2(3) and A2G4(3) as applicable. (See commentary on Part A2).

The Deemed-to-Satisfy Provisions, including those related to house energy rating software, described are limited to the most common forms of construction and the simplest forms of buildings. It is expected that the more innovative construction techniques and the more complex buildings will be designed and assessed using a performance approach.

A major consideration in developing the measures was the likelihood of a building being heated or cooled by an air-conditioning system, and whether the Deemed-to-Satisfy Provisions should assume this to be the case, or only apply the provisions if a heating or cooling system is installed. It is recognised that most Class 3, 5, 6 and 9 buildings and some Class 7 and 8 buildings are heated or cooled, and this is the basis of the provisions. Consideration was also given to the fact that although the first owner may be prepared to ‘manage’ their building in the appropriate manner, the next owner or tenant may not, and instead may install air-conditioning.

Because of the performance-based structure of the NCC, a Performance Solution may be proposed instead of the Deemed-to-Satisfy Provisions.

NCC Blurbs

The Deemed-to-Satisfy Provisions of this Part apply to elements forming the envelope of a Class 2 to 9 building, other than—

  1. a building in climate zones 1, 2, 3 and 5 where the only means of air-conditioning is by using an evaporative cooler; or
  2. a permanent building opening, in a space where a gas appliance is located, that is necessary for the safe operation of a gas appliance; or
  3. in a Class 3 or Class 5 to 9 building, a building or space where the mechanical ventilation required by Part F6 provides sufficient pressurisation to prevent infiltration; or
  4. parts of buildings that cannot be fully enclosed.
NCC Title
Application of Part
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Application of Part

The Deemed-to-Satisfy Provisions of this Part apply to elements forming the envelope of a Class 2 to 9 building, other than—

  1. a building in climate zones 1, 2, 3 and 5 where the only means of air-conditioning is by using an evaporative cooler; or
  2. a permanent building opening, in a space where a gas appliance is located, that is necessary for the safe operation of a gas appliance; or
  3. a building or space where the mechanical ventilation required by Part F6 provides sufficient pressurisation to prevent infiltration.

To clarify that the Deemed-to-Satisfy Provisions of Part J5 do not apply to certain buildings and areas within certain buildings.

J5D2 does not apply where the only conditioning is provided by an evaporative cooler or to openings necessary for the safe operation of a gas appliance.

A building that is conditioned by heating or refrigerative cooling needs to be sealed to conserve energy but one that is conditioned by evaporative cooling does not need to be sealed as windows or doors would need to be opened anyway in order to provide the relief for the ventilation air. However, if the building is in climate zones 4, 6, 7 or 8, or has a refrigerative cooler, then it has to be sealed because of the likelihood of heating during colder periods or to avoid the loss of cooled air when the refrigerated cooler is running.

The Deemed-to-Satisfy Provisions of Part J5 do not apply to Class 8 electricity network substations as these buildings are not required to be air-conditioned for the purposes of Section J. See the definition for air-conditioning. The air-conditioning systems of these buildings are instead designed to maintain the efficient operation of sensitive electrical equipment.

Ventilation for safe operation of a gas appliance is not covered by the NCC, but is addressed by other legislation. Appropriate ventilation for gas appliances can be obtained from the relevant legislation, reference standards and product installation manuals.

Unique to this Part is that as air-conditioned buildings are often pressurised by the introduction of outside air through a mechanical supply system, it may not be necessary to seal the building to the same degree as for an un-pressurised building.

The chimney or flue of an open solid-fuel burning appliance must be provided with a damper or flap that can be closed to seal the chimney or flue.

To provide energy efficiency requirements to chimneys and flues.

The requirements of this Part are to be read in conjunction with the fire safety requirements in Part G2.

A solid-fuel burning device is a heater that burns material such as timber, coal and the like. This provision does not apply to gas and liquid fuel burning devices.

(1) A roof light must be sealed, or capable of being sealed, when serving—

  1. a conditioned space; or
  2. a habitable room in climate zones 4, 5, 6, 7 or 8.

(2) A roof light required by (1) to be sealed, or capable of being sealed, must be constructed with—

  1. an imperforate ceiling diffuser or the like installed at the ceiling or internal lining level; or
  2. a weatherproof seal; or
  3. a shutter system readily operated either manually, mechanically or electronically by the occupant.

To provide energy efficiency requirements for the sealing of roof lights.

Roof lights that are openable must be sealed when closed in order to restrict the loss of conditioned air to the outside environment. It is assumed that most of the habitable rooms in residential type buildings in the cooler climate zones will be heated by installed or portable heaters. However, if a non-habitable room is conditioned, either cooled or heated, then it must also be sealed. For the hotter climate zones, the roof lights need be sealed only if conditioning is being installed. 

NCC Blurbs

(1) A door, openable window or the like must be sealed—

  1. when forming part of the envelope; or
  2. in climate zones 4, 5, 6, 7 or 8.

(2) The requirements of (1) do not apply to—

  1. a window complying with AS 2047; or
  2. a fire door or smoke door; or
  3. a roller shutter door, roller shutter grille or other security door or device installed only for out-of-hours security.

(3) A seal to restrict air infiltration—

  1. for the bottom edge of a door, must be a draft protection device; and
  2. for the other edges of a door or the edges of an openable window or other such opening, may be a foam or rubber compression strip, fibrous seal or the like.

(4) An entrance to a building, if leading to a conditioned space must have an airlock, self-closing door, rapid roller door, revolving door or the like, other than—

  1. where the conditioned space has a floor area of not more than 50 m2; or
  2. where a café, restaurant, open front shop or the like has—
    1. a 3 m deep un-conditioned zone between the main entrance, including an open front, and the conditioned space; and
    2. at all other entrances to the café, restaurant, open front shop or the like, self-closing doors.

(5) A loading dock entrance, if leading to a conditioned space, must be fitted with a rapid roller door or the like.

Applications

NSW J5D5(5) does not apply to a Class 2 building or a Class 4 part of a building.

NCC Title
Windows and doors
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Windows and doors

(1) A door, openable window or the like must be sealed—

  1. when forming part of the envelope; or
  2. in climate zones 4, 5, 6, 7 or 8.

(2) The requirements of (1) do not apply to—

  1. a window complying with AS 2047; or
  2. a fire door or smoke door; or
  3. a roller shutter door, roller shutter grille or other security door or device installed only for out-of-hours security.

(3) A seal to restrict air infiltration—

  1. for the bottom edge of a door, must be a draft protection device; and
  2. for the other edges of a door or the edges of an openable window or other such opening, may be a foam or rubber compression strip, fibrous seal or the like.

(4) An entrance to a building, if leading to a conditioned space must have an airlock, self-closing door, rapid roller door, revolving door or the like, other than—

  1. where the conditioned space has a floor area of not more than 50 m2; or
  2. where a café, restaurant, open front shop or the like has—
    1. a 3 m deep un-conditioned zone between the main entrance, including an open front, and the conditioned space; and
    2. at all other entrances to the café, restaurant, open front shop or the like, self-closing doors.

(5) A loading dock entrance, if leading to a conditioned space, must be fitted with a rapid roller door or the like.

To provide energy efficiency requirements for the sealing of windows and doors.

An external door opening to a conditioned space must also have a device to prevent significant amounts of conditioned air being continuously lost. This only applies to conditioned spaces greater than 50 m2. Devices that may be installed to comply with this requirement may include an airlock, self-closing door, or revolving door. Provisions for people with a disability should also be considered when selecting the device.

There are a couple of exemptions to these requirements, such as for roller shutter doors or the like, that are used for out-of-hours security purposes only, i.e. when conditioning is not operating. Another exemption has been granted for the main entrance to a café, restaurant or open front shop that has a 3 m non-conditioned zone. Where staff are carrying trays of food or drink it may be unsafe to require an airlock, self-closing door or sliding door.

An exhaust fan must be fitted with a sealing device such as a self-closing damper or the like when serving—

  1. a conditioned space; or
  2. a habitable room in climate zones 4, 5, 6, 7 or 8.

To provide energy efficiency requirements for the sealing of exhaust fans.

The sealing of exhaust fans applies to the same spaces and in the same climate zones as described for roof lights. It also only applies to “miscellaneous” exhaust fans, such as smaller fans used for domestic kitchen exhaust. The provisions do not apply to smoke exhaust fans and the like. The term “miscellaneous” is comparable with the use of this term in AS 1668.1 for certain air-handling systems.

A miscellaneous exhaust fan is considered to be adequately sealed if it is fitted with a self-closing damper or similar sealing device.

(1) Ceilings, walls, floors and any opening such as a window frame, door frame, roof light frame or the like must be constructed to minimise air leakage in accordance with (2)—

  1. when forming part of the envelope; or
  2. in climate zones 4, 5, 6, 7 or 8.

(2) Construction required by (1) must be—

  1. enclosed by internal lining systems that are close fitting at ceiling, wall and floor junctions; or
  2. sealed at junctions and penetrations with—
    1. close fitting architrave, skirting or cornice; or
    2. expanding foam, rubber compressible strip, caulking or the like.

(3) The requirements of (1) do not apply to openings, grilles or the like required for smoke hazard management.

To provide energy efficiency requirements for the sealing of roofs, walls and floors.

The sealing of roofs, walls and floors applies to the same spaces and in the same climate zones as described for roof lights. For the purposes of J5D7, a suitable seal includes expanded foam, rubber compressible strip, caulking or other gap filling material.

The acceptable solution of a “close fitting internal lining system” is considered to include an allowance for minimum gaps in internal linings for thermal movement at wall, floor and ceiling junctions.

An evaporative cooler must be fitted with a self-closing damper or the like—

  1. when serving a heated space; or
  2. in climate zones 4, 5, 6, 7 or 8.

To provide energy efficiency requirements for the sealing of evaporative coolers when not in use.

Similarly to exhaust fans, an evaporative cooler represents a large opening in the building envelope. This opening needs sealing when the evaporative cooler is not in use, such as in the winter when a heating system may be operating.