(1) The floor must be—
- of impervious material with a smooth, unbroken surface; and
- uniformly graded to a floor drain.
(2) All walls and partitions must be of concrete or masonry with a smooth, unbroken finish for ease of cleaning.
(3) All joints between the floor, walls, partitions, ceiling, ventilation grilles, fittings, pipework, windows and light fittings must be sealed with impervious material for ease of cleaning.
(4) All joints between the floor and walls or partitions must be coved for ease of cleaning.
(5) The body preparation room must be provided with at least one washbasin, fitting with elbow or foot-operated taps, and an adequate supply of hot and cold water.
(6) The body preparation room must be provided with refrigerated storage facilities—
- With sufficient capacity for the storage of at least two adult bodies; and
- Capable of maintaining an internal temperature between 1°C and 5°C.