I12

TAS Part I12 Premises for manufacture or processing of glass reinforced plastics

TAS Part I12 Premises for manufacture or processing of glass reinforced plastics

Introduction to this Part

This Part contains additional requirements for premises used for the manufacture or processing of glass reinforced plastics.

Deemed-to-Satisfy Provisions

NCC Blurbs

(1) This Part is applicable to every building in which glass reinforced plastics are manufactured or processed.

(2) Premises for manufacture or processing of glass reinforced plastic must—

  1. provide for the safety and comfort or workers; and
  2. be constructed in a manner that will avoid the spread of fire within the building and to other buildings.
NCC Title

Application of Part

NCC State
TAS
NCC SPTC Current
Application of Part
NCC Blurbs

A building for the manufacture or processing of glass reinforced plastics must be—

  1. separated from other buildings or parts of an occupancy by means of impervious walls with FRL at least 120/120/120; or
  2. separated from all other buildings by a clear space of not less than 6 m.
NCC Title

Separation from other buildings

NCC State
TAS
NCC SPTC Current
Separation from other buildings
NCC Blurbs

The building must be of single storey construction.

NCC Title

Rise in storeys

NCC State
TAS
NCC SPTC Current
Rise in storeys
NCC Blurbs

The floor area of any building or fire-separated section must not exceed the relevant maximum floor area set out in Table TAS I12D4.

Insert TAS table (I12D4) I12D4 as follows:
TAS Table I12D4: Maximum floor area of buildings for manufacture or processing of glass reinforced plastics or isocyanates
Type A building construction Type B building construction Type C building construction
Not sprinklered: 1500 m2 Not sprinklered: 1200 m2 Not sprinklered: 1000 m2
Sprinklered: 6000 m2 Sprinklered: 5000 m2 Sprinklered: 3000 m2
NCC Title

Maximum floor areas

NCC State
TAS
NCC SPTC Current
Maximum floor areas
NCC Blurbs

(1) Each fire-separated section of a building which is a work place must have at least two exits for escape purposes and the number and location of exits must be such that any point on the floor is not further than 20 m from one of the exits.

(2) Only exits with vertically hinged swinging doors may be considered as exits for the purposes of this clause.

NCC Title

Required exits

NCC State
TAS
NCC SPTC Current
Required exits
NCC Blurbs

The walls and floors of areas to be used for hand laminating and spray depositing must be constructed of non-combustible materials.

NCC Title

Hand laminating and spray depositing

NCC State
TAS
NCC SPTC Current
Hand laminating and spray depositing
NCC Blurbs

(1) Mechanical or natural ventilation must be via low-level, exhaust ducting in a wall and a fixed, open, floor-level, fresh-air inlet ducting in the opposite wall such as to ensure a cross flow of the ventilation over the complete working area.

(2) Mechanical ventilation must provide not less than 6 air changes per hour.

(3) The ventilation fan and exhaust ducting must be arranged in such a manner as to—

  1. produce a negative pressure within any exhaust ducting within the work place so that a leak in the ducting will not vent exhaust air back in to the work place; and
  2. vent the exhaust air to the atmosphere so as to prevent recirculation of that exhaust air.
NCC Title

Ventilation

NCC State
TAS
NCC SPTC Current
Ventilation
NCC Blurbs

Each fire-separated section must be provided with automatic smoke and heat roof vents.

NCC Title

Smoke and heat roof vents

NCC State
TAS
NCC SPTC Current
Smoke and heat roof vents