Specification 27 Accessible adult change facilities

Specification 27 Accessible adult change facilities

This Specification contains the requirements for accessible adult change facilities.

The intent of this Specification is to prescribe how an accessible adult change facility is to be designed and the equipment, fixtures and fittings that must be included in each facility.

Specification 27 is based on the Changing Places Information Guide and Technical Standard (June 2017 edition), copies of which can be obtained from the Changing Places website at: https://changingplaces.org.au/.

(Note: Changing Places is not in any way affiliated with, or endorsed by, the ABCB.)

(1) Each accessible adult change facility must—

  1. be constructed so that all required equipment and fixtures are contained within the same room; and
  2. if it is a unisex facility, be located such that it can be entered without crossing an area reserved for one sex only.

(2) In each accessible adult change facility, the following must be provided:

  1. A hoist complying with S27C3.
  2. A toilet pan, seat, backrest and grabrails complying with S27C4.
  3. A washbasin and tap complying with S27C5.
  4. Fixtures and fittings as specified in S27C6.
  5. A change table complying with S27C7.
  6. Changing rails complying with S27C8.
  7. An automated sliding entrance door complying with S27C9.
  8. Signage complying with S27C10.
  9. Operating instructions for the hoist and change table in accordance with S27C11.
  10. Circulation spaces complying with Figures S27C2a, S27C2b and S27C2c.

(3) The floor surface must have a slip resistance classification of not less than R10 or P3 when tested in accordance with AS 4586.

(4) For the purposes of Figures S27C2a, S27C2b and S27C2c, the following applies:

  1. The Roman numerals shown in Figures S27C2a, S27C2b and S27C2c indicate the following required circulation spaces:
    1. Turning space: a full circle of 1125 mm radius.
    2. Each side of the pan: 900 mm (measured from each edge of the pan).
    3. In front of the pan: 2350 mm (measured from the wall behind the pan, and therefore includes the pan itself).
    4. For a washbasin: the width of the basin (450 mm) increasing to a width of 1350 mm measured at a distance of 750 mm out from the wall against which the washbasin is mounted then continuing at that width for a further 800 mm (to a total of 1550 mm out from the wall).
    5. For changing rails: the width of the rails increasing to a width of 1350 mm at a distance of 750 mm out from the wall to which the rails are fixed then continuing at that width for a further 800 mm (to a total of 1550 mm out from the wall).
  2. All required circulation spaces must extend for a minimum height of 2000 mm above finished floor level.
  3. Required circulation spaces may be overlapped.
Figure S27C2a Required circulation spaces — Turning space, each side of the pan and in front of the pan
image-S27C2a-required-circulation-spaces-turning-space-each-side-of-pan-and-in-front-of-pan.svg
Figure S27C2b Required circulation spaces — Turning space and circulation space for a washbasin
image-S27C2b-required-circulation-spaces-turning-space-and-circulation-space-for-washbasin.svg
Figure S27C2c Required circulation spaces — Turning space and circulation space for changing rails
image-S27C2c-required-turning-space-and-circulation-space-for-changing-rails.svg

The hoist must—

  1. provide a constant charge in-line room coverage hoist system (also known as an “XY” system or gantry) including 2 parallel fixed rails and a moving traverse rail; and
  2. provide coverage over the entire room; and
  3. have a maximum safe working load of not less than 180 kg; and
  4. be capable of sustaining a static load of not less than 1.5 times the rated load; and
  5. have a minimum lifting height of 2100 mm.

(1) The toilet pan must be of the centrally located ("peninsula-type") design.

(2) The toilet pan must be installed so that—

  1. the front edge of the pan is 800 mm (±10 mm) from the rear wall; and
  2. the top of the seat is between 460 mm and 480 mm above finished floor level; and
  3. there is a minimum clearance of 900 mm, measured horizontally, between each side of the pan and any adjacent wall or privacy screen.

(3) The toilet seat must—

  1. be of the full-round type (not open-fronted) with minimal contours to the top surface; and
  2. be securely fixed in position when in use; and
  3. have seat fixings that provide lateral stability to the seat when the seat is in use; and
  4. be load-rated to 150 kg; and
  5. have a minimum luminance contrast of 30% against the pan, wall or floor; and
  6. remain in the fully upright position when raised.

(4) A hand-operated flushing control must—

  1. be located on the centreline of the toilet, at a height above finished floor level of—
    1. not less than 600 mm; and
    2. not more than 1100 mm; and
  2. not be located within the area required for any grabrails or backrest; and
  3. have the button mounted so that it is proud of the wall surface, and activates the flushing operation before the button becomes level with the surrounding surface.

(5) An automatically activated flushing system need not comply with the requirements of (4).

(6) The backrest must—

  1. be capable of withstanding a force, in any direction, of not less than 1100 N; and
  2. have a minimum height, between the lower edge of the backrest and the top of the seat, of between 120 mm and 150 mm; and
  3. have a vertical height, between the upper and lower edges of the backrest, of between 150 mm and 200 mm; and
  4. have a width of between 350 mm and 400 mm; and
  5. be positioned such that the face of the backrest achieves an angle of between 95° and 100° back from the seat, when the seat is in use.

(7) Grabrails must be installed adjacent to each side of the pan and must be—

  1. of the drop-down type; and
  2. located such that—
    1. the top of each rail is between 800 mm and 810 mm above finished floor level; and
    2. the rails are between 750 mm and 770 mm apart, measured centre-to-centre, and equidistant to the centreline of the pan; and
  3. at least 850 mm long; and
  4. with a diameter of between 30 mm and 40 mm; and
  5. securely fixed to withstand a force, in any direction, of not less than 1100 N; and
  6. provided with a toilet paper dispenser on one side; and
  7. capable of being lifted up or swung away when not in use, so as to allow unimpeded access to the toilet pan.

(1) The washbasin must be installed so that the rim of the basin is between 800 mm and 830 mm above finished floor level.

(2) Exposed heated water supply pipes must be insulated or located so as not to pose a hazard.

(3) Water supply or sanitary drainage pipes must not encroach on the space under the basin.

(4) The washbasin must have an integrated shelf not less than 300 mm long.

(5) Water taps must have a single lever flick-mixer handle or a sensor plate or the like.

(6) Where lever handles are provided, they must be installed with a clear space of not less than 50 mm between the tap and any adjacent surface.

(7) Heated water must be provided and temperature controlled in accordance with Part B2 of NCC Volume Three.

(1) A vertical mirror must be provided at the washbasin, with a reflective surface that—

  1. is not less than 600 mm wide; and
  2. has its bottom edge not more than 900 mm above finished floor level; and
  3. has its top edge not less than 1850 mm above finished floor level.

(2) If a second vertical mirror is provided in the facility, it must have a reflective surface that—

  1. is not less than 600 mm wide; and
  2. has its bottom edge not less than 600 mm above finished floor level; and
  3. has its top edge not less than 1850 mm above finished floor level.

(3) Towel dispensers, hand dryers, soap dispensers and the like must be operable using one hand, and must be installed with their output or operative components—

  1. between 900 mm and 1100 mm above finished floor level; and
  2. not less than 500 mm from any internal corner.

(4) A soap dispenser must be installed above the integrated shelf required by S27C5(4).

(5) A clothing hook must be installed so that it is located—

  1. at a height of between 1200 mm and 1350 mm above finished floor level; and
  2. adjacent to the washbasin; and
  3. not less than 500 mm from any internal corner.

(6) A sling hook with a minimum projection of 50 mm from the wall must be installed beside the change table at a height of 1500 mm above finished floor level.

(7) Disposal bins must be provided as follows:

  1. A sanitary disposal bin in the corner adjacent to the toilet pan.
  2. An incontinence pad disposal bin in the corner adjacent to the change table.

Explanatory information

The purpose of the sling hook is to store the sling when it is not in use.

(1) The change table must be—

  1. permanently installed, with one of the long edges up against a wall and with a retractable safety rail on the opposite side; and
  2. motorised for the purposes of height adjustment; and
  3. height adjustable between 450 mm and 900 mm above finished floor level; and
  4. not less than 700 mm wide; and
  5. not less than 1800 mm long.

(2) The change table must have a maximum safe working load of not less than 180 kg, including when raising or lowering the table.

(3) The change table must not encroach on any required circulation space.

(4) A dispenser for sanitary wipes must be provided.

(5) A shelf not less than 400 mm long and 150 mm wide must be provided.

Changing rails must be installed as two horizontal and parallel rails fixed to a wall, not less than 800 mm long, each with a diameter between 30 mm and 40 mm, and—

  1. the lower rail must be installed between 800 mm and 810 mm above finished floor level; and
  2. the upper rail must be installed between 1000 mm and 1010 mm above finished floor level; and
  3. the rails must be able to withstand a force of not less than 1100 N in any direction.

The entrance door and associated door controls must be automated and must comply with the following:

  1. The threshold must incorporate a smooth transition without a step or lip.
  2. The minimum clear opening width must be—
    1. 1100 mm in locations where beach wheelchairs are likely to be used; or
    2. 950 mm in all other locations.
  3. The doorway must achieve a luminance contrast of at least 30% between—
    1. door leaf and door jamb; or
    2. door leaf and adjacent wall; or
    3. architraves (where used) and adjacent wall; or
    4. door leaf and architrave (where used); or
    5. door jamb and adjacent wall.
  4. The operation of the door must be calibrated such that—
    1. it has a gentle opening and closing movement; and
    2. there is sufficient dwell time for a user to safely travel through the doorway.
  5. The door must be fitted with a fail-safe opening mechanism that opens the door if an obstruction is detected during its closing movement.
  6. Door controls must be located internally and externally—
    1. between 900 mm and 1200 mm above finished floor level; and
    2. not less than 500 mm from any internal corner.
  7. Door control buttons must—
    1. have a minimum diameter of 25 mm; and
    2. be proud of the surrounding surface; and
    3. activate the door operation before the button becomes level with the surrounding surface; and
    4. be of a contrasting colour to the surrounding plate.
  8. The surrounding plates of both internal and external door controls must include the words “Push to Open”.
  9. The following indicator lights must be provided:
    1. “Occupied” and “Vacant” on the external plate.
    2. “Locked” and “Unlocked” on the internal plate.
  10. Braille and tactile signage complying with Specification 15 must identify the door controls.

(1) External signage must incorporate—

  1. the symbol shown in Figure S27C10; and
  2. the words “Accessible Adult Change Facility”.

(2) The symbol required by (1)(a) must have a blue (B21, ultramarine) background with the hoist and table elements shown in white.

(3) Signage must be braille and tactile signage complying with Specification 15.

Figure S27C10 Accessible adult change facility symbol
image-S27C10-accessible-adult-change-facility-symbol.svg

Signage provided within the facility must include the following information for the hoist and change table:

  1. Operating instructions.
  2. Safe working load limits.