NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Filter by state
  • Australian Capital Territory
  • New South Wales
  • Northern Territory
  • Queensland
  • South Australia
  • Tasmania
  • Victoria
  • Western Australia
Filter by zone
  • Climate Zone 1
  • Climate Zone 2
  • Climate Zone 3
  • Climate Zone 4
  • Climate Zone 5
  • Climate Zone 6
  • Climate Zone 7
  • Climate Zone 8
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Filter by state
  • Australian Capital Territory
  • New South Wales
  • Northern Territory
  • Queensland
  • South Australia
  • Tasmania
  • Victoria
  • Western Australia
Filter by zone
  • Climate Zone 1
  • Climate Zone 2
  • Climate Zone 3
  • Climate Zone 4
  • Climate Zone 5
  • Climate Zone 6
  • Climate Zone 7
  • Climate Zone 8
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

2

Specification 2 Descriptions of elements referred to in Specification 1

Specification 2 Descriptions of elements referred to in Specification 1

New for 2022
2019: Sch. 5 (Annex): 1.1
2019: Sch. 5 (Annex): 1.2
2019: Sch. 5 (Annex): 1.3
2019: Sch. 5 (Annex): 1.4
2019: Sch. 5 (Annex): 1.5
2019: Sch. 5 (Annex): 1.6
2019: Sch. 5 (Annex): 2
2019: Sch. 5 (Annex): 3
2019: Sch. 5 (Annex): 3.1
2019: Sch. 5 (Annex): 3.2
2019: Sch. 5 (Annex): 3.3
2019: Sch. 5 (Annex): 5
2019: Sch. 5 (Annex): 6.1
2019: Sch. 5 (Annex): 6.2
2019: Sch. 5 (Annex): 7.1
2019: Sch. 5 (Annex): 7.2
2019: Sch. 5 (Annex): 7.3
2019: Sch. 5 (Annex): 8.1
2019: Sch. 5 (Annex): 8.2
2019: Sch. 5 (Annex): 9
2019: Sch. 5 (Annex): 10
2019: Sch. 5 (Annex): 11.1
2019: Sch. 5 (Annex): 11.2
2019: Sch. 5 (Annex): 11.3
2019: Sch. 5 (Annex): 11.4
2019: Sch. 5 (Annex): 12.1
Table S1C2e FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on not more than 3 sides
Fire protection Minimum thickness (mm) of principal material for FRLs
60/60/60 90/90/90 120/120/120 180/180/180 240/240/240
Concrete cast in-situ — loadbearing 25 30 40 55 75
Concrete cast in-situ — non-loadbearing unplastered 25 30 40 50 75
Concrete cast in-situ — non-loadbearing plastered 13 mm 25 25 30 40 50
Gypsum cast in-situ - - - - 50
Gypsum — perlite or gypsum-vermiculite plaster—sprayed to contour 20 25 35 50 55
Gypsum — perlite or gypsum-vermiculite plaster—sprayed on metal lath 20 20 25 35 45
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2j FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides and with column spaces unfilled
Fire protection Minimum thickness (mm) of principal material for FRLs
60/–/– 90/–/– 120/–/– 180/–/– 240/–/–
Solid calcium-silicate masonry 50 50 50 - -
Solid clay masonry 50 50 65 - -
Solid concrete masonry 50 50 65 - -
Solid gypsum blocks 50 50 50 - -
Hollow terracotta blocks — plastered 13 mm 50 50 65 - -
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2m FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on 4 sides
Fire protection Minimum thickness (mm) of principal material for FRLs
60/–/– 90/–/– 120/–/– 180/–/– 240/–/–
Concrete — cast in-situ 25 40 45 60 90
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour 20 30 40 55 65
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath 20 20 35 40 50
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2g FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces unfilled
Fire protection Minimum thickness (mm) of principal material for FRLs
60/60/60 90/90/90 120/120/120 180/180/180 240/240/240
Solid calcium-silicate masonry 50 50 50 - -
Solid clay masonry 50 50 65 - -
Solid concrete masonry 50 50 65 - -
Solid gypsum blocks 50 50 50 - -
Hollow terracotta blocks — plastered 13 mm 50 50 65 - -
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2b FRLs deemed to be achieved by walls — concrete
Concrete type Minimum thickness (mm) of principal material for FRLs
60/60/60 90/90/90 120/120/120 180/180/180 240/240/240
No fines - - - 150 300
Prestressed See clause S1C2(d)(iv)
Reinforced
Plain - - - 150 170
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2c FRLs deemed to be achieved by walls — gypsum
Gypsum type Minimum thickness (mm) of principal material for FRLs
60/60/60 90/90/90 120/120/120 180/180/180 240/240/240
Solid gypsum blocks 75 90 100 110 125
Gypsum — perlite or gypsum vermiculite-plaster on metal lath and channel (non-loadbearing walls only) 50 50 65 - -
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2i FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides and with column spaces filled
Fire protection Minimum thickness (mm) of principal material for FRLs
60/–/– 90/–/– 120/–/– 180/–/– 240/–/–
Solid calcium-silicate masonry 50 50 50 65 75
Solid clay masonry 50 50 50 75 100
Solid concrete masonry 50 50 50 75 100
Solid gypsum blocks 50 50 50 65 75
Hollow terracotta blocks — plastered 13 mm 50 50 50 75 100
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2h FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides
Fire protection Minimum thickness (mm) of principal material for FRLs
60/–/– 90/–/– 120/–/– 180/–/– 240/–/–
Concrete cast in-situ — loadbearing 25 40 45 65 90
Concrete cast in-situ — non-loadbearing unplastered 35 30 40 50 65
Concrete cast in-situ — non-loadbearing plastered 13 mm 25 25 30 40 50
Gypsum cast in-situ - - - - 50
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour 25 30 40 55 65
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath 20 20 30 40 50
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2f FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces filled
Fire protection Minimum thickness (mm) of principal material for FRLs
60/60/60 90/90/90 120/120/120 180/180/180 240/240/240
Solid calcium-silicate masonry 50 50 50 50 65
Solid clay masonry 50 50 50 65 90
Solid concrete masonry 50 50 50 65 90
Solid gypsum blocks 50 50 50 50 65
Hollow terracotta blocks — plastered 13 mm 50 50 50 65 90
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2a FRLs deemed to be achieved by walls — masonry
Masonry type Minimum thickness (mm) of principal material for FRLs
60/60/60 90/90/90 120/120/120 180/180/180 240/240/240
Ashlar - - - - 300
Calcium silicate See clause S1C2(d)(iv)
Concrete
Fired clay
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2l FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on no more than 3 sides
Fire protection Minimum thickness (mm) of principal material for FRLs
60/–/– 90/–/– 120/–/– 180/–/– 240/–/–
Concrete — cast in-situ 25 30 40 50 65
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour 20 25 35 50 55
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath 20 20 25 35 45
Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.