Specification 4 Design of buildings in cyclonic areasTo clarify that Specification 4 contains requirements for the design of metal roofing cladding assemblies in cyclonic areas.
This specification must be read in conjunction with the provisions of AS/NZS 1170.2. The ABCB commissioned research to establish a national consistent testing regime for metal roof cladding assemblies in cyclonic areas. The results of this research are reflected in Specification 4.
Test for strength: Metal roof cladding, its connections and immediate supporting members must be capable of remaining in position notwithstanding any permanent distortion, fracture or damage that might occur in the sheet or fastenings under the pressure sequences A to G defined in Table S4C2.
Sequence | Number of cycles | Load |
---|---|---|
A | 4500 | 0 to 0.45 Pt |
B | 600 | 0 to 0.6 Pt |
C | 80 | 0 to 0.8 Pt |
D | 1 | 0 to 1.0 Pt |
E | 80 | 0 to 0.8 Pt |
F | 600 | 0 to 0.6 Pt |
G | 4500 | 0 to 0.45 Pt |
To define the expected performance of roof cladding assemblies in cyclonic areas when subjected to the specified test regime (Table S4C2).
Low cycle fatigue cracking of metal roof cladding elements during tropical cyclones is a complex process where small changes in load, geometry or material properties can significantly affect the fatigue performance of the cladding system (includes immediate supports, fixings and cladding). The consequences of failure of an element can quickly lead to more elements progressively failing. These failed elements may become wind driven debris and so pose impact threat to people and other structures.
Table S4C2
The fatigue loading sequence prescribed in Table S4C2 is to simulate the wind load induced by a cyclonic event. In order to have a repeatable standard test that can be performed by different testing laboratories within a reasonable time frame on different types of test equipment, the loading sequences a simplification of the dynamic wind loading environment. In the formulation of the fatigue loading sequence, assumptions such as cyclone counts, load range, cyclone duration, wind direction change, building orientation and building geometry have been made.
If a system does not successfully resist the fatigue loading sequence in Table S4C2 it does not comply.
The test section is to consist of cladding elements, fastenings and immediate supporting members assembled together in a manner identical to those parts of the particular roof which the test section is intended to replicate.
Sequence | Number of cycles | Load |
---|---|---|
A | 4500 | 0 to 0.45 Pt |
B | 600 | 0 to 0.6 Pt |
C | 80 | 0 to 0.8 Pt |
D | 1 | 0 to 1.0 Pt |
E | 80 | 0 to 0.8 Pt |
F | 600 | 0 to 0.6 Pt |
G | 4500 | 0 to 0.45 Pt |