NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Filter by state
  • Australian Capital Territory
  • New South Wales
  • Northern Territory
  • Queensland
  • South Australia
  • Tasmania
  • Victoria
  • Western Australia
Filter by zone
  • Climate Zone 1
  • Climate Zone 2
  • Climate Zone 3
  • Climate Zone 4
  • Climate Zone 5
  • Climate Zone 6
  • Climate Zone 7
  • Climate Zone 8
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Filter by state
  • Australian Capital Territory
  • New South Wales
  • Northern Territory
  • Queensland
  • South Australia
  • Tasmania
  • Victoria
  • Western Australia
Filter by zone
  • Climate Zone 1
  • Climate Zone 2
  • Climate Zone 3
  • Climate Zone 4
  • Climate Zone 5
  • Climate Zone 6
  • Climate Zone 7
  • Climate Zone 8
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

40

Specification 40 Lighting and power control devices

Specification 40 Lighting and power control devices

2019: Spec J6: 1

To clarify the extent of items covered by this Specification.

2019: Spec J6: 2

To detail the required performance of corridor light timers.

Lighting timers are time delay switches that activate a section of lighting when the button is pressed, and switches the lights off again after a predetermined time, provided the button is not pushed again. The provisions for the minimum distance of travel into the space, and for the 5% of lighting that must remain on in larger areas, are designed to reduce the situation of walking into a dark space to switch on the lighting. In many applications the exit signs will provide the continuous 5% of lighting required.

2019: Spec J6: 3

To detail the required performance of time switches.

Time switches are devices that turn lights or equipment on and off at predetermined and pre-programmed times. S40C3(2) and S40C3(3) provides specifications for time switches controlling internal and external lighting. S40C3(4) provides specifications for time switches that operate boiling and chilled water storage units.

2019: Spec J6: 4

To detail the required performance of motion detectors.

The motion detector requirements are similar to those of the corridor lighting timer, except that a motion detector is activated by the motion of people, and the operation of the lighting is maintained while the motion continues.


The advantages of motion detectors are: 
•    a person does not need to find the button; and 
•    a person can enter the space with more confidence as another person already within the space would have activated the lighting; and 
•    the time duration for the lighting to be activated does not need to be as long as it does with a corridor lighting timer because the lighting is continuously reset, whereas with a timer, the duration has to be set for the slowest person travelling the greatest distance. 
 

The clause specifies different requirements for motion detectors for four situations— 
•    a Class 2, 3 or Class 9c residential care building other than sole-occupancy units: and 
•    a Class 5, 6, 7, 8, 9a and 9b building; and 
•    outside a building, including when controlling a light in a carpark entry zone; and 
•    when in a fire-isolated stairway, passageway or ramp. 
 

Fire-isolated exit lights 
Unlike other lights required to be controlled by a motion sensor, in a fire-isolated stairway, passageway or ramp it is acceptable for lights to be dimmed to at least 30% of their peak power instead of being switched off.

2019: Spec J6: 5