in every storey of a Class 5, 6, 7, 8 or 9 building where the storey has a floor area more than 300 m2—
in every passageway, corridor, hallway, or the like, that is part of the path of travel to an exit; and
in any room having a floor area more than 100 m2 that does not open to a corridor or space that has emergency lighting or to a road or open space; and
in any room having a floor area more than 300 m2, except that—
in a farm building any area primarily used for the storage of hay can be excluded when calculating the floor area of the storey or room of the building for the purpose of determining emergency lighting requirements; and
emergency lighting is not required in a farm building where automatic back-up power is provided by a fuel driven back-up generator or where no artificial lighting is provided in the building; and
in a bulk grain storage facility the spacing of emergency lights can be increased to twice the distance required for Class 7 buildings; and
in every passageway, corridor, hallway, or the like, having a length of more than 6 m from the entrance doorway of any sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building to the nearest doorway opening directly to—
the floor area of the unit is more than 300 m2; and
an exit from the unit does not open to a road or open space or to an external stairway, passageway, balcony or ramp, leading directly to a road or open space; and
in every room or space to which there is public access in every storey in a Class 6 or 9b building if—
any point on the floor of that storey is more than 20 m from the nearest doorway leading directly to a stairway, ramp, passageway, road or open space; or
egress from that storey involves a vertical rise within the building of more than 1.5 m, or any vertical rise if the storey concerned does not admit sufficient light; or
the storey provides a path of travel from any other storeyrequired by (i), (ii) or (iii) to have emergency lighting; and