NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
11
Specification 11 Smoke-proof walls in health-care and residential care buildingsTo prescribe construction requirements for smoke-proof walls required by C3D6 in health-care and residential care buildings.
Specification 11 applies to smoke-proof walls in:
Smoke-proof walls required by C3D6 in Class 9a health-care buildings must comply with the following:
To prescribe construction requirements for smoke-proof walls required by C3D6 in Class 9a health-care buildings.
S11C2 applies to smoke-proof walls in Class 9a health-care buildings.
Smoke-proof walls required by C3D6 in Class 9c buildings must comply with the following:
To prescribe construction requirements for smoke-proof walls required by C3D6 in Class 9c buildings.
S11C3 applies to smoke-proof walls in Class 9c buildings.
The purpose of the smoke-proof walls is to create a “smoke compartment” to stop or limit the spread of smoke to adjoining areas. It is therefore important that all penetrations of the walls and ceiling of the “smoke compartment” be sealed against the penetration of smoke. This includes any light fitting in the flush plasterboard ceiling referred to in S11C3(a)(iii).
A wall lining need only be applied to one side of the wall to achieve compliance with S11C3.
A door required by C3D6 or this Specification to be smoke-proof or have an FRL, other than one that serves a fire compartment provided with a zone pressurisation system in accordance with AS 1668.1, must provide a smoke reservoir by not extending within 400 mm of the underside of—
To limit the spread of smoke between smoke-zones by the use of smoke-reservoirs.