NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

E2

Part E2 Smoke hazard management

Part E2 Smoke hazard management

Introduction to this Part

This Part is intended to reduce the risk of injury or loss of life for occupants due to the effects of smoke, including inhalation, if a fire occurs in a building. It provides for automatic warning of the presence of smoke or fire, and measures to ensure conditions within evacuation routes remain tenable long enough for occupants evacuate safely and to facilitate fire brigade intervention.

Objectives

The Objective of this Part is to—

  1. safeguard occupants from illness or injury by warning them of a fire so that they may safely evacuate; and
  2. safeguard occupants from illness or injury while evacuating during a fire.

Safeguard occupants from illness and injury

Part E2 aims to safeguard building occupants from illness or injury from the products of combustion (including smoke and toxic gases). E2O1(a) deals with warning of a fire and E2O1(b) deals with requirements for evacuating.

Smoke and toxic gases kill

Smoke and toxic gases are the main causes of death in building fires. Such deaths have occurred in locations remote from the fire to where smoke and gases have spread. Smoke and toxic gases cause disorientation, incapacitation and ultimately death, depending on the concentration and length of exposure.

Management of the smoke and toxic gas hazard is crucial for occupant safety. This is best achieved through a combination of active and passive measures, such as:

  • building materials and finishes;
  • compartmentation;
  • egress;
  • smoke and toxic gas detection;
  • fire suppression; and
  • smoke and toxic gas control by mechanical means.

Part E2 addresses some of the active measures which, together with the relevant provisions in other Parts of the BCA, provide appropriate strategies for the protection of occupants.

Functional Statements

A building is to be provided with safeguards so that—

  1. occupants are warned of a fire in the building so that they may safely evacuate; and
  2. occupants have time to safely evacuate before the environment in any evacuation route becomes untenable from the effects of fire.

E2F1 requires that a building have safeguards to warn occupants of a fire so they may safely evacuate before the conditions in any evacuation route become untenable, due to the effects of fire.

Performance Requirements

In a building providing sleeping accommodation, occupants must be provided with automatic warning on the detection of smoke so they may evacuate in the event of a fire to a safe place.

Applications

E2P1 only applies to a Class 2, 3, 9a or 9c building or Class 4 part of a building.

Sleeping accommodation—smoke alarms

A Class 2, 3, 9a and 9c building and a Class 4 part must contain automatic warning on the detection of smoke for occupants in sleeping areas, so they may be alerted to a fire.

(1) In the event of a fire in a building the conditions in any evacuation route must be maintained for the period of time occupants take to evacuate the part of the building so that—

  1. the temperature will not endanger human life; and
  2. the level of visibility will enable the evacuation route to be determined; and
  3. the level of toxicity will not endanger human life.

(2) The period of time occupants take to evacuate referred to in (1) must be appropriate to—

  1. the number, mobility and other characteristics of the occupants; and
  2. the function or use of the building; and
  3. the travel distance and other characteristics of the building; and
  4. the fire load; and
  5. the potential fire intensity; and
  6. the fire hazard; and
  7. any active fire safety systems installed in the building; and
  8. fire brigade intervention.

Limitations

E2P2 does not apply to an open-deck carpark or open spectator stand.

Evacuation routes must remain tenable

Occupants must be given time to evacuate before the onset of untenable conditions. E2P2(1) specifies these conditions as dangerous temperatures, low visibility and dangerous levels of toxicity.

Hence, evacuation time must take account of a range of factors including the following:

  • E2P2(2)(a)—the difficulty of evacuation and/or rescue. An example is where there is a large number of occupants, or they are not mobile, such as patients in a hospital or residents of an elderly people’s home. Here the evacuation time could be high.
  • E2P2(2)(b)—the likelihood or risk of a fire occurring in the building, which can have an influence on risk levels during evacuation and along the evacuation route.
  • E2P2(2)(c)—the time necessary to travel to an exit, and the difficulty of evacuation and/or rescue.
  • E2P2(2)(d)(e) and (f)—the size, load or intensity of any fire in the building, which has a clear influence on the speed of fire development and spread, and heat and toxic gas characteristics.
  • E2P2(2)(g)—the fire safety systems in the building can influence the rate of fire spread and intensity and toxic gas development (e.g. if a sprinkler system is installed, it should extinguish the fire or reduce its growth rate).
  • E2P2(2)(h)—the firefighting operations of the fire brigade and the resources available to it, which influences the extent to which a fire can develop before the fire brigade is likely to bring it under control.

Under its Limitation provision, E2P2 does not apply to open-deck carparks or open spectator stands where the smoke and hot gases can vent naturally, thereby allowing occupants to safely evacuate.

 

Verification Methods

Compliance with E2P1 and E2P2 is verified when a building is designed in accordance with C1V4.

Deemed-to-Satisfy Provisions

(1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements E2P1 and E2P2 are satisfied by complying with—

  1. E2D2 to E2D21; and
  2. in a building containing an atrium, Part G3; and
  3. in a building in an alpine area, Part G4; and
  4. for additional requirements for Class 9b buildings, Part I1.

SA E2D1 Deemed-to-Satisfy Provisions2019: E2.0

Delete subclause E2D1(1) and insert E2D1(1) as follows:

(1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements E2P1 and E2P2 are satisfied by complying with—

  1. E2D2 to SA E2D22; and
  2. in a building containing an atrium, Part G3; and
  3. in a building in an alpine area, Part G4; and
  4. for additional requirements for Class 9b buildings, Part I1.

(2) Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2G2(3) and A2G4(3) as applicable.

To clarify that the requirements of E2P1 and E2P2 will be satisfied if compliance is achieved with E2D2 to E2D21 in the case of all buildings, Part G3 in the case of buildings with an atrium, Part G4 in the case of buildings in alpine areas, Part I1 in the case of theatres, stages and public halls.

E2D2 to E2D21 and E2P1 and E2P2

Where a solution is proposed to comply with the Deemed-to-Satisfy Provisions, except in buildings containing atriums, compliance with E2D2 to E2D21 achieves compliance with E2P1 and E2P2.

Buildings with atriums

In addition to achieving compliance with E2D2 to E2D21, to achieve compliance with E2P1 and E2P2 buildings with atriums must also comply with Part G3.

Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2G2(3) and A2G4(3) as applicable. (See commentary on Part A2).

 

(1) The Deemed-to-Satisfy Provisions of this Part do not apply to—

  1. an open-deck carpark; or
  2. an open spectator stand; or
  3. a Class 8 electricity network substation with a floor area not more than 200 m2, located within a multi-classified building.

(2) In addition to the Deemed-to-Satisfy Provisions of E2D3 to E2D13, the following specific Deemed-to-Satisfy Provisions apply to the following Class 6 and Class 9b buildings:

  1. For Class 6 buildings, in fire compartments more than 2000 m2
    1. not containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit — must comply with E2D14; or
    2. containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit — must comply with E2D15.
  2. For Class 9b assembly buildings
    1. nightclubs, discotheques and the like — must comply with E2D16; and
    2. exhibition halls — must comply with E2D17; and
    3. theatres and public halls — must comply with E2D18; and
    4. theatres and public halls (not covered by E2D18) including lecture theatres and cinema/auditorium complexes — must comply with E2D19; and
    5. other assembly buildings (not listed in (i) to (iv)) excluding schools — must comply with E2D20.

(3) The smoke exhaust and smoke-and-heat vent provisions of this Part do not apply to any area not used by occupants for an extended period of time such as a storeroom with a floor area less than 30 m2, sanitary compartment, plant room or the like.

To specify when E2D3 to E2D21 do not apply.

Open-deck carparks, open spectator stands and Class 8 electricity network substations—E2D2(2)

E2D2(2) and E2D3 to E2D21 do not apply to open-deck carparks or open spectator stands. E2P2 does not apply to such buildings because the smoke and hot gases can vent naturally.

The Deemed-to-Satisfy Provisions of Part E2 do not apply to small Class 8 electricity network substations, located in a multi-classified building. These smaller substations are usually located within a “host” building and the associated electrical equipment has its own sensitive dedicated systems that provide a rapid response signal to a central control room that is constantly staffed.

Smoke exhaust systems and smoke-and-heat vents—E2D2(3)

Under E2D2(3), the E2D3 to E2D21 provisions regarding smoke exhaust systems and smoke-and-heat vents do not apply to small areas used for short periods.

A small area will be easily evacuated before smoke build-up and if the area is only used for short periods, the risk of occupants being trapped in it during a fire is low.

Application of E2D4 to E2D13—General provisions—whole building strategies

E2D4 to E2D13 provide smoke hazard management strategies structured to help application to buildings of mixed classification. In the case of a multi-classified building, each classifiable part must comply with the relevant provisions for its classification. Certain Class 6 and Class 9b parts of buildings must also comply with the specific provisions in E2D14 to E2D20.

Application of E2D4 to E2D13—General provisions—zone pressurisation systems

Where zone pressurisation systems are specified in various locations in E2D4 to E2D13 to be in accordance with AS 1668.1, the provision states that zone pressurisation systems only apply between vertically separated fire compartments and not horizontal fire compartments.

Application of E2D14 to E2D20—Specific provisions—Class 6 and 9b buildings

The provisions of E2D14 to E2D20 are additional strategies which only apply to certain Class 6 and Class 9b buildings where there is a high risk that occupants may not be able to safely evacuate the fire-affected compartment. This risk may be due to factors such as:

  • building design;
  • function;
  • usage;
  • fire load; or
  • nature of occupancy.

Occupants of such buildings are also not necessarily familiar with the building or the procedures for evacuation.

Application of E2D14 to E2D20—Specific provisions—Maintenance of safe conditions in evacuation routes

E2D14 to E2D20 address requirements under E2P2 in terms of maintaining safe conditions in any evacuation route within the fire-affected compartment of Class 6 and Class 9b buildings, for the period of time it would take occupants to evacuate that part of the building.

(1) An air-handling system which does not form part of a smoke hazard management system in accordance with E2D4 to E2D20 and which recycles air from one fire compartment to another fire compartment or operates in a manner that may unduly contribute to the spread of smoke from one fire compartment to another fire compartment must, subject to (2), be designed and installed—

  1. to operate as a smoke control system in accordance with AS 1668.1; or
  2. such that it—
    1. incorporates smoke dampers where the air-handling ducts penetrate any elements separating the fire compartments served; and
    2. is arranged such that the air-handling system is shut down and the smoke dampers are activated to close automatically by smoke detectors complying with clause 7.5 of AS 1670.1.

(2) For the purposes of (1), each sole-occupancy unit in a Class 2 or 3 building is treated as a separate fire compartment.

(3) Miscellaneous air-handling systems covered by Sections 5 and 6 of AS 1668.1 serving more than one fire compartment (other than a carpark ventilation system) and not forming part of a smoke hazard management system must comply with these Sections of the Standard.

(4) A smoke detection system must be installed in accordance with S20C6 to operate AS 1668.1 systems that are provided for zone pressurisation and automatic air pressurisation for fire-isolated exits.

To specify the requirements for minimising the smoke risks.

Air-handling system which is not part of a smoke hazard management system—E2D3(1)

E2D3(1) requires that an air-handling system that is not part of a smoke hazard management system be designed and installed with suitable strategies to ensure that, during a fire, it does not:

  • recycle air (and therefore smoke) from one fire compartment to another; or
  • otherwise contribute to the spread of smoke between fire compartments.

Comply with AS 1668.1 —E2D3(1)(a)

The effect of E2D3(1)(a) is that in a fire, an air-handling system must either operate as a smoke control system in accordance with AS 1668.1 (as specified in E2D3(1)(a)) or shut down (as specified in E2D3(1)(b)).

A smoke purging system, in accordance with AS 1668.1, is allowable in buildings not covered by the general provisions in E2D4 to E2D13, and, in some instances, in conjunction with other measures in accordance with E2D4 to E2D13.

Non-smoke control system—E2D3(1)

An air-handling system not designed as a smoke control system must comply with the requirements set out in E2D3(1) as follows:

  • Automatic smoke dampers—E2D3(1)(b)(i): Where the air-handling system is shut down in fire mode, it must incorporate automatic smoke dampers where the ducts penetrate any fire barriers. This requirement may apply to an air-handling system which supplies outside air to a group of residential sole-occupancy units.
  • System shut down—E2D3(1)(b)(ii): The air handling system must shut down, and smoke detectors must automatically activate smoke dampers.
  • Class 2 and Class 3 buildings—E2D3(2): Sole-occupancy units in Class 2 and Class 3 buildings are, under E2D3(2), regarded as separate fire compartments.

Sections 5 and 6 of AS 1668.1—E2D3(3)

Air-handling systems, other than one in a carpark, serving more than one fire compartment covered by Sections 5 and 6 of AS 1668.1 must be designed and installed in compliance with those sections of the Australian Standard. This will restrict the spread of smoke between fire compartments.

Provisions on the operation of carpark ventilation systems during a fire in the carpark are included under the general provisions in E2D4 to E2D13.

Smoke detection systems to operate AS 1668.1 smoke control systems—E2D3(4)

An AS 1668.1 system for zone pressurisation and automatic air pressurisation for fire-isolated exits must be controlled by a smoke detection and alarm system installed in compliance with Specification 20. Activation of these systems also requires the activation of a building occupant warning system.

(1) A part of a building listed in (2) must be provided with—

  1. an automatic air pressurisation system for fire-isolated exits in accordance with AS 1668.1; or
  2. open access ramps or balconies in accordance with D3D6.

(2) The requirements of (1) apply to—

  1. a required fire-isolated stairway, including any associated fire-isolated passageway or fire-isolated ramp serving—
    1. any storey above an effective height of 25 m; or
    2. more than 2 below ground storeys, not counted in the rise in storeys in accordance with C2D3; or
    3. an atrium to which Part G3 applies; or
    4. a Class 9a building with a rise in storeys of more than 2; or
    5. a Class 9c building with a rise in storeys of more than 2; or
    6. a Class 3 building used as a residential care building with a rise in storeys of more than 2; and
  2. a required fire-isolated passageway or fire-isolated ramp with a length of travel more than 60 m to a road or open space.

(3) An automatic air pressurisation system for a fire-isolated exit must serve the entire exit.

Notes

Refer to D2D12(4) for pressurisation of a fire-isolated exit having more than 2 access doorways from within the same storey.

Fire-isolated exits enable the safe evacuation of occupants, and also aid fire brigade access. Smoke must not unduly affect the conditions in such exits during an evacuation.

To minimise smoke intrusion, the exits may need to be pressurised with outside air for the entire exit route. See the following examples. Alternatively, the exits may be provided with open access ramps or balconies from which smoke can vent naturally.

Examples

Pressurised fire-isolated exits are required where:

  • tenable conditions must be maintained for an extended period due to a long distance of travel, such as exits which serve storeys above 25 metres in effective height or which are more than 60 metres in length to a road or open space;
  • tenable conditions must be maintained for an extended period of time to enable the safe evacuation of non- ambulatory occupants, such as in health-care buildings with a rise in storeys of more than 2;
  • the exits are the only possible means of escape, such as those serving basements more than two storeys below ground; or
  • the risk of smoke intrusion into the exits is high on account of a particular building characteristic, such as is generally the case in a building containing an atrium.

An automatic smoke detection and alarm system complying with Specification 20 must be provided to the following:

  1. A Class 2 or 3 building which is more than 25 m in effective height.
  2. A Class 2 or 3 part of a building, or a Class 4 part of a building, in a building which is more than 25 m in effective height.

Notes

Refer to C3D15 for division of public corridors greater than 40 m in length.

In buildings more than 25 metres in effective height, tenable conditions need to be maintained in the fire-isolated exits and, where practicable, in other parts of the building to enable the staged evacuation of occupants.

Occupants of such buildings may continue to occupy compartments remote from the fire for an extended time before evacuation. Accordingly, suitable measures must be adopted to minimise the spread of smoke from the fire-affected compartment to non-affected compartments by way of a number of potential leakage paths.

These paths include lift shafts, air-handling ducts, services risers, building penetrations, spandrels, and the like, through which smoke can be driven by buoyancy, expansion, stack and wind effects, and air-handling systems.

In order to minimise the spread of smoke, a zone pressurisation system is considered necessary in buildings more than 25 metres in effective height. This does not apply to the residential parts of a building in view of:

  • the alternative protection provided by the fire compartmentation of sole-occupancy units;
  • separation of public corridors by bounding construction; and
  • division of such corridors by smoke-proof walls into lengths of not more than 40 metres (see C3D15).

Additionally, this requirement does not apply to a building that contains only one single fire compartment containing a Class 5, 6, 7b, 8 or 9b part (or a combination of these classes in the same fire compartment) in an otherwise Class 2, 3, 9a or 9c building. Reference to a Class 2, 3, 9a or 9c building does not include a building that also contains a Class 7a carpark (see Figure E2D5). The reasons for this exemption are:

  • the provision of a zone pressurisation system is considered inappropriate for a single compartment in a building; and
  • any single fire compartment Class 9b building or Class 6 building with a floor area greater than 2000 mis also subject to the provisions of E2D14 to E2D20, ensuring that smoke hazard management considerations are applied; and
  • to require compliance could create an anomaly with the exemption of sporting complexes, including gymnasiums and swimming pools from required smoke hazard management measures under E2D14 to E2D20.

Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings to provide early warning to occupants who may be asleep, confused, or non-ambulatory and dependent on assistance.

E2D4 to E2D13 provisions are additional to other safety provisions for buildings with an effective height of more than 25 metres.

Figure E2D5: Zone pressurisation concession

Image
Figure E2D5: Zone pressurisation concession

Figure Notes

  • Building A: Although the building has only one fire compartment containing a Class 5, 6, 7b, 8 or 9b part, the concession does not apply because the building contains a Class 7a part.
  • Building B: A zone pressurisation system is required because the building contains more than one fire compartment containing a Class 5, 6, 7b, 8 or 9b part.
  • Building C: A zone pressurisation system is not required because the building has only one fire compartment containing a Class 5, 6, 7b, 8 or 9b part and the remainder of the building is solely Class 2.

(1) A Class 5, 6, 7b, 8 or 9b building or part of a building must be provided with a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1, if the building is more than 25 m in effective height.

(2) The requirements of (1) do not apply to a building that has a fire compartment containing a Class 5, 6, 7b, 8 or 9b part (or a combination of these classes in the same fire compartment) where there is only one fire compartment containing these classifications in an otherwise Class 2, 3, 9a or 9c building.

(3) For the purposes of (1), ‘vertically separated fire compartments’ are fire compartments above and below each other, and not fire compartments within the same storey.

Notes

Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.

In buildings more than 25 metres in effective height, tenable conditions need to be maintained in the fire-isolated exits and, where practicable, in other parts of the building to enable the staged evacuation of occupants.

Occupants of such buildings may continue to occupy compartments remote from the fire for an extended time before evacuation. Accordingly, suitable measures must be adopted to minimise the spread of smoke from the fire-affected compartment to non-affected compartments by way of a number of potential leakage paths.

These paths include lift shafts, air-handling ducts, services risers, building penetrations, spandrels, and the like, through which smoke can be driven by buoyancy, expansion, stack and wind effects, and air-handling systems.

In order to minimise the spread of smoke, a zone pressurisation system is considered necessary in buildings more than 25 metres in effective height. This does not apply to the residential parts of a building in view of:

  • the alternative protection provided by the fire compartmentation of sole-occupancy units;
  • separation of public corridors by bounding construction; and
  • division of such corridors by smoke-proof walls into lengths of not more than 40 metres (see C3D15).

Additionally, this requirement does not apply to a building that contains only one single fire compartment containing a Class 5, 6, 7b, 8 or 9b part (or a combination of these classes in the same fire compartment) in an otherwise Class 2, 3, 9a or 9c building. Reference to a Class 2, 3, 9a or 9c building does not include a building that also contains a Class 7a carpark (see Figure E2D6). The reasons for this exemption are:

  • the provision of a zone pressurisation system is considered inappropriate for a single compartment in a building; and
  • any single fire compartment Class 9b building or Class 6 building with a floor area greater than 2000 mis also subject to the provisions of E2D14 to E2D20, ensuring that smoke hazard management considerations are applied; and
  • to require compliance could create an anomaly with the exemption of sporting complexes, including gymnasiums and swimming pools from required smoke hazard management measures under E2D14 to E2D20.

Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings to provide early warning to occupants who may be asleep, confused, or non-ambulatory and dependent on assistance.

E2D4 to E2D13 provisions are additional to other safety provisions for buildings with an effective height of more than 25 metres.

Figure E2D6: Zone pressurisation concession

Image
Figure E2D6: Zone pressurisation concession

Figure Notes

  • Building A: Although the building has only one fire compartment containing a Class 5, 6, 7b, 8 or 9b part, the concession does not apply because the building contains a Class 7a part.
  • Building B: A zone pressurisation system is required because the building contains more than one fire compartment containing a Class 5, 6, 7b, 8 or 9b part.
  • Building C: A zone pressurisation system is not required because the building has only one fire compartment containing a Class 5, 6, 7b, 8 or 9b part and the remainder of the building is solely Class 2.

(1) A Class 9a building must be provided with—

  1. an automatic smoke detection and alarm system complying with Specification 20; and
  2. a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1,

if the building is more than 25 m in effective height.

(2) For the purposes of (1), ‘vertically separated fire compartments’ are fire compartments above and below each other, and not fire compartments within the same storey.

Notes

A building more than 25 m in effective height requires a sprinkler system under E1D4.

In buildings more than 25 metres in effective height, tenable conditions need to be maintained in the fire-isolated exits and, where practicable, in other parts of the building to enable the staged evacuation of occupants.

Occupants of such buildings may continue to occupy compartments remote from the fire for an extended time before evacuation. Accordingly, suitable measures must be adopted to minimise the spread of smoke from the fire-affected compartment to non-affected compartments by way of a number of potential leakage paths.

These paths include lift shafts, air-handling ducts, services risers, building penetrations, spandrels, and the like, through which smoke can be driven by buoyancy, expansion, stack and wind effects, and air-handling systems.

In order to minimise the spread of smoke, a zone pressurisation system is considered necessary in buildings more than 25 metres in effective height. This does not apply to the residential parts of a building in view of:

  • the alternative protection provided by the fire compartmentation of sole-occupancy units;
  • separation of public corridors by bounding construction; and
  • division of such corridors by smoke-proof walls into lengths of not more than 40 metres (see C3D15).

Additionally, this requirement does not apply to a building that contains only one single fire compartment containing a Class 5, 6, 7b, 8 or 9b part (or a combination of these classes in the same fire compartment) in an otherwise Class 2, 3, 9a or 9c building. Reference to a Class 2, 3, 9a or 9c building does not include a building that also contains a Class 7a carpark (see Figure E2D7). The reasons for this exemption are:

  • the provision of a zone pressurisation system is considered inappropriate for a single compartment in a building; and
  • any single fire compartment Class 9b building or Class 6 building with a floor area greater than 2000 mis also subject to the provisions of E2D14 to E2D20, ensuring that smoke hazard management considerations are applied; and
  • to require compliance could create an anomaly with the exemption of sporting complexes, including gymnasiums and swimming pools from required smoke hazard management measures under E2D14 to E2D20.

Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings to provide early warning to occupants who may be asleep, confused, or non-ambulatory and dependent on assistance.

E2D4 to E2D13 provisions are additional to other safety provisions for buildings with an effective height of more than 25 metres.

Figure E2D7: Zone pressurisation concession

Image
Figure E2D7: Zone pressurisation concession

Figure Notes

  • Building A: Although the building has only one fire compartment containing a Class 5, 6, 7b, 8 or 9b part, the concession does not apply because the building contains a Class 7a part.
  • Building B: A zone pressurisation system is required because the building contains more than one fire compartment containing a Class 5, 6, 7b, 8 or 9b part.
  • Building C: A zone pressurisation system is not required because the building has only one fire compartment containing a Class 5, 6, 7b, 8 or 9b part and the remainder of the building is solely Class 2.

In a Class 2 and 3 building or part of a building, or Class 4 part of a building, if the building is not more than 25 m in effective height

  1. it must be provided with an automatic smoke detection and alarm system complying with Specification 20; and
  2. where a required fire-isolated stairway serving the Class 2 or 3 parts also serves one or more storeys of Class 5, 6, 7 (other than an open-deck carpark), 8 or 9b parts—
    1. the fire-isolated stairway, including any associated fire-isolated passageway or fire-isolated ramp, must be provided with an automatic air pressurisation system for fire-isolated exits in accordance with AS 1668.1; or
    2. the Class 5, 6, 7 (other than an open-deck carpark), 8 and 9b parts must be provided with—
      1. an automatic smoke detection and alarm system complying with Specification 20; or
      2. a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; and
  3. where a required fire-isolated stairway serving the Class 4 part also serves one or more storeys of Class 5, 6, 7 (other than an open-deck carpark), 8 or 9b parts—
    1. a system complying with (b)(i) or (b)(ii) must be installed; or
    2. a smoke alarm or detector system complying with Specification 20 must be provided except that alarms or detectors need only be installed adjacent to each doorway into each fire-isolated stairway (set back horizontally from the doorway by a distance of not more than 1.5 m) to initiate a building occupant warning system for the Class 4 part.

Notes

  1. Refer to C3D15 for division of public corridors greater than 40 m in length.
  2. Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.

In buildings less than 25 metres in effective height, the necessary levels of protection may be achieved by measures other than zone pressurisation, depending on the Class and rise in storeys of the building.

In buildings other than health-care buildings, zone pressurisation may be substituted by either stairway pressurisation, smoke detection, or sprinkler protection. The rise in storeys before which the provisions become applicable depends on the building’s classification and use.

The above measures do not apply to the residential parts of a building because of the passive protection provided to such parts. However, where one or more fire-isolated exits join residential and non-residential parts, other than open-deck carparks, the fire-isolated exits must either be pressurised, or the non-residential parts provided with smoke detection or sprinkler protection. This is necessary to compensate for the potential additional hazard associated with the particular mix of Classes.

In health-care buildings, zone pressurisation may be substituted by a sprinkler system, providing residential sprinkler heads are used in patient care areas. The quick response of residential sprinkler heads promotes life safety by limiting fire growth and smoke development. Where zone control is not adopted, the air-handling systems must generally be shut down not only to maintain the integrity of the smoke and fire compartmentation, but also to minimise the spread of smoke within the fire-affected compartment.

Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings.

(1) A building not more than 25 m in effective height that—

  1. is a Class 5 or 9b school building or part of a building having a rise in storeys of more than 3; or
  2. is a Class 6, 7b, 8 or 9b building (other than a school) or part of a building having a rise in storeys of more than 2; or
  3. has a rise in storeys of more than 2 and contains—
    1. a Class 5 or 9b school part; and
    2. a Class 6, 7b, 8 or 9b (other than a school) part,

must meet the requirements of (2).

(2) A building referred to in (1) must be provided with—

  1. in each required fire-isolated stairway, including any associated fire-isolated passageway or fire-isolated ramp, an automatic air pressurisation system for fire-isolated exits in accordance with AS 1668.1; or
  2. a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1, if the building has more than one fire compartment; or
  3. an automatic smoke detection and alarm system complying with Specification 20; or
  4. a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

(3) For the purposes of (2), vertically separated fire compartments are fire compartments above and below each other, and not fire compartments within the same storey.

In buildings less than 25 metres in effective height, the necessary levels of protection may be achieved by measures other than zone pressurisation, depending on the Class and rise in storeys of the building.

In buildings other than health-care buildings, zone pressurisation may be substituted by either stairway pressurisation, smoke detection, or sprinkler protection. The rise in storeys before which the provisions become applicable depends on the building’s classification and use.

The above measures do not apply to the residential parts of a building because of the passive protection provided to such parts. However, where one or more fire-isolated exits join residential and non-residential parts, other than open-deck carparks, the fire-isolated exits must either be pressurised, or the non-residential parts provided with smoke detection or sprinkler protection. This is necessary to compensate for the potential additional hazard associated with the particular mix of Classes.

In health-care buildings, zone pressurisation may be substituted by a sprinkler system, providing residential sprinkler heads are used in patient care areas. The quick response of residential sprinkler heads promotes life safety by limiting fire growth and smoke development. Where zone control is not adopted, the air-handling systems must generally be shut down not only to maintain the integrity of the smoke and fire compartmentation, but also to minimise the spread of smoke within the fire-affected compartment.

Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings.

NCC Blurbs

(1) In a Class 5, 6, 7, 8 or 9 building of not more than 25 m in effective height, and which exceeds 18 000 m2 in floor area or 108 000 m3 in volume, the building must be provided with—

  1. if the ceiling height of the fire compartment is not more than 12 m—
    1. an automatic smoke exhaust system in accordance with Specification 21; or
    2. automaticsmoke-and-heat vents in accordance with Specification 22; or
  2. if the ceiling height of the fire compartment is more than 12 m, an automatic smoke exhaust system in accordance with Specification 21.

(2) For the purposes of (1), reference to ‘the building’ being provided with specified measures, means to the nominated classes within the building.

Notes

  1. Refer to E2D14 and E2D15 for specific provisions applicable to a Class 6 building or part of a building (in a fire compartment having a floor area of more than 2000 m2).
  2. Refer to NSW E2D16 to NSW E2D19 for specific provisions applicable to a Class 9b building or part of a building.
  3. Refer to E2D5 and E2D8 where a Class 5, 6, 7b, 8 and 9b building contains a Class 2, 3 or 4 part.
NCC Title
Buildings not more than 25 m in effective height: large isolated buildings subject to C3D4
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Buildings not more than 25 m in effective height: large isolated buildings subject to C3D4

(1) In a Class 7 or 8 building of not more than 25 m in effective height, and which does not exceed 18 000 m2 in floor area nor exceed 108 000 m3 in volume, the building must be provided with—

  1. a sprinkler system complying with Specification 17, and provided with perimeter vehicular access complying with C3D5(2); or
  2. an automatic fire detection and alarm system complying with AS 1670.1 and monitored in accordance with S20C8; or
  3. an automatic smoke exhaust system in accordance with Specification 21; or
  4. automaticsmoke-and-heat vents in accordance with Specification 22; or
  5. natural smoke venting, with ventilation openings distributed as evenly as practicable and comprising permanent openings at roof level with a free area not less than 1.5% of floor area and low level openings which may be permanent or readily openable with a free area not less than 1.5% of floor area.

(2) In a Class 5, 6, 7, 8 or 9 building of not more than 25 m in effective height, and which exceeds 18 000 m2 in floor area or 108 000 m3 in volume, the building must be provided with—

  1. if the ceiling height of the fire compartment is not more than 12 m—
    1. an automatic smoke exhaust system in accordance with Specification 21; or
    2. automaticsmoke-and-heat vents in accordance with Specification 22; or
  2. if the ceiling height of the fire compartment is more than 12 m, an automatic smoke exhaust system in accordance with Specification 21.

(3) For the purposes of (1) and (2), reference to ‘the building’ being provided with specified measures, means to the nominated classes within the building.

Notes

  1. Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.
  2. Refer to E2D5 and E2D8 where a Class 5, 6, 7b, 8 and 9b building contains a Class 2, 3 or 4 part.

Large Class 7 or 8 buildings subject to C3D4

These provisions set out the smoke hazard management measures for large isolated Class 7 or 8 buildings subject to the requirements of C3D4(a) with a floor area of 18 000 m2 or less and a volume of 108 000 m3 or less. Such buildings are required to have:

Large Class 5 to 9 buildings subject to C3D4

These provisions set out the smoke hazard management measures for large isolated Class 5 to 9 buildings subject to the requirements of C3D4(b) having a floor area exceeding 18 000 mor having a volume exceeding 108 000 m3.

Such buildings are required to have:

  • where there is a ceiling height of 12 metres or less, either a specified automatic smoke exhaust system (see Specification 21 for details), or an automatic smoke-and-heat ventilation system (see Specification 22 for details); or
  • where there is a ceiling height of more than 12 metres, a specified automatic smoke exhaust system (see Specification 21 for details).

Roller shutters

Roller shutters and doors can be used for smoke venting purposes in accordance with the table if they are “readily openable”. A building proponent must satisfy the appropriate authority that such roller shutters and doors achieve the “readily openable” requirement.

However, if the openings are also used for egress purposes, they must also comply with the requirements of relevant provisions such as D3D24 and D3D26.

(1) A Class 9a health-care building or a Class 9c building, or a building containing a part thereof, which is not more than 25 m in effective height, must be provided throughout with—

  1. an automatic smoke detection and alarm system complying with Specification 20; and
  2. automatic shutdown of any air-handling system which does not form part of a zone pressurisation system (other than individual room units with a capacity not more than 1000 L/s, systems serving critical treatment areas and miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) on the activation of—
    1. smoke detectors installed in accordance with (a); and
    2. any other installed fire detection and alarm system including a sprinkler system complying with Specification 17; and
  3. in a building having a rise in storeys of more than 2 and not more than 25 m effective height (not being a Class 9c building)—
    1. a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1; or
    2. a sprinkler system complying with Specification 17 throughout with residential sprinkler heads in patient care areas.

(2) For the purposes of (1), ‘vertically separated fire compartments’ are fire compartments above and below each other, and not fire compartments within the same storey.

Notes

Refer to S11C2 for the provisions for smoke dampers.

In buildings less than 25 metres in effective height, the necessary levels of protection may be achieved by measures other than zone pressurisation, depending on the Class and rise in storeys of the building.

In buildings other than health-care buildings, zone pressurisation may be substituted by either stairway pressurisation, smoke detection, or sprinkler protection. The rise in storeys before which the provisions become applicable depends on the building’s classification and use.

The above measures do not apply to the residential parts of a building because of the passive protection provided to such parts. However, where one or more fire-isolated exits join residential and non-residential parts, other than open-deck carparks, the fire-isolated exits must either be pressurised, or the non-residential parts provided with smoke detection or sprinkler protection. This is necessary to compensate for the potential additional hazard associated with the particular mix of Classes.

In health-care buildings, zone pressurisation may be substituted by a sprinkler system, providing residential sprinkler heads are used in patient care areas. The quick response of residential sprinkler heads promotes life safety by limiting fire growth and smoke development. Where zone control is not adopted, the air-handling systems must generally be shut down not only to maintain the integrity of the smoke and fire compartmentation, but also to minimise the spread of smoke within the fire-affected compartment.

Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings.

A Class 7a building, including a basement, provided with a mechanical ventilation system in accordance with AS 1668.2, must comply with clause 5.5 of AS 1668.1.

A carpark ventilation system is consistent with the treatment of miscellaneous air-handling systems in AS 1668.1. Accordingly, the electric power and control cabling for a carpark ventilation system need not be fire rated.

Likewise, a concession is granted to allow fans with metal blades suitable for operating at normal temperatures to be used instead of fans required to operate at elevated temperatures as required by Clause 4.8.1 of AS 1668.1.

To make sure that the manual override provision of Clause 5.5.3 of AS 1668.1 is not subject to the control of any general installation main switches, the power supply arrangement must comply with AS 3000.

(1) A basement, other than a Class 7a basement, not counted in the rise in storeys in accordance with C2D3, must—

  1. comply with measures in accordance with this Part applicable to the building generally; and
  2. where the basement has a total floor area of more than 2000 m2, be provided with—
    1. if not more than 2 below ground storeys
      1. a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1, if the basement has more than one fire compartment; or
      2. an automatic smoke detection and alarm system complying with Specification 20; or
      3. a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; or
    2. if more than 2 below ground storeys, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

(2) For the purposes of (1), ‘vertically separated fire compartments’ are fire compartments above and below each other, and not fire compartments within the same storey.

Notes

  1. Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.
  2. Basements with more than 3 below ground storeys or containing Class 6 or 9b occupancies with a large number of occupants may require special consideration in accordance with E2D21.

The provisions for basements are more stringent due to the special problems they pose for evacuation, search and rescue, and firefighting operations. As the total floor area of the basement increases to above 2 000 m2, certain minimum measures have been stipulated. In basements with three or more below ground storeys, a sprinkler system is considered necessary.

(1) This clause applies to a Class 6 building not containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit, except for—

  1. a Class 6 sole-occupancy unit that—
    1. has a floor area of not more than 2000 m2; and
    2. is single storey with a main public entrance opening to a road or open space; and
    3. is separated from other parts of the fire compartment by construction, including openings, penetrations and junctions with other building elements, that prevents the free passage of smoke; and
  2. parts of any other classification that are smoke separated from a Class 6 part by construction complying with (a)(iii).

(2) Where the floor area of a Class 6 part of a fire compartment referred to in (1) is more than 2000 m2, the fire compartment must be provided with—

  1. an automatic smoke exhaust system complying with Specification 21; or
  2. if the building is single storey, automatic smoke-and-heat vents complying with Specification 22; or
  3. if the floor area of the fire compartment is not more than 3500 m2 and the building—
    1. is single storey, an automatic smoke detection and alarm system complying with Specification 20; or
    2. has a rise in storeys of not more than 2, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

There are specific provisions for large Class 6 buildings in E2D14 and E2D15 for the installation of either an automatic smoke exhaust system or automatic smoke-and-heat vents to control smoke during a fire. These apply to the whole fire compartment where the floor area of the Class 6 part of the fire compartment is more than 2 000 m2.

There are specific concessions that vary these requirements. These are—

  • for buildings where the floor area of the fire compartment does not exceed 3 500 m2, it is permitted to install—
  • an automatic smoke detection and alarm system in lieu of a smoke exhaust or smoke venting system if the building is single storey; or
  • a sprinkler system if the building has a rise in storeys of not more than 2.
  • for single storey shops with a floor area less than 2 000 m2 (within a larger fire compartment) which have a main entrance opening to a road or open space and are smoke separated from the fire compartment. See Example 1.
  • for another part of the building with a different classification (i.e. other than Class 6) which is smoke separated, including openings, junctions and joints of building elements, etc., from the Class 6 part. 
     

Example 1 

This example looks at a single storey shopping complex which does not contain a mall, as shown in Figure E2D14. The fire compartment has a floor area of 5 300 m2, so smoke exhaust/venting is required. The floor area of the fire compartment is more than 3 500 m2, therefore a smoke detection and alarm system or a sprinkler system cannot be used in lieu of smoke exhaust venting. However, smoke exhaust venting need not be provided in shops A and C because their individual floor areas are less than 2 000 m2, they are not interconnected to shop B, and their main entrances open to a road or open space. Smoke exhaust or smoke-and-heat venting must be provided to shop B. 

Example 1: Single storey shopping complex not containing a mall—example

Shop

Area (m2)

Entry

Smoke exhaust OR smoke-and-heat vents OR smoke detection and alarm OR sprinkler system

A

900

From open space

None required

B

2 500

From open space

Smoke exhaust or smoke- and-heat venting required as the floor area exceeds 2 000 m2

C

1 900

From open space

None required

Figure E2D14: Plan of shopping centre for Example 1

Image
Figure E2D14: Plan of shopping centre for Example 1

(1) This clause applies to a Class 6 building containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit, except for—

  1. a Class 6 sole-occupancy unit that—
    1. opens onto the enclosed common walkway or mall if the Class 6 sole-occupancy unit has a floor area of not more than 1000 m2; or
    2. does not open onto the enclosed common walkway or mall if the Class 6 sole-occupancy unit
      1. has a floor area of not more than 2000 m2; and
      2. is single storey with a main entrance opening to a road or open space; and
      3. is separated from other parts of the fire compartment by construction, including openings, penetrations and junctions with other building elements, that prevents the free passage of smoke; and
  2. parts of any other classification that are smoke separated from a Class 6 part by construction complying with (a)(ii)(C).

(2) Where the floor area of a Class 6 part of a fire compartment referred to in (1) is more than 2000 m2, the fire compartment, including the enclosed common walkway or mall, must be provided with—

  1. an automatic smoke exhaust system complying with Specification 21; or
  2. if the building is single storey, automatic smoke-and-heat vents complying with Specification 22; or
  3. if the floor area of the fire compartment is not more than 3500 m2 and the building has a rise in storeys of not more than 2, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

Notes

A fire compartment having a floor area of more than 3500 m2 in a Class 6 building requires a sprinkler system under E1D4.

The specific smoke hazard management provisions for Class 6 buildings containing shops and an enclosed common walkway or mall are similar. Where such a building has a fire compartment with a floor area of more than 2 000 m2, an automatic smoke exhaust system or an automatic smoke-and-heat vent system to control smoke during a fire is required.

However, where a single storey shop does not open onto the mall and its main public entrance opens to a road or open space, it does not need to have any smoke exhaust or smoke venting, if its floor area does not exceed 2 000 m2. This is similar to the concession for a shop in a building which does not contain a mall.

Another concession applies to shops that open onto the mall. They do not need to have any smoke exhaust or smoke venting system if their individual floor areas are less than 1 000m2.

A concession is also available for another part of the building with a different classification (i.e. other than Class 6) which is smoke separated, including openings, junctions and joints of building elements, etc., from the Class 6 part.

In a Class 6 building containing a mall, a sprinkler system can also be used in lieu of a required automatic smoke exhaust system or an automatic smoke-and-heat vent system, if the floor area of the whole fire compartment is not more than 3 500 m2.

Example 2

This example looks at a single storey shopping complex containing a mall, as shown in Figure E2D15. The fire compartment is 15 900 m2, therefore smoke exhaust/venting is required (if the floor area of the fire compartment had been less than 3 500 m2, a sprinkler system could have been used instead of a smoke exhaust/venting system). Smoke exhaust or venting is not required to shop B, which opens onto the mall, because the floor area is less than 1 000 m2. It is also not required to shop D, because the floor area is less than 2 000 m2, it does not open onto the mall, and the main entrance is to a road or open space.

Table E2D15: Single storey shopping complex containing a mall—example

Shop

Area (m2)

Entry

Smoke exhaust OR smoke- and-heat vents

A

900

From open space

None required as it is single storey, the floor area is less than 2 000 m2 and the main entrance opens to a road or open space

B

900

From mall

None required as the floor area is less than 1 000 m2

C

900

From mall and open space

None required as the floor area is less than 1 000 m2

D

1 900

From open space

None required as it is single storey, the floor area is less than 2 000 m2 and the main entrance opens to a road or open space

E

1 900

From mall

Required as the floor area is over 1 000 m2 and opens onto mall

F

1 900

From mall and open space

Required as the floor area is over 1 000 m2 and opens onto mall

G

2 500

From open space

Required as the floor area is more than 2 000 m2

H

2 500

From mall

Required as the floor area is over 1 000 m2 and opens onto mall

I

2 500

From mall and open space

Required as the floor area is over 1 000 m2 and opens onto mall

Mall

-

-

Required as the fire compartment has a floor area over 2 000 m2

Figure E2D15: Plan of shopping centre for Example 2

Image
Figure E2D15: Plan of shopping centre for Example 2
NCC Blurbs

The following provisions apply to all Class 9b assembly buildings:

  1. A building or part of a building used as an assembly building must be provided with automatic shutdown of any air-handling system (other than non-ducted individual room units with a capacity not more than 1000 L/s and miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system, on the activation of—
    1. smoke detectors installed complying with S20C6; and
    2. any other installed fire detection and alarm system, including a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
  2. A basement not counted in the rise in storeys in accordance with C2D3, less than 2000 m2 used as an assembly building or part of an assembly building containing an auditorium or other public area, must be equipped with—
    1. an automatic smoke detection system in accordance with Specification 20; or
    2. an automatic zone pressurisation system in accordance with AS 1668.1 if the basement has more than one fire compartment; or if the basement forms part of a multi fire compartmented building served by the zone pressurisation system; or
    3. a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
  3. Stages and backstages:
    1. For the purposes of this clause, where a stage is separated from the auditorium by a proscenium wall incorporating a proscenium opening, a backstage room or area that is not separated from the stage by construction having an FRL of not less than 60/60/60, is taken to form part of the stage.
    2. A building or part of a building used as an assembly building which has a stage with a floor area of more than 50 m2 and not more than 150 m2 must, over the stage, be provided with—
      1. an automatic smoke exhaust system complying with Specification 21 (including Figure S21C2); or
      2. roof mounted automatic smoke-and-heat vents complying with NSW I4D59, in a single storey building or the top storey of a multi storey building.
    3. A building or part of a building used as an assembly building which has a stage with a floor area of more than 150 m2 must, over the stage, be provided with an automatic smoke exhaust system complying with Specification 21 (including Figure S21C2).
    4. A building or part of a building used as an assembly building which has a stage equipped with means of flying scenery must, over the stage, be provided with an automatic smoke exhaust system complying with Specification 21 (including Figure S21C2).

Explanatory information

Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.

NCC Title
Class 9b – assembly buildings: all
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Class 9b – assembly buildings: all

A Class 9b assembly building which is a nightclub, discotheque or the like must be provided with—

  1. automatic shutdown of any air-handling system (other than miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system, on the activation of—
    1. smoke detectors installed complying with S20C6; and
    2. any other installed fire detection and alarm system, including a sprinkler system complying with Specification 17; and
  2. at least one of the following:
    1. An automatic smoke exhaust system complying with Specification 21.
    2. If the building is single storey, automatic smoke-and-heat vents complying with Specification 22.
    3. A sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 with quick response sprinkler heads.

E2D16 Class 9b – assembly buildings: nightclubs, discotheques and the like

Greater uniformity and consistency

Assembly buildings cover a wide range of uses with varying degrees of hazards. E2D16 to E2D20 address some of the uses to enable greater uniformity in the treatment of the buildings or parts of buildings. It provides for assembly buildings generally, except for certain low hazard occupancies which have been exempted from compliance.

Exempted assembly buildings

Certain provisions for assembly buildings do not apply to schools, apart from the automatic shutdown of air-handling systems in lecture theatres. This is because such buildings may have alarm systems with which the occupants are familiar, and the occupants are usually under a sufficient level of control to enable quick and orderly evacuation.

Concessions are granted for sporting complexes, excluding indoor stadiums with total spectator seating of more than 1000, principally because the risk levels are not high, particularly with regard to open-air complexes. Buildings used solely for religious worship are also exempt.

Assembly buildings with floor area over 2 000 m2

The provisions for smoke exhaust or smoke-and-heat vents are applicable to fire compartments having a floor area of more than 2 000 m2, except that certain concessions apply to low rise buildings.

If the floor area of the fire compartment is not more than 5 000 m2, smoke extraction need not be provided if the building has a rise in storeys of two or less, and a smoke detection and alarm system, or a sprinkler system is installed.

Nightclubs, discotheques and the like

The provisions apply to all nightclubs, discotheques and the like, regardless of the floor area, in recognition of the high hazards generated by such factors as:

  • occupant density;
  • access control;
  • indoor environment;
  • quantity and location of soft furnishings;
  • whether or not smoking is permitted; and
  • occupant behaviour.

Exhibition halls

The provisions for exhibition halls which are used for trade displays and the like are based on them having hazards similar to those for shopping centres and indoor markets.

Theatres and public halls

The provisions only apply to those theatres and public halls which are considered a high hazard occupancy due to the potential fire load associated with the stage and backstage areas and/or rigging lofts. Under Part I1, such theatres and public halls are also required to be sprinkler protected or have the stage and backstage areas separated from the audience by a proscenium wall.

The provisions for these occupancies are similar to those for assembly buildings. The provision for automatic shutdown of air-handling systems (which do not form part of a smoke management system) is applicable in all such buildings, including those serving school lecture theatres not more than 2 000 min area.

Other assembly buildings

E2D20 includes provisions for general assembly buildings not covered elsewhere. Museums and art galleries with fire compartments in excess of 2000 mare covered by these provisions.

NCC Blurbs

A building or part of a building being a night club, discotheque or the like, must be provided with—

  1. in an auditorium—
    1. an automatic smoke exhaust system complying with Specification 21; or
    2. roof mounted automatic smoke-and-heat vents complying with Specification 22, in a single storey building or the top storey of a multi storey building; or
    3. a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 with fast response sprinkler heads; and
  2. in all other areas—
    1. where a building or part of a building has a floor area not more than 2000 m2
      1. one of the smoke hazard management measures listed under (a) above; or
      2. an automatic smoke detection and alarm system complying with Specification 20; or
    2. where a building or part of a building has a floor area of more than 2000 m2, smoke hazard management measures as provided for under NSW E2D19.

Notes

  1. Paragraph (a) applies only to an auditorium designed principally to accommodate an audience to an entertainment.
  2. Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.
NCC Title
Class 9b – assembly buildings: night clubs, discotheques and the like
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Class 9b – assembly buildings: night clubs, discotheques and the like

A Class 9b assembly building which is an exhibition hall must be provided with—

  1. automatic shutdown of any air-handling system (other than miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system, on the activation of—
    1. smoke detectors installed complying with Specification 20; and
    2. any other installed fire detection and alarm system, including a sprinkler system complying with Specification 17; and
  2. where the floor area is more than 2000 m2 and not more than 3500 m2
    1. an automatic smoke exhaust system complying with Specification 21; or
    2. if the building is single storey, automatic smoke-and-heat vents complying with Specification 22; or
    3. a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; and
  3. where the floor area is more than 3500 m2, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and—
    1. an automatic smoke exhaust system complying with Specification 21; or
    2. automaticsmoke-and-heat vents complying with Specification 22, if the building is single storey.

E2D17 Class 9b – assembly buildings: exhibition halls

Greater uniformity and consistency

Assembly buildings cover a wide range of uses with varying degrees of hazards. E2D16 to E2D20 address some of the uses to enable greater uniformity in the treatment of the buildings or parts of buildings. It provides for assembly buildings generally, except for certain low hazard occupancies which have been exempted from compliance.

Exempted assembly buildings

Certain provisions for assembly buildings do not apply to schools, apart from the automatic shutdown of air-handling systems in lecture theatres. This is because such buildings may have alarm systems with which the occupants are familiar, and the occupants are usually under a sufficient level of control to enable quick and orderly evacuation.

Concessions are granted for sporting complexes, excluding indoor stadiums with total spectator seating of more than 1000, principally because the risk levels are not high, particularly with regard to open-air complexes. Buildings used solely for religious worship are also exempt.

Assembly buildings with floor area over 2 000 m2

The provisions for smoke exhaust or smoke-and-heat vents are applicable to fire compartments having a floor area of more than 2 000 m2, except that certain concessions apply to low rise buildings.

If the floor area of the fire compartment is not more than 5 000 m2, smoke extraction need not be provided if the building has a rise in storeys of two or less, and a smoke detection and alarm system, or a sprinkler system is installed.

Nightclubs, discotheques and the like

The provisions apply to all nightclubs, discotheques and the like, regardless of the floor area, in recognition of the high hazards generated by such factors as:

  • occupant density;
  • access control;
  • indoor environment;
  • quantity and location of soft furnishings;
  • whether or not smoking is permitted; and
  • occupant behaviour.

Exhibition halls

The provisions for exhibition halls which are used for trade displays and the like are based on them having hazards similar to those for shopping centres and indoor markets.

Theatres and public halls

The provisions only apply to those theatres and public halls which are considered a high hazard occupancy due to the potential fire load associated with the stage and backstage areas and/or rigging lofts. Under Part I1, such theatres and public halls are also required to be sprinkler protected or have the stage and backstage areas separated from the audience by a proscenium wall.

The provisions for these occupancies are similar to those for assembly buildings. The provision for automatic shutdown of air-handling systems (which do not form part of a smoke management system) is applicable in all such buildings, including those serving school lecture theatres not more than 2 000 min area.

Other assembly buildings

E2D20 includes provisions for general assembly buildings not covered elsewhere. Museums and art galleries with fire compartments in excess of 2000 mare covered by these provisions.

NCC Blurbs

A building or part of a building used as an exhibition hall, museum, art gallery or the like, must be provided with—

  1. where the floor area is more than 2000 m2 and not more than 3500 m2
    1. an automatic smoke exhaust system complying with Specification 21; or
    2. roof mounted automatic smoke-and-heat vents complying with Specification 22 in a single storey building or the top storey of a multi storey building; or
    3. a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; and
  2. where the floor area is more than 3500 m2, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and—
    1. an automatic smoke exhaust system complying with Specification 21; or
    2. roof mounted automatic smoke-and-heat vents complying with Specification 22 , in a single storey building or the top storey of a multi storey building.

Notes

Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.

NCC Title
Class 9b – assembly buildings: exhibition halls, museums and art galleries
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Class 9b – assembly buildings: exhibition halls, museums and art galleries

(1) This clause applies to a Class 9b assembly building where the building or part of the building is used as a theatre or public hall which—

  1. is a school assembly, church or community hall, and has a stage and any backstage area with a total floor area of more than 300 m2; or
  2. is not a school assembly, church or community hall, and has a stage and any backstage area with a total floor area of more than 200 m2; or
  3. has a stage with an associated rigging loft.

(2) A building or part of a building referred to in (1) must be provided with—

  1. an automatic smoke exhaust system complying with Specification 21; or
  2. if the building is single storey, automatic smoke-and-heat vents complying with Specification 22.

E2D18 Class 9b – assembly buildings: theatres and public halls

Greater uniformity and consistency

Assembly buildings cover a wide range of uses with varying degrees of hazards. E2D16 to E2D20 address some of the uses to enable greater uniformity in the treatment of the buildings or parts of buildings. It provides for assembly buildings generally, except for certain low hazard occupancies which have been exempted from compliance.

Exempted assembly buildings

Certain provisions for assembly buildings do not apply to schools, apart from the automatic shutdown of air-handling systems in lecture theatres. This is because such buildings may have alarm systems with which the occupants are familiar, and the occupants are usually under a sufficient level of control to enable quick and orderly evacuation.

Concessions are granted for sporting complexes, excluding indoor stadiums with total spectator seating of more than 1000, principally because the risk levels are not high, particularly with regard to open-air complexes. Buildings used solely for religious worship are also exempt.

Assembly buildings with floor area over 2 000 m2

The provisions for smoke exhaust or smoke-and-heat vents are applicable to fire compartments having a floor area of more than 2 000 m2, except that certain concessions apply to low rise buildings.

If the floor area of the fire compartment is not more than 5 000 m2, smoke extraction need not be provided if the building has a rise in storeys of two or less, and a smoke detection and alarm system, or a sprinkler system is installed.

Nightclubs, discotheques and the like

The provisions apply to all nightclubs, discotheques and the like, regardless of the floor area, in recognition of the high hazards generated by such factors as:

  • occupant density;
  • access control;
  • indoor environment;
  • quantity and location of soft furnishings;
  • whether or not smoking is permitted; and
  • occupant behaviour.

Exhibition halls

The provisions for exhibition halls which are used for trade displays and the like are based on them having hazards similar to those for shopping centres and indoor markets.

Theatres and public halls

The provisions only apply to those theatres and public halls which are considered a high hazard occupancy due to the potential fire load associated with the stage and backstage areas and/or rigging lofts. Under Part I1, such theatres and public halls are also required to be sprinkler protected or have the stage and backstage areas separated from the audience by a proscenium wall.

The provisions for these occupancies are similar to those for assembly buildings. The provision for automatic shutdown of air-handling systems (which do not form part of a smoke management system) is applicable in all such buildings, including those serving school lecture theatres not more than 2 000 min area.

Other assembly buildings

E2D20 includes provisions for general assembly buildings not covered elsewhere. Museums and art galleries with fire compartments in excess of 2000 mare covered by these provisions.

NCC Blurbs

(1) Unless otherwise described in (2), in a building or part of a building used as an assembly building (not being a night club, discotheque or the like; or an exhibition hall, museum or art gallery) where the floor area of a fire compartment is more than 2000 m2, the fire compartment must be provided with—

  1. an automatic smoke exhaust system complying with Specification 21; or
  2. roof mounted automatic smoke-and-heat vents complying with Specification 22, in a single storey building or the top storey of a multi storey building; or
  3. if the floor area of the fire compartment is not more than 5000 m2 and the building has a rise in storeys of not more than 2—
    1. an automatic smoke detection and alarm system complying with Specification 20; or
    2. a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

(2) The following buildings are exempt from the provisions of (1):

  1. Sporting complexes, (including sports halls, gymnasiums, swimming pools, ice and roller rinks, and the like) other than indoor sports stadiums with total spectator seating for more than 1000 persons.
  2. Churches and other places used solely for religious worship.
  3. School classrooms.

(3) A building containing a Class 9b early childhood centre must be provided with an automatic smoke detection and alarm system complying with Specification 20 throughout the whole building, including any part of another Class.

Notes

Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.

NCC Title
Class 9b – assembly buildings: other assembly buildings (not listed in NSW E2D16 to E2D18)
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Class 9b – assembly buildings: other assembly buildings (not listed in NSW E2D16 to E2D18)

(1) This clause applies to a Class 9b assembly building where the building or part of the building is used as a theatre or public hall not listed in E2D18 and includes lecture theatres and cinema/auditorium complexes.

(2) A building or part of a building referred to in (1)—

  1. must be provided with automatic shutdown of any air-handling system (other than miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system, on the activation of—
    1. smoke detectors installed complying with Specification 20; and
    2. any other installed fire detection and alarm system, including a sprinkler system complying with Specification 17; and
  2. other than in the case of a school lecture theatre, where the floor area of the fire compartment is more than 2000 m2
    1. an automatic smoke exhaust system complying with Specification 21; or
    2. if the building is single storey, automatic smoke-and-heat vents complying with Specification 22; or
    3. if the floor area of the fire compartment is not more than 5000 m2 and the building has a rise in storeys of not more than 2—
      1. an automatic smoke detection and alarm system complying with Specification 20; or
      2. a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

E2D19 Class 9b – assembly buildings: theatres and public halls (not listed in E2D18) including lecture theatres and cinema/auditorium complexes

Greater uniformity and consistency

Assembly buildings cover a wide range of uses with varying degrees of hazards. E2D16 to E2D20 address some of the uses to enable greater uniformity in the treatment of the buildings or parts of buildings. It provides for assembly buildings generally, except for certain low hazard occupancies which have been exempted from compliance.

Exempted assembly buildings

Certain provisions for assembly buildings do not apply to schools, apart from the automatic shutdown of air-handling systems in lecture theatres. This is because such buildings may have alarm systems with which the occupants are familiar, and the occupants are usually under a sufficient level of control to enable quick and orderly evacuation.

Concessions are granted for sporting complexes, excluding indoor stadiums with total spectator seating of more than 1000, principally because the risk levels are not high, particularly with regard to open-air complexes. Buildings used solely for religious worship are also exempt.

Assembly buildings with floor area over 2 000 m2

The provisions for smoke exhaust or smoke-and-heat vents are applicable to fire compartments having a floor area of more than 2 000 m2, except that certain concessions apply to low rise buildings.

If the floor area of the fire compartment is not more than 5 000 m2, smoke extraction need not be provided if the building has a rise in storeys of two or less, and a smoke detection and alarm system, or a sprinkler system is installed.

Nightclubs, discotheques and the like

The provisions apply to all nightclubs, discotheques and the like, regardless of the floor area, in recognition of the high hazards generated by such factors as:

  • occupant density;
  • access control;
  • indoor environment;
  • quantity and location of soft furnishings;
  • whether or not smoking is permitted; and
  • occupant behaviour.

Exhibition halls

The provisions for exhibition halls which are used for trade displays and the like are based on them having hazards similar to those for shopping centres and indoor markets.

Theatres and public halls

The provisions only apply to those theatres and public halls which are considered a high hazard occupancy due to the potential fire load associated with the stage and backstage areas and/or rigging lofts. Under Part I1, such theatres and public halls are also required to be sprinkler protected or have the stage and backstage areas separated from the audience by a proscenium wall.

The provisions for these occupancies are similar to those for assembly buildings. The provision for automatic shutdown of air-handling systems (which do not form part of a smoke management system) is applicable in all such buildings, including those serving school lecture theatres not more than 2 000 min area.

Other assembly buildings

E2D20 includes provisions for general assembly buildings not covered elsewhere. Museums and art galleries with fire compartments in excess of 2000 mare covered by these provisions.

NCC Title
Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)
NCC State
NSW
NCC Variation Type
Deletion
NCC SPTC Current
Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)
NCC Notice
E2D20 does not apply in NSW. This clause is deleted from the BCA in NSW, as requirements for Class 9b – Assembly buildings in NSW are covered under NSW E2D16 to NSW E2D19.

(1) The requirements of (2)—

  1. apply to a Class 9b assembly building where the building or part of the building is used for a purpose other than—
    1. as described in E2D16 to E2D19; or
    2. a school; and
  2. do not apply to—
    1. sporting complexes (including sports halls, gymnasiums, swimming pools, ice and roller rinks, and the like) other than an indoor sports stadium with total spectator seating for more than 1000; or
    2. churches and other places used solely for religious worship.

(2) Each fire compartment, other than one in a building referred to in (1)(b), having a floor area of more than 2000 m2 must be provided with—

  1. an automatic smoke exhaust system complying with Specification 21; or
  2. if the building is single storey, automatic smoke-and-heat vents complying with Specification 22; or
  3. if the floor area of the fire compartment is not more than 5000 m2 and the building has a rise in storeys of not more than 2—
    1. an automatic smoke detection and alarm system complying with Specification 20; or
    2. a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

(3) A building containing a Class 9b early childhood centre must be provided with an automatic smoke detection and alarm system complying with Specification 20 throughout the whole building, including any part of another class.

E2D20 Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)

Greater uniformity and consistency

Assembly buildings cover a wide range of uses with varying degrees of hazards. E2D16 to E2D20 address some of the uses to enable greater uniformity in the treatment of the buildings or parts of buildings. It provides for assembly buildings generally, except for certain low hazard occupancies which have been exempted from compliance.

Exempted assembly buildings

Certain provisions for assembly buildings do not apply to schools, apart from the automatic shutdown of air-handling systems in lecture theatres. This is because such buildings may have alarm systems with which the occupants are familiar, and the occupants are usually under a sufficient level of control to enable quick and orderly evacuation.

Concessions are granted for sporting complexes, excluding indoor stadiums with total spectator seating of more than 1000, principally because the risk levels are not high, particularly with regard to open-air complexes. Buildings used solely for religious worship are also exempt.

Assembly buildings with floor area over 2 000 m2

The provisions for smoke exhaust or smoke-and-heat vents are applicable to fire compartments having a floor area of more than 2 000 m2, except that certain concessions apply to low rise buildings.

If the floor area of the fire compartment is not more than 5 000 m2, smoke extraction need not be provided if the building has a rise in storeys of two or less, and a smoke detection and alarm system, or a sprinkler system is installed.

Nightclubs, discotheques and the like

The provisions apply to all nightclubs, discotheques and the like, regardless of the floor area, in recognition of the high hazards generated by such factors as:

  • occupant density;
  • access control;
  • indoor environment;
  • quantity and location of soft furnishings;
  • whether or not smoking is permitted; and
  • occupant behaviour.

Exhibition halls

The provisions for exhibition halls which are used for trade displays and the like are based on them having hazards similar to those for shopping centres and indoor markets.

Theatres and public halls

The provisions only apply to those theatres and public halls which are considered a high hazard occupancy due to the potential fire load associated with the stage and backstage areas and/or rigging lofts. Under Part I1, such theatres and public halls are also required to be sprinkler protected or have the stage and backstage areas separated from the audience by a proscenium wall.

The provisions for these occupancies are similar to those for assembly buildings. The provision for automatic shutdown of air-handling systems (which do not form part of a smoke management system) is applicable in all such buildings, including those serving school lecture theatres not more than 2 000 min area.

Other assembly buildings

E2D20 includes provisions for general assembly buildings not covered elsewhere. Museums and art galleries with fire compartments in excess of 2000 mare covered by these provisions.

Additional smoke hazard management measures may be necessary due to the—

  1. special characteristics of the building; or
  2. special function or use of the building; or
  3. special type or quantity of materials stored, displayed or used in a building; or
  4. special mix of classifications within a building or fire compartment,

which are not addressed in E2D4 to E2D20.

To state that some special hazards may require additional smoke hazard management measures.

E2D21 states that certain factors may need additional smoke hazard management measures.

E2D21 reinforces the need for careful consideration and sound professional judgement in the application of the smoke hazard management provisions of the BCA.

Examples

E2D21 may be applicable in situations where:

  • Occupants are held under detention in a correctional or health-care facility. The BCA does not specifically address the special circumstances surrounding these facilities. To ensure an acceptable level of safety is provided to occupants, special provisions may need to be provided.
  • A high hazard process is carried out in an industrial building. Due to the variance in such processes, it would be difficult to develop specific generic provisions. Such processes may also be subject to other legislation. Hence each process should be considered on its merits and additional safeguards provided as necessary.
NCC Blurbs

In bulk grain storage facility

  1. suitable natural smoke venting by fixed vents must be provided at the top of elevator towers and overhead galleries in a cell type silo; and
  2. smoke venting is not required in a storage shed.
NCC Title
Smoke venting in bulk grain storage facilities
NCC State
SA
NCC Variation Type
Insertion
NCC SPTC Current
Smoke venting in bulk grain storage facilities