NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
E2
Part E2 Smoke hazard managementThis Part is intended to reduce the risk of injury or loss of life for occupants due to the effects of smoke, including inhalation, if a fire occurs in a building. It provides for automatic warning of the presence of smoke or fire, and measures to ensure conditions within evacuation routes remain tenable long enough for occupants evacuate safely and to facilitate fire brigade intervention.
The Objective of this Part is to—
Safeguard occupants from illness and injury
Part E2 aims to safeguard building occupants from illness or injury from the products of combustion (including smoke and toxic gases). E2O1(a) deals with warning of a fire and E2O1(b) deals with requirements for evacuating.
Smoke and toxic gases kill
Smoke and toxic gases are the main causes of death in building fires. Such deaths have occurred in locations remote from the fire to where smoke and gases have spread. Smoke and toxic gases cause disorientation, incapacitation and ultimately death, depending on the concentration and length of exposure.
Management of the smoke and toxic gas hazard is crucial for occupant safety. This is best achieved through a combination of active and passive measures, such as:
Part E2 addresses some of the active measures which, together with the relevant provisions in other Parts of the BCA, provide appropriate strategies for the protection of occupants.
A building is to be provided with safeguards so that—
E2F1 requires that a building have safeguards to warn occupants of a fire so they may safely evacuate before the conditions in any evacuation route become untenable, due to the effects of fire.
In a building providing sleeping accommodation, occupants must be provided with automatic warning on the detection of smoke so they may evacuate in the event of a fire to a safe place.
E2P1 only applies to a Class 2, 3, 9a or 9c building or Class 4 part of a building.
Sleeping accommodation—smoke alarms
A Class 2, 3, 9a and 9c building and a Class 4 part must contain automatic warning on the detection of smoke for occupants in sleeping areas, so they may be alerted to a fire.
E2P2 does not apply to an open-deck carpark or open spectator stand.
Evacuation routes must remain tenable
Occupants must be given time to evacuate before the onset of untenable conditions. E2P2(1) specifies these conditions as dangerous temperatures, low visibility and dangerous levels of toxicity.
Hence, evacuation time must take account of a range of factors including the following:
Under its Limitation provision, E2P2 does not apply to open-deck carparks or open spectator stands where the smoke and hot gases can vent naturally, thereby allowing occupants to safely evacuate.
To clarify that the requirements of E2P1 and E2P2 will be satisfied if compliance is achieved with E2D2 to E2D21 in the case of all buildings, Part G3 in the case of buildings with an atrium, Part G4 in the case of buildings in alpine areas, Part I1 in the case of theatres, stages and public halls.
E2D2 to E2D21 and E2P1 and E2P2
Where a solution is proposed to comply with the Deemed-to-Satisfy Provisions, except in buildings containing atriums, compliance with E2D2 to E2D21 achieves compliance with E2P1 and E2P2.
Buildings with atriums
In addition to achieving compliance with E2D2 to E2D21, to achieve compliance with E2P1 and E2P2 buildings with atriums must also comply with Part G3.
Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2G2(3) and A2G4(3) as applicable. (See commentary on Part A2).
To specify when E2D3 to E2D21 do not apply.
Open-deck carparks, open spectator stands and Class 8 electricity network substations—E2D2(2)
E2D2(2) and E2D3 to E2D21 do not apply to open-deck carparks or open spectator stands. E2P2 does not apply to such buildings because the smoke and hot gases can vent naturally.
The Deemed-to-Satisfy Provisions of Part E2 do not apply to small Class 8 electricity network substations, located in a multi-classified building. These smaller substations are usually located within a “host” building and the associated electrical equipment has its own sensitive dedicated systems that provide a rapid response signal to a central control room that is constantly staffed.
Smoke exhaust systems and smoke-and-heat vents—E2D2(3)
Under E2D2(3), the E2D3 to E2D21 provisions regarding smoke exhaust systems and smoke-and-heat vents do not apply to small areas used for short periods.
A small area will be easily evacuated before smoke build-up and if the area is only used for short periods, the risk of occupants being trapped in it during a fire is low.
Application of E2D4 to E2D13—General provisions—whole building strategies
E2D4 to E2D13 provide smoke hazard management strategies structured to help application to buildings of mixed classification. In the case of a multi-classified building, each classifiable part must comply with the relevant provisions for its classification. Certain Class 6 and Class 9b parts of buildings must also comply with the specific provisions in E2D14 to E2D20.
Application of E2D4 to E2D13—General provisions—zone pressurisation systems
Where zone pressurisation systems are specified in various locations in E2D4 to E2D13 to be in accordance with AS 1668.1, the provision states that zone pressurisation systems only apply between vertically separated fire compartments and not horizontal fire compartments.
Application of E2D14 to E2D20—Specific provisions—Class 6 and 9b buildings
The provisions of E2D14 to E2D20 are additional strategies which only apply to certain Class 6 and Class 9b buildings where there is a high risk that occupants may not be able to safely evacuate the fire-affected compartment. This risk may be due to factors such as:
Occupants of such buildings are also not necessarily familiar with the building or the procedures for evacuation.
Application of E2D14 to E2D20—Specific provisions—Maintenance of safe conditions in evacuation routes
E2D14 to E2D20 address requirements under E2P2 in terms of maintaining safe conditions in any evacuation route within the fire-affected compartment of Class 6 and Class 9b buildings, for the period of time it would take occupants to evacuate that part of the building.
To specify the requirements for minimising the smoke risks.
Air-handling system which is not part of a smoke hazard management system—E2D3(1)
E2D3(1) requires that an air-handling system that is not part of a smoke hazard management system be designed and installed with suitable strategies to ensure that, during a fire, it does not:
Comply with AS 1668.1 —E2D3(1)(a)
The effect of E2D3(1)(a) is that in a fire, an air-handling system must either operate as a smoke control system in accordance with AS 1668.1 (as specified in E2D3(1)(a)) or shut down (as specified in E2D3(1)(b)).
A smoke purging system, in accordance with AS 1668.1, is allowable in buildings not covered by the general provisions in E2D4 to E2D13, and, in some instances, in conjunction with other measures in accordance with E2D4 to E2D13.
Non-smoke control system—E2D3(1)
An air-handling system not designed as a smoke control system must comply with the requirements set out in E2D3(1) as follows:
Sections 5 and 6 of AS 1668.1—E2D3(3)
Air-handling systems, other than one in a carpark, serving more than one fire compartment covered by Sections 5 and 6 of AS 1668.1 must be designed and installed in compliance with those sections of the Australian Standard. This will restrict the spread of smoke between fire compartments.
Provisions on the operation of carpark ventilation systems during a fire in the carpark are included under the general provisions in E2D4 to E2D13.
Smoke detection systems to operate AS 1668.1 smoke control systems—E2D3(4)
An AS 1668.1 system for zone pressurisation and automatic air pressurisation for fire-isolated exits must be controlled by a smoke detection and alarm system installed in compliance with Specification 20. Activation of these systems also requires the activation of a building occupant warning system.
Fire-isolated exits enable the safe evacuation of occupants, and also aid fire brigade access. Smoke must not unduly affect the conditions in such exits during an evacuation.
To minimise smoke intrusion, the exits may need to be pressurised with outside air for the entire exit route. See the following examples. Alternatively, the exits may be provided with open access ramps or balconies from which smoke can vent naturally.
Examples
Pressurised fire-isolated exits are required where:
An automatic smoke detection and alarm system complying with Specification 20 must be provided to the following:
Refer to C3D15 for division of public corridors greater than 40 m in length.
In buildings more than 25 metres in effective height, tenable conditions need to be maintained in the fire-isolated exits and, where practicable, in other parts of the building to enable the staged evacuation of occupants.
Occupants of such buildings may continue to occupy compartments remote from the fire for an extended time before evacuation. Accordingly, suitable measures must be adopted to minimise the spread of smoke from the fire-affected compartment to non-affected compartments by way of a number of potential leakage paths.
These paths include lift shafts, air-handling ducts, services risers, building penetrations, spandrels, and the like, through which smoke can be driven by buoyancy, expansion, stack and wind effects, and air-handling systems.
In order to minimise the spread of smoke, a zone pressurisation system is considered necessary in buildings more than 25 metres in effective height. This does not apply to the residential parts of a building in view of:
Additionally, this requirement does not apply to a building that contains only one single fire compartment containing a Class 5, 6, 7b, 8 or 9b part (or a combination of these classes in the same fire compartment) in an otherwise Class 2, 3, 9a or 9c building. Reference to a Class 2, 3, 9a or 9c building does not include a building that also contains a Class 7a carpark (see Figure E2D5). The reasons for this exemption are:
Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings to provide early warning to occupants who may be asleep, confused, or non-ambulatory and dependent on assistance.
E2D4 to E2D13 provisions are additional to other safety provisions for buildings with an effective height of more than 25 metres.
Figure E2D5: Zone pressurisation concession
Figure Notes
Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.
In buildings more than 25 metres in effective height, tenable conditions need to be maintained in the fire-isolated exits and, where practicable, in other parts of the building to enable the staged evacuation of occupants.
Occupants of such buildings may continue to occupy compartments remote from the fire for an extended time before evacuation. Accordingly, suitable measures must be adopted to minimise the spread of smoke from the fire-affected compartment to non-affected compartments by way of a number of potential leakage paths.
These paths include lift shafts, air-handling ducts, services risers, building penetrations, spandrels, and the like, through which smoke can be driven by buoyancy, expansion, stack and wind effects, and air-handling systems.
In order to minimise the spread of smoke, a zone pressurisation system is considered necessary in buildings more than 25 metres in effective height. This does not apply to the residential parts of a building in view of:
Additionally, this requirement does not apply to a building that contains only one single fire compartment containing a Class 5, 6, 7b, 8 or 9b part (or a combination of these classes in the same fire compartment) in an otherwise Class 2, 3, 9a or 9c building. Reference to a Class 2, 3, 9a or 9c building does not include a building that also contains a Class 7a carpark (see Figure E2D6). The reasons for this exemption are:
Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings to provide early warning to occupants who may be asleep, confused, or non-ambulatory and dependent on assistance.
E2D4 to E2D13 provisions are additional to other safety provisions for buildings with an effective height of more than 25 metres.
Figure E2D6: Zone pressurisation concession
Figure Notes
if the building is more than 25 m in effective height.
A building more than 25 m in effective height requires a sprinkler system under E1D4.
In buildings more than 25 metres in effective height, tenable conditions need to be maintained in the fire-isolated exits and, where practicable, in other parts of the building to enable the staged evacuation of occupants.
Occupants of such buildings may continue to occupy compartments remote from the fire for an extended time before evacuation. Accordingly, suitable measures must be adopted to minimise the spread of smoke from the fire-affected compartment to non-affected compartments by way of a number of potential leakage paths.
These paths include lift shafts, air-handling ducts, services risers, building penetrations, spandrels, and the like, through which smoke can be driven by buoyancy, expansion, stack and wind effects, and air-handling systems.
In order to minimise the spread of smoke, a zone pressurisation system is considered necessary in buildings more than 25 metres in effective height. This does not apply to the residential parts of a building in view of:
Additionally, this requirement does not apply to a building that contains only one single fire compartment containing a Class 5, 6, 7b, 8 or 9b part (or a combination of these classes in the same fire compartment) in an otherwise Class 2, 3, 9a or 9c building. Reference to a Class 2, 3, 9a or 9c building does not include a building that also contains a Class 7a carpark (see Figure E2D7). The reasons for this exemption are:
Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings to provide early warning to occupants who may be asleep, confused, or non-ambulatory and dependent on assistance.
E2D4 to E2D13 provisions are additional to other safety provisions for buildings with an effective height of more than 25 metres.
Figure E2D7: Zone pressurisation concession
Figure Notes
In a Class 2 and 3 building or part of a building, or Class 4 part of a building, if the building is not more than 25 m in effective height—
In buildings less than 25 metres in effective height, the necessary levels of protection may be achieved by measures other than zone pressurisation, depending on the Class and rise in storeys of the building.
In buildings other than health-care buildings, zone pressurisation may be substituted by either stairway pressurisation, smoke detection, or sprinkler protection. The rise in storeys before which the provisions become applicable depends on the building’s classification and use.
The above measures do not apply to the residential parts of a building because of the passive protection provided to such parts. However, where one or more fire-isolated exits join residential and non-residential parts, other than open-deck carparks, the fire-isolated exits must either be pressurised, or the non-residential parts provided with smoke detection or sprinkler protection. This is necessary to compensate for the potential additional hazard associated with the particular mix of Classes.
In health-care buildings, zone pressurisation may be substituted by a sprinkler system, providing residential sprinkler heads are used in patient care areas. The quick response of residential sprinkler heads promotes life safety by limiting fire growth and smoke development. Where zone control is not adopted, the air-handling systems must generally be shut down not only to maintain the integrity of the smoke and fire compartmentation, but also to minimise the spread of smoke within the fire-affected compartment.
Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings.
must meet the requirements of (2).
In buildings less than 25 metres in effective height, the necessary levels of protection may be achieved by measures other than zone pressurisation, depending on the Class and rise in storeys of the building.
In buildings other than health-care buildings, zone pressurisation may be substituted by either stairway pressurisation, smoke detection, or sprinkler protection. The rise in storeys before which the provisions become applicable depends on the building’s classification and use.
The above measures do not apply to the residential parts of a building because of the passive protection provided to such parts. However, where one or more fire-isolated exits join residential and non-residential parts, other than open-deck carparks, the fire-isolated exits must either be pressurised, or the non-residential parts provided with smoke detection or sprinkler protection. This is necessary to compensate for the potential additional hazard associated with the particular mix of Classes.
In health-care buildings, zone pressurisation may be substituted by a sprinkler system, providing residential sprinkler heads are used in patient care areas. The quick response of residential sprinkler heads promotes life safety by limiting fire growth and smoke development. Where zone control is not adopted, the air-handling systems must generally be shut down not only to maintain the integrity of the smoke and fire compartmentation, but also to minimise the spread of smoke within the fire-affected compartment.
Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings.
Large Class 7 or 8 buildings subject to C3D4
These provisions set out the smoke hazard management measures for large isolated Class 7 or 8 buildings subject to the requirements of C3D4(a) with a floor area of 18 000 m2 or less and a volume of 108 000 m3 or less. Such buildings are required to have:
Large Class 5 to 9 buildings subject to C3D4
These provisions set out the smoke hazard management measures for large isolated Class 5 to 9 buildings subject to the requirements of C3D4(b) having a floor area exceeding 18 000 m2 or having a volume exceeding 108 000 m3.
Such buildings are required to have:
Roller shutters
Roller shutters and doors can be used for smoke venting purposes in accordance with the table if they are “readily openable”. A building proponent must satisfy the appropriate authority that such roller shutters and doors achieve the “readily openable” requirement.
However, if the openings are also used for egress purposes, they must also comply with the requirements of relevant provisions such as D3D24 and D3D26.
Refer to S11C2 for the provisions for smoke dampers.
In buildings less than 25 metres in effective height, the necessary levels of protection may be achieved by measures other than zone pressurisation, depending on the Class and rise in storeys of the building.
In buildings other than health-care buildings, zone pressurisation may be substituted by either stairway pressurisation, smoke detection, or sprinkler protection. The rise in storeys before which the provisions become applicable depends on the building’s classification and use.
The above measures do not apply to the residential parts of a building because of the passive protection provided to such parts. However, where one or more fire-isolated exits join residential and non-residential parts, other than open-deck carparks, the fire-isolated exits must either be pressurised, or the non-residential parts provided with smoke detection or sprinkler protection. This is necessary to compensate for the potential additional hazard associated with the particular mix of Classes.
In health-care buildings, zone pressurisation may be substituted by a sprinkler system, providing residential sprinkler heads are used in patient care areas. The quick response of residential sprinkler heads promotes life safety by limiting fire growth and smoke development. Where zone control is not adopted, the air-handling systems must generally be shut down not only to maintain the integrity of the smoke and fire compartmentation, but also to minimise the spread of smoke within the fire-affected compartment.
Notwithstanding the above, a smoke detection and alarm system must be provided in residential and health-care buildings.
A Class 7a building, including a basement, provided with a mechanical ventilation system in accordance with AS 1668.2, must comply with clause 5.5 of AS 1668.1.
A carpark ventilation system is consistent with the treatment of miscellaneous air-handling systems in AS 1668.1. Accordingly, the electric power and control cabling for a carpark ventilation system need not be fire rated.
Likewise, a concession is granted to allow fans with metal blades suitable for operating at normal temperatures to be used instead of fans required to operate at elevated temperatures as required by Clause 4.8.1 of AS 1668.1.
To make sure that the manual override provision of Clause 5.5.3 of AS 1668.1 is not subject to the control of any general installation main switches, the power supply arrangement must comply with AS 3000.
The provisions for basements are more stringent due to the special problems they pose for evacuation, search and rescue, and firefighting operations. As the total floor area of the basement increases to above 2 000 m2, certain minimum measures have been stipulated. In basements with three or more below ground storeys, a sprinkler system is considered necessary.
There are specific provisions for large Class 6 buildings in E2D14 and E2D15 for the installation of either an automatic smoke exhaust system or automatic smoke-and-heat vents to control smoke during a fire. These apply to the whole fire compartment where the floor area of the Class 6 part of the fire compartment is more than 2 000 m2.
There are specific concessions that vary these requirements. These are—
Example 1
This example looks at a single storey shopping complex which does not contain a mall, as shown in Figure E2D14. The fire compartment has a floor area of 5 300 m2, so smoke exhaust/venting is required. The floor area of the fire compartment is more than 3 500 m2, therefore a smoke detection and alarm system or a sprinkler system cannot be used in lieu of smoke exhaust venting. However, smoke exhaust venting need not be provided in shops A and C because their individual floor areas are less than 2 000 m2, they are not interconnected to shop B, and their main entrances open to a road or open space. Smoke exhaust or smoke-and-heat venting must be provided to shop B.
Shop | Area (m2) | Entry | Smoke exhaust OR smoke-and-heat vents OR smoke detection and alarm OR sprinkler system |
A | 900 | From open space | None required |
B | 2 500 | From open space | Smoke exhaust or smoke- and-heat venting required as the floor area exceeds 2 000 m2 |
C | 1 900 | From open space | None required |
Figure E2D14: Plan of shopping centre for Example 1
A fire compartment having a floor area of more than 3500 m2 in a Class 6 building requires a sprinkler system under E1D4.
The specific smoke hazard management provisions for Class 6 buildings containing shops and an enclosed common walkway or mall are similar. Where such a building has a fire compartment with a floor area of more than 2 000 m2, an automatic smoke exhaust system or an automatic smoke-and-heat vent system to control smoke during a fire is required.
However, where a single storey shop does not open onto the mall and its main public entrance opens to a road or open space, it does not need to have any smoke exhaust or smoke venting, if its floor area does not exceed 2 000 m2. This is similar to the concession for a shop in a building which does not contain a mall.
Another concession applies to shops that open onto the mall. They do not need to have any smoke exhaust or smoke venting system if their individual floor areas are less than 1 000m2.
A concession is also available for another part of the building with a different classification (i.e. other than Class 6) which is smoke separated, including openings, junctions and joints of building elements, etc., from the Class 6 part.
In a Class 6 building containing a mall, a sprinkler system can also be used in lieu of a required automatic smoke exhaust system or an automatic smoke-and-heat vent system, if the floor area of the whole fire compartment is not more than 3 500 m2.
Example 2
This example looks at a single storey shopping complex containing a mall, as shown in Figure E2D15. The fire compartment is 15 900 m2, therefore smoke exhaust/venting is required (if the floor area of the fire compartment had been less than 3 500 m2, a sprinkler system could have been used instead of a smoke exhaust/venting system). Smoke exhaust or venting is not required to shop B, which opens onto the mall, because the floor area is less than 1 000 m2. It is also not required to shop D, because the floor area is less than 2 000 m2, it does not open onto the mall, and the main entrance is to a road or open space.
Shop | Area (m2) | Entry | Smoke exhaust OR smoke- and-heat vents |
A | 900 | From open space | None required as it is single storey, the floor area is less than 2 000 m2 and the main entrance opens to a road or open space |
B | 900 | From mall | None required as the floor area is less than 1 000 m2 |
C | 900 | From mall and open space | None required as the floor area is less than 1 000 m2 |
D | 1 900 | From open space | None required as it is single storey, the floor area is less than 2 000 m2 and the main entrance opens to a road or open space |
E | 1 900 | From mall | Required as the floor area is over 1 000 m2 and opens onto mall |
F | 1 900 | From mall and open space | Required as the floor area is over 1 000 m2 and opens onto mall |
G | 2 500 | From open space | Required as the floor area is more than 2 000 m2 |
H | 2 500 | From mall | Required as the floor area is over 1 000 m2 and opens onto mall |
I | 2 500 | From mall and open space | Required as the floor area is over 1 000 m2 and opens onto mall |
Mall | - | - | Required as the fire compartment has a floor area over 2 000 m2 |
Figure E2D15: Plan of shopping centre for Example 2
The following provisions apply to all Class 9b assembly buildings:
Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.
A Class 9b assembly building which is a nightclub, discotheque or the like must be provided with—
Greater uniformity and consistency
Assembly buildings cover a wide range of uses with varying degrees of hazards. E2D16 to E2D20 address some of the uses to enable greater uniformity in the treatment of the buildings or parts of buildings. It provides for assembly buildings generally, except for certain low hazard occupancies which have been exempted from compliance.
Exempted assembly buildings
Certain provisions for assembly buildings do not apply to schools, apart from the automatic shutdown of air-handling systems in lecture theatres. This is because such buildings may have alarm systems with which the occupants are familiar, and the occupants are usually under a sufficient level of control to enable quick and orderly evacuation.
Concessions are granted for sporting complexes, excluding indoor stadiums with total spectator seating of more than 1000, principally because the risk levels are not high, particularly with regard to open-air complexes. Buildings used solely for religious worship are also exempt.
Assembly buildings with floor area over 2 000 m2
The provisions for smoke exhaust or smoke-and-heat vents are applicable to fire compartments having a floor area of more than 2 000 m2, except that certain concessions apply to low rise buildings.
If the floor area of the fire compartment is not more than 5 000 m2, smoke extraction need not be provided if the building has a rise in storeys of two or less, and a smoke detection and alarm system, or a sprinkler system is installed.
Nightclubs, discotheques and the like
The provisions apply to all nightclubs, discotheques and the like, regardless of the floor area, in recognition of the high hazards generated by such factors as:
Exhibition halls
The provisions for exhibition halls which are used for trade displays and the like are based on them having hazards similar to those for shopping centres and indoor markets.
Theatres and public halls
The provisions only apply to those theatres and public halls which are considered a high hazard occupancy due to the potential fire load associated with the stage and backstage areas and/or rigging lofts. Under Part I1, such theatres and public halls are also required to be sprinkler protected or have the stage and backstage areas separated from the audience by a proscenium wall.
The provisions for these occupancies are similar to those for assembly buildings. The provision for automatic shutdown of air-handling systems (which do not form part of a smoke management system) is applicable in all such buildings, including those serving school lecture theatres not more than 2 000 m2 in area.
Other assembly buildings
E2D20 includes provisions for general assembly buildings not covered elsewhere. Museums and art galleries with fire compartments in excess of 2000 m2 are covered by these provisions.
A building or part of a building being a night club, discotheque or the like, must be provided with—
A Class 9b assembly building which is an exhibition hall must be provided with—
Greater uniformity and consistency
Assembly buildings cover a wide range of uses with varying degrees of hazards. E2D16 to E2D20 address some of the uses to enable greater uniformity in the treatment of the buildings or parts of buildings. It provides for assembly buildings generally, except for certain low hazard occupancies which have been exempted from compliance.
Exempted assembly buildings
Certain provisions for assembly buildings do not apply to schools, apart from the automatic shutdown of air-handling systems in lecture theatres. This is because such buildings may have alarm systems with which the occupants are familiar, and the occupants are usually under a sufficient level of control to enable quick and orderly evacuation.
Concessions are granted for sporting complexes, excluding indoor stadiums with total spectator seating of more than 1000, principally because the risk levels are not high, particularly with regard to open-air complexes. Buildings used solely for religious worship are also exempt.
Assembly buildings with floor area over 2 000 m2
The provisions for smoke exhaust or smoke-and-heat vents are applicable to fire compartments having a floor area of more than 2 000 m2, except that certain concessions apply to low rise buildings.
If the floor area of the fire compartment is not more than 5 000 m2, smoke extraction need not be provided if the building has a rise in storeys of two or less, and a smoke detection and alarm system, or a sprinkler system is installed.
Nightclubs, discotheques and the like
The provisions apply to all nightclubs, discotheques and the like, regardless of the floor area, in recognition of the high hazards generated by such factors as:
Exhibition halls
The provisions for exhibition halls which are used for trade displays and the like are based on them having hazards similar to those for shopping centres and indoor markets.
Theatres and public halls
The provisions only apply to those theatres and public halls which are considered a high hazard occupancy due to the potential fire load associated with the stage and backstage areas and/or rigging lofts. Under Part I1, such theatres and public halls are also required to be sprinkler protected or have the stage and backstage areas separated from the audience by a proscenium wall.
The provisions for these occupancies are similar to those for assembly buildings. The provision for automatic shutdown of air-handling systems (which do not form part of a smoke management system) is applicable in all such buildings, including those serving school lecture theatres not more than 2 000 m2 in area.
Other assembly buildings
E2D20 includes provisions for general assembly buildings not covered elsewhere. Museums and art galleries with fire compartments in excess of 2000 m2 are covered by these provisions.
A building or part of a building used as an exhibition hall, museum, art gallery or the like, must be provided with—
Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.
Greater uniformity and consistency
Assembly buildings cover a wide range of uses with varying degrees of hazards. E2D16 to E2D20 address some of the uses to enable greater uniformity in the treatment of the buildings or parts of buildings. It provides for assembly buildings generally, except for certain low hazard occupancies which have been exempted from compliance.
Exempted assembly buildings
Certain provisions for assembly buildings do not apply to schools, apart from the automatic shutdown of air-handling systems in lecture theatres. This is because such buildings may have alarm systems with which the occupants are familiar, and the occupants are usually under a sufficient level of control to enable quick and orderly evacuation.
Concessions are granted for sporting complexes, excluding indoor stadiums with total spectator seating of more than 1000, principally because the risk levels are not high, particularly with regard to open-air complexes. Buildings used solely for religious worship are also exempt.
Assembly buildings with floor area over 2 000 m2
The provisions for smoke exhaust or smoke-and-heat vents are applicable to fire compartments having a floor area of more than 2 000 m2, except that certain concessions apply to low rise buildings.
If the floor area of the fire compartment is not more than 5 000 m2, smoke extraction need not be provided if the building has a rise in storeys of two or less, and a smoke detection and alarm system, or a sprinkler system is installed.
Nightclubs, discotheques and the like
The provisions apply to all nightclubs, discotheques and the like, regardless of the floor area, in recognition of the high hazards generated by such factors as:
Exhibition halls
The provisions for exhibition halls which are used for trade displays and the like are based on them having hazards similar to those for shopping centres and indoor markets.
Theatres and public halls
The provisions only apply to those theatres and public halls which are considered a high hazard occupancy due to the potential fire load associated with the stage and backstage areas and/or rigging lofts. Under Part I1, such theatres and public halls are also required to be sprinkler protected or have the stage and backstage areas separated from the audience by a proscenium wall.
The provisions for these occupancies are similar to those for assembly buildings. The provision for automatic shutdown of air-handling systems (which do not form part of a smoke management system) is applicable in all such buildings, including those serving school lecture theatres not more than 2 000 m2 in area.
Other assembly buildings
E2D20 includes provisions for general assembly buildings not covered elsewhere. Museums and art galleries with fire compartments in excess of 2000 m2 are covered by these provisions.
Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.
Greater uniformity and consistency
Assembly buildings cover a wide range of uses with varying degrees of hazards. E2D16 to E2D20 address some of the uses to enable greater uniformity in the treatment of the buildings or parts of buildings. It provides for assembly buildings generally, except for certain low hazard occupancies which have been exempted from compliance.
Exempted assembly buildings
Certain provisions for assembly buildings do not apply to schools, apart from the automatic shutdown of air-handling systems in lecture theatres. This is because such buildings may have alarm systems with which the occupants are familiar, and the occupants are usually under a sufficient level of control to enable quick and orderly evacuation.
Concessions are granted for sporting complexes, excluding indoor stadiums with total spectator seating of more than 1000, principally because the risk levels are not high, particularly with regard to open-air complexes. Buildings used solely for religious worship are also exempt.
Assembly buildings with floor area over 2 000 m2
The provisions for smoke exhaust or smoke-and-heat vents are applicable to fire compartments having a floor area of more than 2 000 m2, except that certain concessions apply to low rise buildings.
If the floor area of the fire compartment is not more than 5 000 m2, smoke extraction need not be provided if the building has a rise in storeys of two or less, and a smoke detection and alarm system, or a sprinkler system is installed.
Nightclubs, discotheques and the like
The provisions apply to all nightclubs, discotheques and the like, regardless of the floor area, in recognition of the high hazards generated by such factors as:
Exhibition halls
The provisions for exhibition halls which are used for trade displays and the like are based on them having hazards similar to those for shopping centres and indoor markets.
Theatres and public halls
The provisions only apply to those theatres and public halls which are considered a high hazard occupancy due to the potential fire load associated with the stage and backstage areas and/or rigging lofts. Under Part I1, such theatres and public halls are also required to be sprinkler protected or have the stage and backstage areas separated from the audience by a proscenium wall.
The provisions for these occupancies are similar to those for assembly buildings. The provision for automatic shutdown of air-handling systems (which do not form part of a smoke management system) is applicable in all such buildings, including those serving school lecture theatres not more than 2 000 m2 in area.
Other assembly buildings
E2D20 includes provisions for general assembly buildings not covered elsewhere. Museums and art galleries with fire compartments in excess of 2000 m2 are covered by these provisions.
Greater uniformity and consistency
Assembly buildings cover a wide range of uses with varying degrees of hazards. E2D16 to E2D20 address some of the uses to enable greater uniformity in the treatment of the buildings or parts of buildings. It provides for assembly buildings generally, except for certain low hazard occupancies which have been exempted from compliance.
Exempted assembly buildings
Certain provisions for assembly buildings do not apply to schools, apart from the automatic shutdown of air-handling systems in lecture theatres. This is because such buildings may have alarm systems with which the occupants are familiar, and the occupants are usually under a sufficient level of control to enable quick and orderly evacuation.
Concessions are granted for sporting complexes, excluding indoor stadiums with total spectator seating of more than 1000, principally because the risk levels are not high, particularly with regard to open-air complexes. Buildings used solely for religious worship are also exempt.
Assembly buildings with floor area over 2 000 m2
The provisions for smoke exhaust or smoke-and-heat vents are applicable to fire compartments having a floor area of more than 2 000 m2, except that certain concessions apply to low rise buildings.
If the floor area of the fire compartment is not more than 5 000 m2, smoke extraction need not be provided if the building has a rise in storeys of two or less, and a smoke detection and alarm system, or a sprinkler system is installed.
Nightclubs, discotheques and the like
The provisions apply to all nightclubs, discotheques and the like, regardless of the floor area, in recognition of the high hazards generated by such factors as:
Exhibition halls
The provisions for exhibition halls which are used for trade displays and the like are based on them having hazards similar to those for shopping centres and indoor markets.
Theatres and public halls
The provisions only apply to those theatres and public halls which are considered a high hazard occupancy due to the potential fire load associated with the stage and backstage areas and/or rigging lofts. Under Part I1, such theatres and public halls are also required to be sprinkler protected or have the stage and backstage areas separated from the audience by a proscenium wall.
The provisions for these occupancies are similar to those for assembly buildings. The provision for automatic shutdown of air-handling systems (which do not form part of a smoke management system) is applicable in all such buildings, including those serving school lecture theatres not more than 2 000 m2 in area.
Other assembly buildings
E2D20 includes provisions for general assembly buildings not covered elsewhere. Museums and art galleries with fire compartments in excess of 2000 m2 are covered by these provisions.
Additional smoke hazard management measures may be necessary due to the—
To state that some special hazards may require additional smoke hazard management measures.
E2D21 states that certain factors may need additional smoke hazard management measures.
E2D21 reinforces the need for careful consideration and sound professional judgement in the application of the smoke hazard management provisions of the BCA.
Examples
E2D21 may be applicable in situations where:
In bulk grain storage facility—