Part E1 Fire fighting equipmentThis Part focuses on provision of fire-fighting equipment which can enable occupants to fight the fire in its early stages and/or evacuate the building safely, facilitate fire brigade intervention and minimise the risk of fire spread between buildings.
The Objective of this Part is to—
Fire in buildings
If a fire occurs in a buildingit must not endanger evacuating occupants or spreadto another building.
Facilities to fight a fire in its early stages
Simple and lightweight equipment allows occupants to attack a fire during its early stages. Provision of this equipment often helps occupants to either extinguish or limit the development of a fire before the fire brigade arrives.
Facilities to assistthe fire brigade
To assist in stopping or limiting the spread of fire, facilities must be providedto assist the fire brigade
A building is to be provided with fire-fighting equipment to safeguard against fire spread—
Suitable facilities to be installed
Suitable facilities may need to be installed in a building to minimise the risk of fire spread to:
Facilities may be manually or automatically operated ,and include :fire hydrants ;fire hose reels; sprinkler systems; portable fire extinguishers.
Buildings may incorporate a fire-control centre.
A fire hose reel system must be installed to the degree necessary to allow occupants to safely undertake initial attack on a fire appropriate to—
Fire hose reels in buildings allow occupants to fight a fire. The fire may be in its infancy, and early control or extinguishment may reduce the hazard, allow more time for evacuation and prevent structural damage.
“To the degree necessary”
See the explanation of this term in A1G4(3)(c).
Criteria for fire hose reels
As set out in E1P1, fire hose reels must be installed when necessary, and be appropriate to a number of factors, including:
Deemed-to-Satisfy Provisions
E1D3 provides a number of examples where fire hose reels must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
Performance Solutions
If a Performance Solution is used, it may be appropriate to assess it using E1D3 for guidance purposes. However, it is stressed that compliance with E1D3 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
Fire extinguishers must be installed to the degree necessary to allow occupants to undertake initial attack on a fire appropriate to—
Fire extinguishers in buildings allow occupants to fight fires. Extinguishment may complete all the functions listed in E1P1 above.
Fire extinguishers should be located in plain view, along normal paths of travel and near exits where possible. They should not be located in hazardous places.
“To the degree necessary”
This expression’s use in E1P2 indicates that the BCA recognises that not all buildings need fire extinguishers; and fire extinguishers are used for specific purposes, as set out in AS 2444.
Any decision made in this context can extend to not requiring an item to be installed or a particular level of performance to be achieved, if that is the appropriate action to be taken.
Criteria for fire extinguishers
As set out in E1P2, fire extinguishers must be installed when necessary, and be appropriate to a number of factors, including:
Deemed-to-Satisfy Provisions
E1D5 to E1D12 provide a number of examples where fire extinguishers must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
Performance Solutions
If a Performance Solution is being used, it may be appropriate to assess it using E1D14(3), (4), (5) and (6) for guidance purposes. However, it is stressed that compliance with E1D14(3), (4), (5) and (6) is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
A fire hydrant system must be provided to the degree necessary to facilitate the needs of the fire brigade appropriate to—
E1P3 only applies to a building where a fire brigade is available to attend.
The intent of installing a fire hydrant system is to provide adequate water, under sufficient pressure and flow, to allow the fire brigade to fight fires.
Under its Application provision, E1P3 only applies to buildings located in an area serviced by a fire brigade. This is primarily because the pressures and flows from a fire hydrant are such that hydrants should only be used by the fire brigade.
It is expected that designers will meet any special fire brigade requirements, which may cover such matters as the types of couplings and special flows and pressures to suit a particular nozzle.
“To the degree necessary”
The use of the expression “to the degree necessary” in E1P3 indicates that the BCA recognises that not all buildings need fire hydrants.
Any decision made in this context can extend to not requiring an item to be installed or a particular level of performance to be achieved, if that is the appropriate action to be taken.
Criteria for fire hydrant systems
As set out in E1P3, a fire hydrant system must be installed when necessary, and be appropriate to a number of factors, including:
Deemed-to-Satisfy Provisions
E1D2 provides a number of examples where fire hydrants must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
Performance Solutions
If a Performance Solution is used, it may be appropriate to assess it using E1D2 for guidance purposes. However it is stressed that compliance with E1D2 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
An automatic fire suppression system must be installed to the degree necessary to control the development and spread of fire appropriate to—
E1P4 is not limited to sprinkler systems
A sprinkler system is only one type of automatic fire suppression system. E1P4 is not limited to sprinkler systems. If it can be demonstrated that another automatic fire system can control the development and spread of a fire, it may comply with E1P4. Its activation must be “automatic” and must not depend on human intervention.
Life safety and fire suppression
Automatic fire suppression systems, such as sprinkler systems, are normally used in a building to contain and extinguish fire. When an automatic fire suppression system operates, it not only controls or limits the fire development, but statistics show that, in most cases, the fire is extinguished before the fire brigade arrives at the building.
An automatic fire suppression system is regarded as part of a building’s life safety package because:
“To the degree necessary”
The use of the expression “to the degree necessary” in E1P4 indicates that the BCA recognises that not all buildings need an automatic fire suppression system.
Any decision made in this context can extend to not requiring an item to be installed or particular level of performance to be achieved, if that is the appropriate action to be taken.
Criteria for automatic fire suppression systems
As set out in E1P4, an automatic fire suppression system, such as a sprinkler system, must be installed when necessary, and be appropriate to a number of factors.
When implementing, the likely size and intensity of a fire should be taken into consideration. This can be as measured by:
Deemed-to-Satisfy Provisions
E1D4 provides a number of examples where a sprinkler system must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
Performance Solutions
If a Performance Solution to the Deemed-to-Satisfy Provisions in Part E1 is being used, it may be appropriate to assess it using E1D4 for guidance purposes. However, it is stressed that compliance with E1D4 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
Suitable means of fire-fighting must be installed to the degree necessary in a building under construction to allow initial fire attack by construction workers and for the fire brigade to undertake attack on the fire appropriate to—
A fire in a building under construction represents a significant public safety, health and amenity risk. Accordingly, there is a need for firefighting in such buildings.
This Performance Requirement recognises the fact that a significant number of fires occur in buildings during their construction or major refurbishment. Statistics indicate that a number of fires have been started by sparks. The fire has then spread because services were turned off for construction purposes.
“To the degree necessary”
The use of the expression “to the degree necessary” in E1P5 indicates that the BCA recognises that not all buildings need firefighting services during construction.
Any decision made in this context can extend to not requiring an item to be installed or a particular level of performance to be achieved, if that is the appropriate action to be taken.
Criteria for firefighting services in buildings under construction
As set out in E1P5, firefighting services must be installed in buildings under construction when necessary, and must be appropriate to a number of factors, including:
Deemed-to-Satisfy Provisions
E1D16 provides a number of examples where firefighting services must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
Performance Solutions
If a Performance Solution to the Deemed-to-Satisfy Provisions in Part E1 is being used, it may be appropriate to assess it using E1D16 for guidance purposes. However, it is stressed that compliance with E1D16 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
Suitable facilities must be provided to the degree necessary in a building to co-ordinate fire brigade intervention during an emergency appropriate to—
E1P6 requires that a part of a building be set aside for the fire brigade to co-ordinate its search and rescue, and firefighting operations during a fire. These areas are referred to as “fire control centres”.
“To the degree necessary”
The use of the expression “to the degree necessary” in E1P6 indicates that the BCA recognises that not all buildings need a fire control centre. Any decision made in this context can extend to not requiring an item to be installed or a particular level of performance to be achieved, if that is the appropriate action to be taken.
Criteria for co-ordination facilities
As set out in E1P6, co-ordination facilities must be installed when necessary, and be appropriate to a number of factors, including:
Deemed-to-Satisfy Provisions
E1D15 provides a number of examples where a fire control centre must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
Performance Solutions
If a Performance Solution to the Deemed-to-Satisfy Provisions in Part E1 is being used, it may be appropriate to assess it using E1D15 for guidance purposes. However, it is stressed that compliance with E1D15 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
An automatic fire detection system must be installed to the degree necessary to alert the fire brigade of fire so that fire fighting operations may be undertaken at the earliest possible time to limit property and environmental damage appropriate to—
Tas E1P7 only applies to—
Performance RequirementsE1P1 to E1P6 and TAS E1P7 are satisfied by complying with E1D2 to E1D16, TAS E1D17, and for farm buildings and farm sheds, Part I3.
To clarify that the requirements of E1P1 to E1P6 will be satisfied if compliance is achieved with E1D2 to E1D17 in the case of all buildings, Part G3 in the case of buildings with an atrium, Part G4 in the case of buildings in alpine areas, Part G6 in the case of occupiable outdoor areas, Part I1 in the case of theatres, stages and public halls and Part I3 for farm buildings and farm sheds.
Building Group | Floor area (m2) | Minimum water supply quantity (L) |
---|---|---|
Group A | 500 to 1,000 | 36,000 |
1,001 to 2,000 | 72,000 | |
2,001 to 5,000 | 144,000 | |
Group B | 500 to 1,000 | 72,000 |
1,001 to 2,000 | 144,000 | |
Group C | 5 L/m2 or 36,000 L at each location, whichever is greater |
A single water supply with the minimum water quantity outlined in Table SA E1D2 can serve more than one building.
To require the installation of suitable fire hydrant systems to facilitate the fire brigade’s firefighting operations.
When required—E1D2(1)
Fire hydrants are needed to prevent the spread of fire between buildings and fire compartments. They are basically needed for fire brigade use and are not intended for use by occupants. Properly trained people and special equipment are needed for effective firefighting using a fire hydrant system.
The floor area of 500 m2 referred to in E1D2(1)(a) represents the level of hazard which justifies the installation of a fire hydrant system.
If the building is located a substantial distance from a fire brigade station equipped to utilise fire hydrants, E1D2(1)(b) allows the building to be constructed without a fire hydrant system. The reasons for this are that the fire hydrants are intended for use only by a fire brigade and the benefit of fire brigade intervention during a building fire is expected to diminish with the passage of time.
AS 2419.1—E1D2(2)
Under E1D2(2), the installation of a fire hydrant system, including the associated water supply, pipe work, pumps, and so on, must be in accordance with AS 2419.1 subject to concessions granted under E1D2(3).
Clause 4.2 of AS 2419.1 requires a four hour water storage capacity for firefighting purposes. This clause does not apply to Class 8 electricity network substations where town main water supply cannot be connected and where at least one hour storage capacity of water for fire fighting purposes is provided. The reduced capacity is in recognition of the inherent fire mitigation measures such as boundary separation, vegetation removal programs, and perimeter access road protection associated with remotely located Class 8 electricity network substations. The nature of the initial fire response will also always require substation staff involvement prior to any fire brigade response. This removes the need for large water storage capacities usually associated with early intervention by the fire brigade.
Location—E1D2(3)
External fire hydrants are to be located in accordance with the requirements of AS 2419.1. Multiple buildings may be served by a single fire hydrant providing the proximity requirements of AS 2419.1 are met.
For internal fire hydrants, E1D2(4) generally requires the installation of internal fire hydrants on the storey they are to service. The reason for this is to eliminate running a fire hydrant hose up or down a stairway. Also, if the sole-occupancy units are in different ownership or leasehold, access between them may be difficult.
E1D2(4) grants a concession when a sole-occupancy unit occupies more than one storey. The concession is conditional on the fire hydrant being located at the level of egress from the sole-occupancy unit.
In the case of a Class 2 or Class 3 building or a Class 4 part, there is no limitation on the size or number of storeys within the sole-occupancy unit which can be served by the fire hydrant.
For Class 5 to Class 9 buildings the concession is limited to sole-occupancy units with only two storeys, where the fire hydrant at the entrance level provides total hose coverage. AS 2419.1 provides details of the required coverage.
If any conflict exists between AS 2419.1 and the BCA, then the BCA takes precedence. Additional information can be obtained by reference to the standard, includingit’s informative appendices.
AS 2419.1 provides the details for determining the number of fire hydrants required and where they should be located.
Pumpsets
Requirements for pumpsets, including the location of pumprooms, etc., is contained in AS 2419.1.
Water source, pressures and flows
The requirements for the water supply and source, and the required flows and pressure for the fire hydrant system to operate effectively are contained in AS 2419.1.
must be installed to provide the minimum flow and pressures required by clause 6.1 of AS 2441.
To require the installation of suitable fire hose reel systems to enable, where appropriate, a building’s occupants to undertake initial attack on a fire.
When required—E1D3(1)
Refer to E1P1 for the reasons why the BCA requires the installation of fire hose reels in buildings.
E1D3(1)(a) provides an exemption to the installation of fire hose reels in a Class 2, 3 or 5 building or Class 4 part of a building. However, it should be noted that portable fire extinguishers must be installed to cover Class A fire risks in accordance with E1D14.
E1D3(1)(b) provides an exemption to the installation of fire hose reels in Class 8 electricity network substations. The use of water as an extinguishing medium in electricity network substations can cause extensive damage to the electricity assets and create increased hazards for firefighters. The initial staff response to fire will always be through the more appropriate usage of portable fire extinguishers followed by evacuation.
E1D3(1)(c) does not require the installation of fire hose reels in a Class 9c building. It is recognised that occupants close to the point of ignition often provide the most effective means of extinguishing a small fire before it grows. In this case staff and visitors, if not some residents, can be effective in performing this function. To do so, they require appropriate means of extinguishment.
It is considered that the provision of portable extinguishers in a residential care building provides adequate means for staff and visitors to attack the fire. The additional level of fire safety associated with the provision of fire hose reels is not considered necessary.
It is not expected that the number of staff available in a residential care building will be adequate to both fight a growing fire with fire hose reels and evacuate residents. This is particularly the case when it is noted that the BCA provisions for residential care buildings are based on minimum staffing levels. When a fire becomes too large to be attacked with portable extinguishers, staff will be fully involved in closing doors and evacuating residents rather than fighting the fire.
E1D3(1)(d) does not require the installation of fire hose reels in classrooms and associated corridors of primary and secondary schools. However, it should be noted that where fire hose reels are not installed in these buildings, portable fire extinguishers must be installed in accordance with E1D14.
The concession not requiring the installation of fire hose reels in classrooms, etc is based on normal school use when teachers or school staff could be expected to be in control of students for the purpose of evacuation. Fire hose reels are required in other areas of the school such as halls, gymnasiums, etc where activities take place outside normal school hours and with outside organisations that are not under the control of teachers or school staff.
E1D3(2)(a) requires the installation of fire hose reels where internal fire hydrants are provided.
The 500 m2 floor area referred to in E1D3(2)(b) represents the level of hazard which justifies the installation of fire hose reels to allow occupants the opportunity to attempt an initial attack on a fire.
System design—E1D3(3)
E1D3(3)(b) generally requires the installation of fire hose reels on the storey they are to service. This eliminates the need to run a fire hose up or down a stairway. Also, if the sole-occupancy units are in different ownership or leasehold, access between them may be difficult. It means that anyone using the fire hose will be able to get away quickly if the fire gets out of control.
E1D3(3)(b) grants a concession when a sole-occupancy unit in a Class 6–9 building occupies two storeys provided the fire hose reel can provide total hose coverage. The fire hose reel must also be located at the level of egress from the sole- occupancy unit.
E1D3(4), (5) and (6) relate to the positioning of fire hose reels to help occupants attack a fire in its early stages. These provisions emphasise the importance of the location of fire hose reels to ensure safety.
E1D3(4) ensures that fire hose reels are located to achieve the system coverage required by AS 2441. The fire hose reels can be located internally, externally or in any combination to achieve this coverage as set out in E1D3(5).
Fire hose reels are not permitted to be installed within a fire-isolated exit, thereby avoiding having the hose pass through the door to access the fire. Such an arrangement would require the exit to be open, and therefore cause a significant risk of smoke entering.
The same concerns do not apply to the other Deemed-to-Satisfy Provisions listed in E1D3(6). In the cases listed below, the door may remain open for the hose to pass through.
E1D3(5) is applicable to individual fire hose reels, such that the choices offered in E1D3(5)(a), (b) or (c) are applied to the location of each hose reel in turn, to assure that coverage is achieved. However E1D3(5)(c) is only applicable when the application of E1D3(5)(a) or (b) does not achieve coverage.
The individual application means that when each hose reel is located adjacent to a hydrant or an exit, a check for coverage should be done before the next location is chosen.
Once coverage has been achieved, it is not necessary to install any more hose reels, even if additional exits or hydrants are provided for the storey.
Alternatively, if hose reels have been located adjacent to all relevant hydrants or exits without achieving coverage, E1D3(5)(c) permits the additional hose reels needed to achieve coverage to be located in a path of travel to an exit.
A sprinkler system must—
To require the installation of suitable fire sprinkler systems where necessary to address specific hazards.
When required
Refer to the comment on E1P4 for the reasons why the BCA requires the installation of sprinkler systems in buildings.
E1D5 to E1D13 set out when sprinklers are required in a building, while Specification 17 and Specification 18 set out the type of sprinkler system required and other technical details.
Specification 17 and Specification 18 allow the use of a residential sprinkler system in certain Class 2, 3, 9a and 9c buildings.
Sprinklers are required throughout the whole building if any part of the building has an effective height of more than 25 m—
To require the installation of suitable fire sprinkler systems where necessary to address specific hazards.
E1D5 to E1D13
These provisions specify when sprinklers are required in a building and which parts of the building must be sprinkler protected. Unless a fire wall or other construction with the appropriate FRLs separates parts of a building required to have sprinklers from a part of a building not required to have sprinklers, then the sprinkler requirements must be applied to the whole building.
E1D5 requires all buildings with an effective height of more than 25 metres,except those which only contain an open-deck carpark, to be sprinkler protected. An exemption is also granted to smaller Class 8 electricity network substations within a multi-classified building as they are provided with additional fire protection measures to compensate for the removal of sprinklers. The provision regarding an effective height of 25 metres recognises the effective operating height for fire brigade ladders and other firefighting and rescue equipment.
E1D6 requires sprinkler protection to Class 2 or 3 buildings (excluding a residential care building — see other table items for residential care buildings) where the rise in storeys is 4 or more and the effective height is not more than 25 m. The requirements for these sprinkler systems are contained within Specification 17 and Specification 18.
The reference in E1D10 to a Class 9a health care building used as a residential care building makes it clear that where a Class 9a building is used as a residential care building as defined in Schedule 3, it must be fitted with a sprinkler system installed in accordance with AS 2118.1 or AS 2118.4.
To provide further clarification, a Class 9a health care building used as a residential care building must meet the BCA provisions that apply for a Class 9a health care building.
The definition of a health care building means a building whose occupants or patients undergoing medical treatment need physical assistance to evacuate the building during an emergency and includes a nursing home or similar facility for sick ordisabled persons needing full-time care. Therefore, a health care building could include a residential aged care building in which occupants are provided with some level of medication, and need assistance to evacuate.
To require the installation of suitable fire sprinkler systems where necessary to address specific hazards.
E1D5 to E1D13
These provisions specify when sprinklers are required in a building and which parts of the building must be sprinkler protected. Unless a fire wall or other construction with the appropriate FRLs separates parts of a building required to have sprinklers from a part of a building not required to have sprinklers, then the sprinkler requirements must be applied to the whole building.
E1D5 requires all buildings with an effective height of more than 25 metres,except those which only contain an open-deck carpark, to be sprinkler protected. An exemption is also granted to smaller Class 8 electricity network substations within a multi-classified building as they are provided with additional fire protection measures to compensate for the removal of sprinklers. The provision regarding an effective height of 25 metres recognises the effective operating height for fire brigade ladders and other firefighting and rescue equipment.
E1D6 requires sprinkler protection to Class 2 or 3 buildings (excluding a residential care building — see other table items for residential care buildings) where the rise in storeys is 4 or more and the effective height is not more than 25 m. The requirements for these sprinkler systems are contained within Specification 17 and Specification 18.
The reference in E1D10 to a Class 9a health care building used as a residential care building makes it clear that where a Class 9a building is used as a residential care building as defined in Schedule 3, it must be fitted with a sprinkler system installed in accordance with AS 2118.1 or AS 2118.4.
To provide further clarification, a Class 9a health care building used as a residential care building must meet the BCA provisions that apply for a Class 9a health care building.
The definition of a health care building means a building whose occupants or patients undergoing medical treatment need physical assistance to evacuate the building during an emergency and includes a nursing home or similar facility for sick ordisabled persons needing full-time care. Therefore, a health care building could include a residential aged care building in which occupants are provided with some level of medication, and need assistance to evacuate.
Sprinklers are required throughout—
Sprinklers are required throughout a building containing—
To require the installation of suitable fire sprinkler systems where necessary to address specific hazards.
E1D5 to E1D13
These provisions specify when sprinklers are required in a building and which parts of the building must be sprinkler protected. Unless a fire wall or other construction with the appropriate FRLs separates parts of a building required to have sprinklers from a part of a building not required to have sprinklers, then the sprinkler requirements must be applied to the whole building.
E1D5 requires all buildings with an effective height of more than 25 metres,except those which only contain an open-deck carpark, to be sprinkler protected. An exemption is also granted to smaller Class 8 electricity network substations within a multi-classified building as they are provided with additional fire protection measures to compensate for the removal of sprinklers. The provision regarding an effective height of 25 metres recognises the effective operating height for fire brigade ladders and other firefighting and rescue equipment.
E1D6 requires sprinkler protection to Class 2 or 3 buildings (excluding a residential care building — see other table items for residential care buildings) where the rise in storeys is 4 or more and the effective height is not more than 25 m. The requirements for these sprinkler systems are contained within Specification 17 and Specification 18.
The reference in E1D10 to a Class 9a health care building used as a residential care building makes it clear that where a Class 9a building is used as a residential care building as defined in Schedule 3, it must be fitted with a sprinkler system installed in accordance with AS 2118.1 or AS 2118.4.
To provide further clarification, a Class 9a health care building used as a residential care building must meet the BCA provisions that apply for a Class 9a health care building.
The definition of a health care building means a building whose occupants or patients undergoing medical treatment need physical assistance to evacuate the building during an emergency and includes a nursing home or similar facility for sick ordisabled persons needing full-time care. Therefore, a health care building could include a residential aged care building in which occupants are provided with some level of medication, and need assistance to evacuate.
In a Class 6 building, sprinklers are required in fire compartments where either of the following apply:
To require the installation of suitable fire sprinkler systems where necessary to address specific hazards.
E1D5 to E1D13
These provisions specify when sprinklers are required in a building and which parts of the building must be sprinkler protected. Unless a fire wall or other construction with the appropriate FRLs separates parts of a building required to have sprinklers from a part of a building not required to have sprinklers, then the sprinkler requirements must be applied to the whole building.
E1D5 requires all buildings with an effective height of more than 25 metres,except those which only contain an open-deck carpark, to be sprinkler protected. An exemption is also granted to smaller Class 8 electricity network substations within a multi-classified building as they are provided with additional fire protection measures to compensate for the removal of sprinklers. The provision regarding an effective height of 25 metres recognises the effective operating height for fire brigade ladders and other firefighting and rescue equipment.
E1D6 requires sprinkler protection to Class 2 or 3 buildings (excluding a residential care building — see other table items for residential care buildings) where the rise in storeys is 4 or more and the effective height is not more than 25 m. The requirements for these sprinkler systems are contained within Specification 17 and Specification 18.
The reference in E1D10 to a Class 9a health care building used as a residential care building makes it clear that where a Class 9a building is used as a residential care building as defined in Schedule 3, it must be fitted with a sprinkler system installed in accordance with AS 2118.1 or AS 2118.4.
To provide further clarification, a Class 9a health care building used as a residential care building must meet the BCA provisions that apply for a Class 9a health care building.
The definition of a health care building means a building whose occupants or patients undergoing medical treatment need physical assistance to evacuate the building during an emergency and includes a nursing home or similar facility for sick ordisabled persons needing full-time care. Therefore, a health care building could include a residential aged care building in which occupants are provided with some level of medication, and need assistance to evacuate.
In a Class 7a building, other than an open-deck carpark, sprinklers are required in fire compartments where more than 40 vehicles are accommodated.
To require the installation of suitable fire sprinkler systems where necessary to address specific hazards.
These provisions specify when sprinklers are required in a building and which parts of the building must be sprinkler protected. Unless a fire wall or other construction with the appropriate FRLs separates parts of a building required to have sprinklers from a part of a building not required to have sprinklers, then the sprinkler requirements must be applied to the whole building.
E1D5 requires all buildings with an effective height of more than 25 metres,except those which only contain an open-deck carpark, to be sprinkler protected. An exemption is also granted to smaller Class 8 electricity network substations within a multi-classified building as they are provided with additional fire protection measures to compensate for the removal of sprinklers. The provision regarding an effective height of 25 metres recognises the effective operating height for fire brigade ladders and other firefighting and rescue equipment.
E1D6 requires sprinkler protection to Class 2 or 3 buildings (excluding a residential care building — see other table items for residential care buildings) where the rise in storeys is 4 or more and the effective height is not more than 25 m. The requirements for these sprinkler systems are contained within Specification 17 and Specification 18.
The reference in E1D10 to a Class 9a health care building used as a residential care building makes it clear that where a Class 9a building is used as a residential care building as defined in Schedule 3, it must be fitted with a sprinkler system installed in accordance with AS 2118.1 or AS 2118.4.
To provide further clarification, a Class 9a health care building used as a residential care building must meet the BCA provisions that apply for a Class 9a health care building.
The definition of a health care building means a building whose occupants or patients undergoing medical treatment need physical assistance to evacuate the building during an emergency and includes a nursing home or similar facility for sick ordisabled persons needing full-time care. Therefore, a health care building could include a residential aged care building in which occupants are provided with some level of medication, and need assistance to evacuate.
To require the installation of suitable fire sprinkler systems where necessary to address specific hazards.
E1D5 to E1D13
These provisions specify when sprinklers are required in a building and which parts of the building must be sprinkler protected. Unless a fire wall or other construction with the appropriate FRLs separates parts of a building required to have sprinklers from a part of a building not required to have sprinklers, then the sprinkler requirements must be applied to the whole building.
E1D5 requires all buildings with an effective height of more than 25 metres,except those which only contain an open-deck carpark, to be sprinkler protected. An exemption is also granted to smaller Class 8 electricity network substations within a multi-classified building as they are provided with additional fire protection measures to compensate for the removal of sprinklers. The provision regarding an effective height of 25 metres recognises the effective operating height for fire brigade ladders and other firefighting and rescue equipment.
E1D6 requires sprinkler protection to Class 2 or 3 buildings (excluding a residential care building — see other table items for residential care buildings) where the rise in storeys is 4 or more and the effective height is not more than 25 m. The requirements for these sprinkler systems are contained within Specification 17 and Specification 18.
The reference in E1D10 to a Class 9a health care building used as a residential care building makes it clear that where a Class 9a building is used as a residential care building as defined in Schedule 3, it must be fitted with a sprinkler system installed in accordance with AS 2118.1 or AS 2118.4.
To provide further clarification, a Class 9a health care building used as a residential care building must meet the BCA provisions that apply for a Class 9a health care building.
The definition of a health care building means a building whose occupants or patients undergoing medical treatment need physical assistance to evacuate the building during an emergency and includes a nursing home or similar facility for sick ordisabled persons needing full-time care. Therefore, a health care building could include a residential aged care building in which occupants are provided with some level of medication, and need assistance to evacuate.
E1D11(2) does not apply to a Class 9b early childhood centre—
To require the installation of suitable fire sprinkler systems where necessary to address specific hazards.
E1D5 to E1D13
These provisions specify when sprinklers are required in a building and which parts of the building must be sprinkler protected. Unless a fire wall or other construction with the appropriate FRLs separates parts of a building required to have sprinklers from a part of a building not required to have sprinklers, then the sprinkler requirements must be applied to the whole building.
E1D5 requires all buildings with an effective height of more than 25 metres,except those which only contain an open-deck carpark, to be sprinkler protected. An exemption is also granted to smaller Class 8 electricity network substations within a multi-classified building as they are provided with additional fire protection measures to compensate for the removal of sprinklers. The provision regarding an effective height of 25 metres recognises the effective operating height for fire brigade ladders and other firefighting and rescue equipment.
E1D6 requires sprinkler protection to Class 2 or 3 buildings (excluding a residential care building — see other table items for residential care buildings) where the rise in storeys is 4 or more and the effective height is not more than 25 m. The requirements for these sprinkler systems are contained within Specification 17 and Specification 18.
The reference in E1D10 to a Class 9a health care building used as a residential care building makes it clear that where a Class 9a building is used as a residential care building as defined in Schedule 3, it must be fitted with a sprinkler system installed in accordance with AS 2118.1 or AS 2118.4.
To provide further clarification, a Class 9a health care building used as a residential care building must meet the BCA provisions that apply for a Class 9a health care building.
The definition of a health care building means a building whose occupants or patients undergoing medical treatment need physical assistance to evacuate the building during an emergency and includes a nursing home or similar facility for sick ordisabled persons needing full-time care. Therefore, a health care building could include a residential aged care building in which occupants are provided with some level of medication, and need assistance to evacuate.
To require the installation of suitable fire sprinkler systems where necessary to address specific hazards.
E1D5 to E1D13
These provisions specify when sprinklers are required in a building and which parts of the building must be sprinkler protected. Unless a fire wall or other construction with the appropriate FRLs separates parts of a building required to have sprinklers from a part of a building not required to have sprinklers, then the sprinkler requirements must be applied to the whole building.
E1D5 requires all buildings with an effective height of more than 25 metres,except those which only contain an open-deck carpark, to be sprinkler protected. An exemption is also granted to smaller Class 8 electricity network substations within a multi-classified building as they are provided with additional fire protection measures to compensate for the removal of sprinklers. The provision regarding an effective height of 25 metres recognises the effective operating height for fire brigade ladders and other firefighting and rescue equipment.
E1D6 requires sprinkler protection to Class 2 or 3 buildings (excluding a residential care building — see other table items for residential care buildings) where the rise in storeys is 4 or more and the effective height is not more than 25 m. The requirements for these sprinkler systems are contained within Specification 17 and Specification 18.
The reference in E1D10 to a Class 9a health care building used as a residential care building makes it clear that where a Class 9a building is used as a residential care building as defined in Schedule 3, it must be fitted with a sprinkler system installed in accordance with AS 2118.1 or AS 2118.4.
To provide further clarification, a Class 9a health care building used as a residential care building must meet the BCA provisions that apply for a Class 9a health care building.
The definition of a health care building means a building whose occupants or patients undergoing medical treatment need physical assistance to evacuate the building during an emergency and includes a nursing home or similar facility for sick ordisabled persons needing full-time care. Therefore, a health care building could include a residential aged care building in which occupants are provided with some level of medication, and need assistance to evacuate.
To require the installation of suitable fire sprinkler systems where necessary to address specific hazards.
E1D5 to E1D13
These provisions specify when sprinklers are required in a building and which parts of the building must be sprinkler protected. Unless a fire wall or other construction with the appropriate FRLs separates parts of a building required to have sprinklers from a part of a building not required to have sprinklers, then the sprinkler requirements must be applied to the whole building.
E1D5 requires all buildings with an effective height of more than 25 metres,except those which only contain an open-deck carpark, to be sprinkler protected. An exemption is also granted to smaller Class 8 electricity network substations within a multi-classified building as they are provided with additional fire protection measures to compensate for the removal of sprinklers. The provision regarding an effective height of 25 metres recognises the effective operating height for fire brigade ladders and other firefighting and rescue equipment.
E1D6 requires sprinkler protection to Class 2 or 3 buildings (excluding a residential care building — see other table items for residential care buildings) where the rise in storeys is 4 or more and the effective height is not more than 25 m. The requirements for these sprinkler systems are contained within Specification 17 and Specification 18.
The reference in E1D10 to a Class 9a health care building used as a residential care building makes it clear that where a Class 9a building is used as a residential care building as defined in Schedule 3, it must be fitted with a sprinkler system installed in accordance with AS 2118.1 or AS 2118.4.
To provide further clarification, a Class 9a health care building used as a residential care building must meet the BCA provisions that apply for a Class 9a health care building.
The definition of a health care building means a building whose occupants or patients undergoing medical treatment need physical assistance to evacuate the building during an emergency and includes a nursing home or similar facility for sick ordisabled persons needing full-time care. Therefore, a health care building could include a residential aged care building in which occupants are provided with some level of medication, and need assistance to evacuate.
To require the installation of suitable portable fire extinguishers, where necessary, to address specific hazards.
When required
Refer to the comment on E1P2 for the reasons why the NCC requires the installation of portable fire extinguishers in buildings.
E1D14(1)(a) requires portable fire extinguishers to be provided as listed in E1D14(3) and (4).
For a Class 2, 3 or 5 building or Class 4 part of a building, E1D14(1)(b) requires portable fire extinguishers to only be provided—
Subject to E1D14(2), E1D14(1)(c) requires portable fire extinguishers to be installed in accordance with Sections 1, 2, 3 and 4 of AS 2444. The other sections of AS 2444 deal with “Selection and distribution of portable fire extinguishers in vehicles and small craft” and “Selection and location of fire blankets”, neither of which are applicable to the BCA. If any conflict exists between AS 2444 and the BCA, then the BCA takes precedence. Additional information can be obtained by reference to the Standard.
E1D14(2) details specific requirements about the type, size and installation of portable fire extinguishers provided in a Class 2 or 3 building or Class 4 part of a building.
E1D14(3) and (4) set out when portable fire extinguishers are required in a building and the class of extinguisher to be used.
It should be noted that E1D14(3) and (4) require the installation of fire extinguishers in classrooms and associated corridors in primary and secondary schools not provided with fire hose reels. The reason for this requirement is that E1D3(1)(d) does not require the installation of fire hose reels in these buildings, even if the floor area of a fire compartment exceeds 500 m2.
A fire control centre facility in accordance with Specification 19 must be provided for—
To require the provision of suitable fire control centres to facilitate fire brigade operations.
When required
Refer to the comment on E1P6 for the reasons why the BCA requires the installation of fire control centres in buildings.
E1D15(a) requires all buildings with an effective height of more than 25 metres to be provided with a fire control centre. Because of their height these buildings require special co-ordination of fire brigade operations. The E1D14(a) reference to an effective height of 25 metres recognises the operating height for fire brigade ladders and other firefighting and rescue equipment.
E1D15(b) requires a fire control centre for Class 6–9 buildings with a total floor area of more than 18 000 m2.
The measurement concerned is of the total building floor area, not the area of an individual sole-occupancy unit or fire compartment.
Class 6 and Class 9 buildings have been included because of their high potential fire load, and the likelihood of large populations unfamiliar with their layout or evacuation procedures.
Class 7 and Class 8 buildings have been included because of the potential size and severity of fires in such buildings. Specification 19 sets out the construction details of such a centre and the facilities it must contain.
In a building under construction—
To require adequate firefighting equipment within a building during its construction.
When required
Refer to the comment on E1P5 for the reasons why the BCA requires the installation of firefighting equipment in buildings during their construction.
E1D16(a) requires the installation of suitable fire extinguishers in all buildings under construction. They are to be placed adjacent to exits on each storey so that they can be easily found by workers if a fire occurs.
Once a building reaches a height of about 12 metres, firefighting in a building under construction becomes increasingly difficult. The installation of fire hydrants, fire hose reels and booster connections (required under E1D16(b)) assist in overcoming such difficulties. The fire hydrants and fire hose reels are not required on the two upper floors because services such as water supply may not be installed. Also, if a fire occurred on these floors, it could be fought from the floors below.
Suitable additional provision must be made if special problems of fighting fire could arise because of—
To require the installation of additional fire safety measures where special hazards exist.
When required
The other Deemed-to-Satisfy Provisions of Part E1 set out the required firefighting equipment and co-ordination facilities required in a building to deal with “expected” or “usual” hazards. However, it is not possible to take account of every possible hazard. E1D17 may even require additional provision for special hazards where Part E1 does not otherwise apply.
Additional provision for special hazards must be made to allow for effective firefighting operations taking into consideration:
Examples
Special fire hazards may exist for hazards under E1D17(a) in a warehouse used to store highly volatile or combustible materials, and also, at a site where highly combustible chemicals are manufactured. Hazards under E1D17(b) may include sites where little or no water is available for firefighting.
The BCA Deemed-to-Satisfy Provisions do not specify what the special provisions must be. Each case must be assessed on its own merits.
Part B4 of NCC Volume Three sets out the requirements for access for maintenance of fire-fighting water services.