NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Filter by state
  • Australian Capital Territory
  • New South Wales
  • Northern Territory
  • Queensland
  • South Australia
  • Tasmania
  • Victoria
  • Western Australia
Filter by zone
  • Climate Zone 1
  • Climate Zone 2
  • Climate Zone 3
  • Climate Zone 4
  • Climate Zone 5
  • Climate Zone 6
  • Climate Zone 7
  • Climate Zone 8
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Filter by state
  • Australian Capital Territory
  • New South Wales
  • Northern Territory
  • Queensland
  • South Australia
  • Tasmania
  • Victoria
  • Western Australia
Filter by zone
  • Climate Zone 1
  • Climate Zone 2
  • Climate Zone 3
  • Climate Zone 4
  • Climate Zone 5
  • Climate Zone 6
  • Climate Zone 7
  • Climate Zone 8
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

19

Specification 19 Fire control centres

Specification 19 Fire control centres

2019: Spec E1.8: 1

To clarify that Specification 19 provides the construction and content details for fire control centres and rooms.

Fire control centres or rooms

Specification 19 sets out the construction and content details for fire control centres and rooms required by the BCA.

A fire control room is a fire control centre in a dedicated room with specific requirements. See S19C7 which requires that where a fire control centre is in a building of more than 50 metres in effective height, the centre must be in a separate room.

S19C3 to S19C6 set out the requirements for fire control centres (including fire control rooms) while S19C7 to S19C13 set out additional requirements for fire control centres which are required to be located in a dedicated room, which is commonly referred to as a fire control room.

Note: this commentary also applies to S19C2.

2019: Spec E1.8: 1

To clarify that Specification 19 provides the construction and content details for fire control centres and rooms.

Fire control centres or rooms

Specification 19 sets out the construction and content details for fire control centres and rooms required by the BCA.

A fire control room is a fire control centre in a dedicated room with specific requirements. See S19C7 which requires that where a fire control centre is in a building of more than 50 metres in effective height, the centre must be in a separate room.

S19C3 to S19C6 set out the requirements for fire control centres (including fire control rooms) while S19C7 to S19C13 set out additional requirements for fire control centres which are required to be located in a dedicated room, which is commonly referred to as a fire control room.

Note: this commentary also applies to S19C2.

2019: Spec E1.8: 2

To clarify the facilities a fire control centre must contain.

Fire control centre required by E1D15

E1D15 sets out when a fire control centre is required in a building.

Exclusive purpose of centre

S19C3 sets out that a fire control centre must be for the exclusive purpose of:

  • directing firefighting operations and other functions of the fire brigade, such as search and rescue operations (this requirement reflects the importance placed on fire brigade operations); and
  • other measures directly relating to occupant safety or security.

In this context, the centre or room cannot be used for any other purpose.

2019: Spec E1.8: 3

To require that a fire control centre be conveniently placed to allow egress.

Egress

Egress from the fire control centre must not involve a change in level exceeding 300 mm. This is to help fire brigade officers carrying their equipment and make entry easy.

2019: Spec E1.8: 4

To limit the type of equipment allowed in a fire control centre.

Extraneous equipment not allowed

Since the fire control centre will be occupied by fire brigade personnel during a fire, possibly for a period long after the other occupants have evacuated, it must be suitable for directing fire brigade operations. Equipment which does not assist in this function, or could endanger the fire brigade personnel, is not allowed in the centre.

2019: Spec E1.8: 5

To minimise the risk of the sound levels in a fire control centre interfering with the room’s function.

Noise must not interfere with communications

The fire control centre is used to direct fire brigade operations during a fire in the building, possibly for a period long after the other occupants have evacuated. This involves communication with other fire brigade officers outside the centre. It is therefore important that ambient sound levels do not interfere with that communication.

2019: Spec E1.8: 6

To set out the construction details of fire control rooms.

Buildings over 50 metres in effective height

E1D15 requires certain buildings to contain a fire control centre. S19C7 only applies to those buildings with an effective height greater than 50 metres. In these buildings, a fire control centre must be within a dedicated room known as a fire control room. Since the fire control room will be occupied by fire brigade personnel during a fire in the building, it must be fire separated from the remainder of the building.

 

2019: Spec E1.8: 7

To require that the fire-resisting performance of a fire control room is maintained.

Openings must be fire protected

The aim of S19C8 is similar to S19C7, except that S19C8 deals with openings in the construction separating the fire control room from the remainder of the building.

2019: Spec E1.8: 8

To require adequate access to a fire control room.

Application

Refer to comment on S19C1.

Access

The main provisions deal with access to the fire control room. Since it will be necessary for the fire brigade to gain access to the fire control room while the building is being evacuated, access to it must not be obstructed by people evacuating.

Providing access by way of two paths of travel is to help fire brigade access. One of those paths must be from the front entrance of the building, and the other must be from a public place or a fire-isolated passage which leads from a public place.

 

2019: Spec E1.8: 9

To set out the contents required in a fire control room.

Application

Refer to comment on S19C1.

S19C10(1) sets out the minimum size and contents required in a fire control room.

S19C10(2) lists additional items which may be contained in a fire control room. This list is not exhaustive, other items may be added provided the floor area of the room is increased, as required by S19C10(3).

S19C10(3) sets out the area requirements for fire control rooms.

 

2019: Spec E1.8: 10

To reduce the likelihood of smoke accumulating in a fire control room.

Application

Refer to comment on S19C1.

Since the fire control room will be occupied by fire brigade personnel, possibly for a period long after the other occupants have evacuated, it must have adequate means of preventing the accumulation of smoke. The room can have either natural ventilation complying with S19C11(1)(a) or a pressurisation system complying with S19C11(1)(b).

If natural ventilation is used, then the window or door must not open to another part of the building.

If a pressurisation system is used, it must comply with AS 1668.1 and the other provisions of S19C11(1)(b). This is achieved by treating the room similarly to a fire-isolated stairway, which includes:

  • activation of the system;
  • air change rates;
  • protection of fans, motors and duct work;
  • protection of the electrical supply to the system; and
  • relief air devices.
2019: Spec E1.8: 11

To require that a fire control room is appropriately identified.

Application

Refer to comment on S19C1.

S19C12 achieves the intent by requiring the placement of a sign on the door to the room. Such a sign is required on all doors to a fire control room.

2019: Spec E1.8: 12

To provide sufficient illumination to the fire control room during an emergency.

Application

Refer to comment on S19C1.

Since the fire control room will be occupied by fire brigade personnel during a fire in the building, possibly for a period long after the other occupants have evacuated, it must have appropriate levels of lighting. As the lighting must be maintained while the room is in use, it must be emergency lighting in case of failure of the building’s normal lighting system.

Normally, emergency lighting is only used for evacuation purposes. A fire control room is used to direct fire brigade operations, which will include such actions as reference to building plans, and the reading of other information. The amount of emergency lighting in the room must therefore be increased to 400 lux.