In this Part, a reference to an entrance or exit does not include a reference to an entrance or exit provided for persons or animals performing in a temporary structure.
NCC Title
Exits — exclusions
NCC State
NSW
NCC SPTC Current
Exits — exclusions
NCC ID
_c68c672b-231b-4fdf-8c05-ea387bc5e6d6
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
Exits must be so provided and arranged as to afford a ready means of egress from all parts of a temporary structure.
the number of exits to be provided for a temporary structure designed to accommodate a number of persons specified in Column 1 of NSW Table I5D4 must be not less than the number of exits specified in Column 2 of that Table in respect of that number of persons; and
the aggregate width of the exits to a temporary structure designed to accommodate a number of persons specified in Column 1 of NSW Table I5D4 must be not less than the width specified in Column 3 of that Table in respect of that number of persons.
5 exits plus one additional exit for each additional 450 persons, or part thereof.
9000 mm, plus 500 mm for each additional 50 persons or part thereof.
Table Notes
Where only one exit is provided that exit must be at least 1000 mm wide.
Where 2 exits are provided each must be at least 500 mm wide.
NCC Title
Exits to be provided
NCC State
NSW
NCC SPTC Current
Exits to be provided
NCC ID
_a5981fcd-c837-4dd4-ba0e-fb92f43a4c7b
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
Every part of an entrance or exit must provide a minimum unobstructed height of 2000 mm and, where the entrance or exit is beneath a stepped seating platform, infilled risers or other approved overhead protection must be provided above the entrance or exit.
NCC Title
Vertical clearance for exits
NCC State
NSW
NCC SPTC Current
Vertical clearance for exits
NCC ID
_77a5cea0-468d-40e4-9cb5-6801367109d9
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
A flap or curtain used to cover an exit must be so designed that, when it is secured, it will not obstruct or impede egress.
(1) A rigid guardrail must be provided at each end of a stepped or inclined platform, at least 750 mm high above the floor of the platform, and must extend—
in the case of a stepped platform, from the front of the first riser; and
in the case of an inclined platform, from the front of the first row of seating,
to the back of the highest platform and along the rear of that platform for its full width.
Artificial lighting must be provided, and must comply with NSW I4D54 and NSW I4D55.
NCC Title
Artificial lighting: general
NCC State
NSW
NCC SPTC Current
Artificial lighting: general
NCC ID
_cad7b1a6-60f3-424e-ba1b-bc06870d270d
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
Emergency lighting must be provided to the areas provided with artificial lighting under NSW I5D15 and must include a sufficient number of lamps to give a minimum illumination of 0.2 lux at floor level.
NCC Title
Emergency lighting
NCC State
NSW
NCC SPTC Current
Emergency lighting
NCC ID
_cc7b0787-c3b0-4adb-9716-1645da7d6bc3
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
Where emergency lighting is provided, the capacity of the battery and charging system must be sufficient to provide the illumination required by NSW I5D16 for—
30 minutes, in respect of a temporary structure designed to accommodate not more than 1000 persons; and
60 minutes, in respect of a temporary structure designed to accommodate more than 1000 persons.
NCC Title
Emergency lighting power supply
NCC State
NSW
NCC SPTC Current
Emergency lighting power supply
NCC ID
_ccaee8eb-0e55-4279-8c52-2194f383cbe8
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
Exit signs must be provided above all exits and in such other locations as may be required by NSW E4D6 and must comply with E4D5 and E4D8.
NCC Title
Exit signs
NCC State
NSW
NCC SPTC Current
Exit signs
NCC ID
_797e40c9-7b54-41bf-83a7-099e6b6f14dc
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
(1) Fire-fighting services and appliances must be so provided as to afford adequate protection and must be so located as the approving authority, on the advice of the Commissioner of Fire and Rescue NSW, may require.
(2) Where required by the approving authority, the fire-fighting services and appliances must comply with Part E1.