is used by the public as a place of assembly as described in the Public Health Act 1997; and
is a temporary structure as described in the Building Act 2016.
NCC Title
Application of Part
NCC State
TAS
NCC SPTC Current
Application of Part
NCC ID
_566b897a-aac4-40b5-8514-ff86bc32566c
Building Classes
1a,1b,10a,10b,10c
TAS I18P2 Safety and serviceability
2019: TAS H123 P1
NCC Blurbs
A temporary structure must, to the degree necessary, be capable of sustaining at an acceptable level of safety and serviceability the most adverse combination of loads and other actions to which it may reasonably be expected to be subjected.
NCC Title
Safety and serviceability
NCC State
TAS
NCC SPTC Current
Safety and serviceability
NCC ID
_a18c70ae-2ea8-42bb-b869-2f886c44fdc9
Building Classes
1a,1b,10a,10b,10c
TAS I18P3 Resistance to the spread of fire
2019: TAS H123 P2
NCC Blurbs
The material used in a temporary structure must, to the degree necessary, be capable of resisting the spread of fire to limit the generation of smoke and heat, and any toxic gases likely to be produced.
NCC Title
Resistance to the spread of fire
NCC State
TAS
NCC SPTC Current
Resistance to the spread of fire
NCC ID
_c4c048e1-3cad-4227-aade-f8974aa5e7f0
Building Classes
1a,1b,10a,10b,10c
TAS I18P4 Access
2019: TAS H123 P3
NCC Blurbs
(1) Access must be provided, to the degree necessary, to enable safe, equitable and dignified movement of people to and within a temporary structure.
(2) So that people can move safely to and within a temporary structure, it must have—
walking surfaces with safe gradients; and
stairways and ramps with slip-resistant walking surfaces; and
suitable handrails where necessary to assist and provide stability to people using a stairway or ramp.
(3) Access for people with disabilities must be provided to and within a temporary structure, including to any public sanitary facilities and all areas normally used by the public.
(4) If fixed seating is provided in a temporary structure, an appropriate number of wheelchair spaces must be provided.
NCC Title
Access
NCC State
TAS
NCC SPTC Current
Access
NCC ID
_be3965f8-8aea-4e04-b0be-0907f26df637
Building Classes
1a,1b,10a,10b,10c
TAS I18P5 Exits
2019: TAS H123 P4
NCC Blurbs
(1) Exits must be provided to the degree necessary, from a temporary structure to enable the safe evacuation of occupants, with their number, location and dimensions being appropriate to the—
number, mobility and other characteristics of the occupants; and
function or use of the structure.
(2) So that occupants can safely evacuate a temporary structure, paths of travel to exits must have dimensions appropriate to the—
number, mobility and other characteristics of the occupants; and
function or use of the structure.
NCC Title
Exits
NCC State
TAS
NCC SPTC Current
Exits
NCC ID
_d44da8bd-8a31-44d5-bb4b-1dddd68eca46
Building Classes
1a,1b,10a,10b,10c
TAS I18P6 Fall prevention
2019: TAS H123 P5
NCC Blurbs
Where a person could fall 1 m or more, due to a sudden change of level within or associated with a temporary structure, a barrier must to the degree necessary, be provided which must be—
continuous and extend for the full extent of the hazard; and
of a height to protect people from accidentally falling from the level; and
constructed to prevent people falling through the barrier; and
capable of restricting the passage of children; and
of a strength and rigidity to withstand the foreseeable impact of people and where appropriate, the static pressure or people pressing against it.
NCC Title
Fall prevention
NCC State
TAS
NCC SPTC Current
Fall prevention
NCC ID
_4e630697-5b37-422e-9c27-637a6a39c02c
Building Classes
1a,1b,10a,10b,10c
TAS I18P7 Lighting
2019: TAS H123 P6
NCC Blurbs
A level of illumination for safe evacuation from a temporary structure in an emergency must be provided, to the degree necessary, appropriate to the—
operate in the event of power failure for a sufficient time for occupants to safely evacuate.
NCC Title
Identification of exits
NCC State
TAS
NCC SPTC Current
Identification of exits
NCC ID
_2e62c3fc-286e-4f94-9cc9-fca7b69599d9
Building Classes
1a,1b,10a,10b,10c
TAS I18P9 Fire-fighting equipment
2019: TAS H123 P8
NCC Blurbs
Fire equipment must be installed in a temporary structure to the degree necessary, to allow the occupants to undertake initial attack on a fire appropriate to the—
function or use of the structure; and
fire hazard.
NCC Title
Fire-fighting equipment
NCC State
TAS
NCC SPTC Current
Fire-fighting equipment
NCC ID
_f759038c-b846-44bd-9a34-c551a26c5e09
Building Classes
1a,1b,10a,10b,10c
TAS I18P10 Sanitary facilities
2019: TAS H123 P9
NCC Blurbs
Sanitary facilities for personal hygiene must be provided in a convenient location associated with a temporary structure, to the degree necessary, appropriate to the—
function or use of the structure; and
number and gender of the occupants; and
disability or other particular needs of the occupants.
NCC Title
Sanitary facilities
NCC State
TAS
NCC SPTC Current
Sanitary facilities
NCC ID
_1cf02e53-dc23-400f-8d55-c3476050bce9
Building Classes
1a,1b,10a,10b,10c
TAS I18P11 Artificial lighting
2019: TAS H123 P10
NCC Blurbs
(1) A temporary structure must be provided with natural or artificial lighting to enable the safe use and movement of people using the structure.
(2) Lighting must be installed to the degree necessary, to provide a level of illumination appropriate to the function or use of a temporary structure to enable safe use and movement by the occupants.
NCC Title
Artificial lighting
NCC State
TAS
NCC SPTC Current
Artificial lighting
NCC ID
_fcdec188-d826-40bc-8574-fabc99a13d12
Building Classes
1a,1b,10a,10b,10c
TAS I18P12 Ventilation
2019: TAS H123 P11
NCC Blurbs
(1) A temporary structure must be provided with a means of ventilation which will maintain adequate air quality.
(2) Ventilation must be provided to the degree necessary, to a level appropriate to the function or use of a temporary structure.
NCC Title
Ventilation
NCC State
TAS
NCC SPTC Current
Ventilation
NCC ID
_53f5bc7e-7964-4935-a645-cd09e71da2d9
Building Classes
1a,1b,10a,10b,10c
TAS I18P13 Electrical services
2019: TAS H123 P12
NCC Blurbs
Electrical services must be installed to the degree necessary, to provide a level of safety appropriate to the environment and function or use of a temporary structure by the occupants.
NCC Title
Electrical services
NCC State
TAS
NCC SPTC Current
Electrical services
NCC ID
_6f770ecc-1a26-4872-8e2c-f4bd0b0eace4
Building Classes
1a,1b,10a,10b,10c
TAS I18P14 Heating appliances
2019: TAS H123 P13
NCC Blurbs
Where provided for a temporary structure, a heating appliance and its associated components must be installed to the degree necessary—
to withstand the temperatures likely to be generated by the appliance; and
so that it does not raise the temperature of any structural element to a level that would adversely affect the element’s physical or mechanical properties or function; and
so that hot products of combustion will not—
escape through the walls of the associated components; and
discharge to a position that will cause fire to spread to nearby combustible materials or allow smoke to penetrate the temporary structure; and
to reduce the likelihood of fire and harmful emissions spreading beyond the appliance.
NCC Title
Heating appliances
NCC State
TAS
NCC SPTC Current
Heating appliances
NCC ID
_5d29079b-91c8-43f4-a098-19bfe198bdd2
Building Classes
1a,1b,10a,10b,10c
TAS I18P15 Tiered seating
2019: TAS H123 P14
NCC Blurbs
A temporary structure of tiered seating must be designed and constructed to the degree necessary, to provide for the safety of occupants and orderly means of evacuation in an emergency.
NCC Title
Tiered seating
NCC State
TAS
NCC SPTC Current
Tiered seating
NCC ID
_f6517fd4-1177-4f18-860c-97448c563e93
Building Classes
1a,1b,10a,10b,10c
TAS I18P16 Safe environment
2019: TAS H123 P15
NCC Blurbs
A temporary structure must, to the degree necessary, be a safe and hazard free environment for the people using the structure.
Disability access requirements, which are included in TAS I18D3.
Lighting requirements, which are included in TAS I18D4.
Ventilation requirements, which are included in TAS I18D5.
Electrical requirements, which are included in TAS I18D6.
Heating appliance requirements, which are included in TAS I18D7.
NCC Title
Deemed-to-Satisfy Provisions
NCC State
TAS
NCC SPTC Current
Deemed-to-Satisfy Provisions
NCC ID
_6af6a5b6-ca55-4c9a-b5b0-75d92b4e60f8
Building Classes
1a,1b,10a,10b,10c
TAS I18D3 Access
2019: TAS H123.4
NCC Blurbs
(1) Access for people with disabilities must be provided to and within a temporary structure by means of a continuous path of travel.
(2) Access for people with disabilities must be provided to—
any public sanitary facilities; and
all areas normally used by the public but excluding those areas only used by persons working in the temporary structure.
(3) If fixed seating is provided, in a temporary structure, wheelchair spaces must be provided not less than—
1 wheelchair space for up to 100 seats; and
2 wheelchair spaces for 100 - 200 seats; and
an additional wheelchair space for each additional 200 seats or part thereof.
(4) Parts of a temporary structure required to be accessible must comply with AS 1428.1.
NCC Title
Access
NCC State
TAS
NCC SPTC Current
Access
NCC ID
_57354691-6972-4c2f-829c-552ccc3596a2
Building Classes
1a,1b,10a,10b,10c
TAS I18D4 Lighting
2019: TAS H123.11
NCC Blurbs
(1) Natural or artificial lighting must be provided to all enclosed areas in a temporary structure.
(2) Natural lighting must as far as practicable be not less than 10% of the floor area of the enclosed area.
(3) The artificial lighting system must as far as practicable comply with the relevant provisions of AS 1680 Parts 1, 2.0, 2.1, 2.2 and 2.3.
NCC Title
Lighting
NCC State
TAS
NCC SPTC Current
Lighting
NCC ID
_579e74f8-6094-424a-9258-4b43d17d3254
Building Classes
1a,1b,10a,10b,10c
TAS I18D5 Ventilation
2019: TAS H123.12
NCC Blurbs
(1) Natural ventilation or mechanical ventilation must be provided to all enclosed areas in a temporary structure.
(2) Natural ventilation must as far as practicable consist of openings or devices which can be opened with an aggregate opening of not less than 5% of the floor area of the enclosed area.
(3) Mechanical ventilation must as far as practicable comply with the relevant provisions of AS 1668.2.
NCC Title
Ventilation
NCC State
TAS
NCC SPTC Current
Ventilation
NCC ID
_f640440a-4129-431e-8308-5d79ddebfc89
TAS I18D6 Electrical
2019: TAS H123.13
NCC Blurbs
All electrical installations in a temporary structure must be installed in accordance with AS/NZS 3000.
NCC Title
Electrical
NCC State
TAS
NCC SPTC Current
Electrical
NCC ID
_88e2ad91-df7f-4de7-9f83-c4f2cf61589e
Building Classes
1a,1b,10a,10b,10c
TAS I18D7 Heating appliances
2019: TAS H123.14
NCC Blurbs
The installation of a stove, heater or similar appliance in a temporary structure must as far as practicable comply with the following standards:
Domestic oil-fired appliances – Installation: AS 1691.