NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
I6
VIC Part I6 Class 9b children’s servicesVIC Part I6 Class 9b children’s services
VIC Part I6 — Class 9b Children’s services contains an additional Performance Requirement and Deemed-to-Satisfy Provisions for Section D for Class 9b children’s services.
Performance Requirements
The number and location of doorways to a children’s room must take into account the mobility of children in the event that emergency egress or entry is required.
VIC I6P1 only applies to Class 9b children’s services.
Doorways to a children’s room
Deemed-to-Satisfy Provisions
Performance RequirementVIC I6P1 and relevant Performance Requirements in Section D are satisfied by complying with VIC I6D2 and VIC I6D3.
Deemed-to-Satisfy Provisions
The Deemed-to-Satisfy Provisions of this Part apply to Class 9b children’s services.
Application of Part
A children’s room must have a doorway, or in the case of every such room accommodating more than 21 children at least two doorways as widely separated as possible, providing direct access to or from—
Doorways to a children’s room