NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
20
Specification 20 Smoke detection and alarm systemsThis Specification describes the installation and operation of automatic smoke detection and alarm systems.
To state that Specification 20 relates to the installation and operation of automatic alarm systems.
Automatic smoke detection and alarm systems
Specification 20 covers the technical requirements for smoke detection and alarm systems, including such detection as is necessary to activate smoke control systems.
A required automatic smoke detection and alarm system must be provided in accordance with the following:
To specify compliance requirements for required automatic smoke detection and alarm systems.
Types of smoke detection and alarm systems
S20C2 covers smoke detection and alarm systems directly referenced in Part E2. The application of smoke detection to smoke control systems is addressed in S20C6.
S20C2 indicates the types of system, in terms of smoke alarm and/or smoke detection, applicable to various Classes of buildings. A smoke detection system is considered necessary in certain Class 3 and Class 9a buildings to facilitate system monitoring as required by S20C8.
Smoke alarm systems
Smoke alarm systems are required in:
Smoke detection systems
Smoke detection systems are required (and in some cases are the sole requirement to satisfy smoke hazard management provisions) in:
Combined systems
Combined smoke alarm and smoke detection systems are permitted (as specified) in:
A smoke alarm system and a smoke detection system are only required to be installed when required by Part E2.
To specify requirements for required automatic smoke alarm systems.
Smoke alarm systems—S20C3(1)
Smoke alarm systems must include smoke alarms which comply with AS 3786 (see S20C3(1)(a)(i)).
Power to smoke alarm systems must come from the electrical power supply to that part of the building served by the smoke alarm system.
Use of other suitable alarms—S20C3(1)(b)
A smoke alarm can give false alarms if the atmosphere contains particles, such as steam or other vapours, which obscure vision. For example, in a kitchen or a bathroom these conditions may be present. S20C3(1)(b) therefore allows the use of a more suitable alarm in these locations. It is important that the alarm used is suitable for the location and type of fire likely to occur. The suitability of alarms can be determined by reference to AS 1670.1. The alternative of an alarm acknowledgement facility complying with AS 1670.1 provides occupants with an opportunity to mitigate the effects of spurious or unwarranted alarms.
Smoke alarms and residential buildings—S20C3(2)
S20C3(2) details the installation requirements for automatic smoke alarms in residential buildings (excluding Class 9 buildings).
S20C3(2)(b) requires alarms located within each sole-occupancy unit to be interconnected to provide a common alarm so that if one alarm sounds then other alarms in the sole-occupancy unit automatically activate, which will increase the likelihood of sleeping occupants being aware of the smoke. The word ‘alarm’ includes any type of alarm allowed under S20C3(1)(b)(i).
Smoke alarms located outside the sole-occupancy units, in public corridors and other common areas within the building, must be interconnected to provide a common building alarm in order to alert all building occupants to the potential hazard in the common evacuation routes.
In buildings which do not contain a sprinkler system complying with Specification 17, S20C3(2)(c) requires smoke alarms to be installed in public corridors and other internal public spaces. Such spaces would include public foyers, reception areas and enclosed carparks. However, these spaces would not include fire-isolated exits, as they are subject to separate smoke hazard management provisions.
Smoke alarms and health-care buildings—S20C3(3)
The application of S20C3(3) is limited by the provisions of S20C2(d) to small health-care buildings, where not more than six patients are accommodated in beds.
S20C3(3) requires smoke alarms to be installed in public corridors and other internal public spaces. Such spaces would include public foyers, reception areas and enclosed carparks. However, these spaces would not include fire-isolated exits, as they are subject to separate smoke hazard management provisions.
Interconnection of smoke alarms is required due to the level of compartmentation and the need to alert staff to help occupants who may be confused, non-ambulatory or otherwise dependent on assistance. Manual call points are also necessary in view of the nature of the occupancy.
To specify requirements for required automatic smoke detection systems.
Smoke detection systems—S20C4(1)
S20C4(1)(b)(i) specifies the circumstances in which AS 1670.1 applies.
S20C4(1)(b)(ii) specifies that the smoke detection system must activate a suitable building occupant warning system. Both apply subject to S20C4(1)(c).
Use of other suitable detectors—S20C4(1)(b)
A smoke detector can give false alarms if the atmosphere contains particles, such as steam or other vapours which obscure vision. For example, in a kitchen or bathroom these conditions may be present. S20C4(1)(b) therefore allows the use of a more suitable detector in these locations. It is important that the detector used is suitable for the location and type of fire likely to occur. The suitability of detectors can be determined by reference to AS 1670.1. The alternative of an alarm acknowledgement facility complying with AS 1670.1 provides occupants with an opportunity to mitigate the effects of spurious or unwarranted alarms.
Residential buildings—S20C4(2)
S20C4(2) details the installation requirements for automatic smoke detection systems in residential buildings (excluding Class 9 buildings).
In buildings which do not contain a sprinkler system complying with Specification 17 (other than a FPAA101D or FPAA101H system), S20C4(2)(a)(ii) requires smoke detectors to be installed in public corridors and other internal public spaces. Such spaces would include public foyers, reception areas and enclosed carparks. However, these spaces would not include fire-isolated exits, commercial storerooms, cleaner’s rooms, service cupboards or the like.
S20C4(2)(a)(i) references S20C3(2)(a) and (b) which require alarms located within each sole-occupancy unit to be interconnected to provide a common alarm so that if one alarm sounds then other alarms in the sole-occupancy unit automatically activate, which will increase the likelihood of sleeping occupants being aware of the smoke. The word ‘alarm’ includes any type of alarm allowed under S20C3(1)(b)(i).
Health-care buildings—S20C4(3)
S20C4(3) applies to all Class 9a buildings which have a smoke detection system. S20C3(a)(i) applies to both within the patient-care area and the path of travel after a person leaves the patient-care area.
Where an area within a health-care building is likely to cause spurious signals, and the area is protected with a sprinkler system complying with Specification 17, S20C4(3)(b) provides a concession to the smoke detector requirements.
Manual call points are required in evacuation routes in view of the nature of the occupancy.
Class 9c residential care buildings—S20C4(4)
In a Class 9c residential care building, an automatic smoke detection system must be installed in accordance with AS 1670.1. Subject to S20C4(1), Clause 3.27 of AS 1670.1 lists areas where detectors are required. Manual call points are also necessary in larger buildings in view of the nature of the occupancy.
To specify requirements for combined smoke alarm and smoke detection systems.
Combined smoke alarm and smoke detection systems—S20C5(1)
S20C2 specifies the circumstances in which S20C5 applies.
S20C5(1)(a) requires smoke alarms which comply with AS 3786 to be located within each sole-occupancy unit in accordance with S20C3.
In buildings which do not contain a sprinkler system complying with Specification 17 (other than a FPAA101D or FPAA101H system), S20C5(1)(b) requires smoke detectors which comply with AS 1670.1 to be installed in public corridors and other internal public spaces in accordance with S20C4.
To specify the smoke detection requirements applicable to smoke control systems.
AS 1668.1 systems—S20C6(1)
S20C6(1) covers smoke detection associated with AS 1668.1 stair pressurisation systems referenced in Part E2. It requires the installation of additional detectors adjacent to each bank of lift landing doors. Lift shafts form one of the principal paths for smoke spreading between floors in a multi-compartmented building.
Location and sensitivity—S20C6(2) and (3)
S20C6(2) and (3) cover the location and sensitivity of smoke detectors associated with smoke control systems referenced in:
Activation—S20C6(4)
Under S20C6(4), smoke detectors which activate a smoke control system must:
Subject to E4D9, a building occupant warning system provided as part of a smoke hazard management system must comply with clause 3.22 of AS 1670.1 to sound through all occupied areas except—
To specify the application of building occupant warning systems.
Residential buildings—S20C7(a) and (b)
Because of the protection provided by the fire compartmentation of sole-occupancy units in residential buildings, it is not mandatory for a building occupant warning system to have sounders or speakers installed within each sole-occupancy unit. Accordingly, S20C7(a) and (b) provide for the sound pressure levels to be measured at the entry to each sole- occupancy unit.
Residential care and health-care buildings—S20C7(c) and (d)
S20C7(c) and (d) provide for the warning signals to be modified in certain areas within residential care and health-care buildings to minimise trauma to occupants who may be confused or immobile. However, in such instances, adequate warning must always be available to staff, carers, employees and the like.
Class 9c buildings—S20C7(e)
S20C7(e) requires warning signals to be modified in certain areas within Class 9c buildings to minimise trauma to residents who may be confused or immobile. However, in such instances, adequate warning must always be available to staff, carers, employees and the like. Residential care facilities may contain more than one building. Nevertheless, staff are required to be notified irrespective of their location.
Occupiable outdoor areas
S20C7 requires a building occupant warning system provided as part of a smoke hazard management system to sound through all occupied areas. An occupiable outdoor area is part of a building, therefore a required occupant warning system must sound in an occupiable outdoor area.
Additional provisions in E4D9
The separate provisions under E4D9 are for emergency warning and intercom systems for emergency purposes in certain buildings.
The following installations must be connected to a fire alarm monitoring system connected to a fire station or fire station dispatch centre in accordance with AS 1670.3:
The following installations must be connected to a fire alarm monitoring system connected to a fire station or a fire station dispatch centre in accordance with AS 1670.3:
The following installations must be connected to a fire alarm monitoring system connected to a fire station or fire station dispatch centre in accordance with AS 1670.3:
To specify the system monitoring requirements in high risk occupancies.
High risk occupancies
S20C8 specifies the system monitoring requirements in high risk occupancies, to enable a timely and appropriate response by the local fire brigade to emergencies in such buildings as:
The standard referenced for the alarm monitoring system is AS 1670.3.