NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
D2
Part D2 Provision for escapeThis Part contains Deemed-to-Satisfy Provisions for Part D1. It sets out required numbers, dimensions and placement of exits, rules for measuring building occupancy and travel distance to exits, places exits lead to and the use of horizontal exits within a building.
There are no Deemed-to-Satisfy Provisions for D1P7 in respect of using lifts to assist occupants to evacuate a building.
To clarify that the requirements of D1P1 to D1P6, D1P8 and D1P9 will be satisfied if compliance is achieved with Parts D2, D3 and D4 in the case of all buildings, Part G3 in the case of buildings with an atrium, Part G4 in the case of buildings in alpine areas, Part G6 in the case of occupiable outdoor areas, Part I1 in the case of theatres, stages and public halls, and Part I2 for public transport buildings; for farm sheds, Part I3.. D1P7 is only required to be complied with if lifts are to be used to assist occupants to evacuate.
Most buildings
Where a solution is proposed to comply with the Deemed-to-Satisfy Provisions, D2D1 clarifies that for most buildings compliance with Parts D2, D3 and D4 will achieve compliance with D1P1 to D1P6, D1P8 and D1P9. The exceptions to this general rule are set out below.
Buildings with an atrium
If the building contains an atrium, it must comply with Part G3 in addition to Parts D2, D3 and D4.
Buildings with an occupiable outdoor area
If the building contains an occupiable outdoor area, it must comply with Part G6 in addition to Parts D2, D3 and D4.
Theatres, stages and public halls
A building which comprises a theatre, stage or public hall must comply with Part I1 in addition to Parts D2, D3 and D4.
Atrium and theatre, stage or public hall
If the building contains an atrium and one or more of a theatre, stage or public hall, it must comply with Parts D2, D3, D4, G3 and I1.
Buildings in alpine areas
A building located in an alpine area must comply with Part G4 in addition to Parts D2, D3 and D4.
Public transport buildings
A building associated with public transport services, such as railway stations, bus interchanges, airports and ferry terminals must comply with Part I2 in addition to Parts D2, D3 and D4.
Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2G2(3) and A2G4(3) as applicable. (See commentary on Part A2).
Farm sheds
For farm sheds, Part I3 contains provisions that apply alongside Parts D2, D3 and D4.
The Deemed-to-Satisfy Provisions of this Part do not apply to the internal parts of a sole-occupancy unit in a Class 2 or 3 building or a Class 4 part of a building.
To exempt internal parts of sole-occupancy units in Class 2 and Class 3 buildings and Class 4 parts from the Part D2 Deemed-to-Satisfy Provisions.
The Part D2 Deemed-to-Satisfy Provisions do not apply within a sole-occupancy unit of a Class 2 or Class 3 building and Class 4 parts.
This is because most occupants are familiar with the layout of their unit. The units are small in area compared to sole- occupancy units in other classes of building. They will also have a low level of occupancy and a lower fire load than most commercial and industrial buildings.
Additionally, such units will be separated from the rest of the building by fire-rated construction, or sprinklers will be installed. Except when considering smoke-hazard management matters, the path to the door leading out of sole-occupancy units is not regarded as part of the path of travel to an exit. See Part E2.
To require the provision of sufficient exits to enable safe egress in case of an emergency.
All buildings—D2D3(1)
Under D2D3(1), all buildings must have at least one exit from each storey. The remainder of D2D3 sets out the circumstances in which more than one exit may be required.
Why do some buildings require multiple exits?
The purpose of regulatory control over the number of exits in a building is to maximise the opportunities for people to have egress from the building in an emergency.
Egress from some buildings can be very difficult (for example, particularly tall or large buildings, or even small buildings which have a complex passageway design). It may be necessary to provide several alternative exits.
Horizontal exits
While a number of the D2D3 provisions refer to “horizontal exit”, they do not require the installation of a horizontal exit. Rather, where a horizontal exit exists or is proposed, at least two additional exits must be provided. Where there is no horizontal exit, there must still be at least two exits.
Class 2 to Class 8 buildings—D2D3(2)
The D2D3(2)(a) provision regarding an effective height of 25 metres recognises the effective operating height for fire brigade ladders and other fire-fighting and rescue equipment. Above this height, fire-fighting, rescue and egress problems increase considerably.
D2D3(2)(b)—Class 2 and Class 3 buildings complying with C2D6
C2D6 provides a concession for Class 2 and Class 3 buildings (having a rise in storeys of two), in that if they comply with certain conditions they may be of Type C construction. In order to qualify for that concession such buildings must have at least 2 exits.
This provision recognises that Class 2 and Class 3 buildings constructed in accordance with C2D6 include additional evacuation provisions.
Basements—D2D3(3)
“Basement” is not defined in the BCA. A basement is regarded as a below-ground-level storey not counted in the rise in storeys.
Any basement in excess of the minimum floor area specified in D2D3(3)(a) which has a travel distance to an exit in excess of that specified in D2D3(3)(b), must have at least two exits. The reason for this is that basements present difficulties in terms of egress and fire-fighting. These include:
All Class 9 buildings
D2D3(4)(a) covers Class 9 buildings with a rise in storeys of more than six (additional to the provisions which apply to Class 2 to Class 8 buildings) and Class 9 buildings with an effective height of more than 25 metres (which is the same as for Class 2 to Class 8 buildings, and recognises the effective operating height for fire brigade ladders and other fire-fighting and rescue equipment).
D2D3(4)(a) recognises the emergency egress requirements for Class 9 buildings. Such buildings could contain large numbers of people who may be unfamiliar with the building’s egress provisions. They might also be confused and in various stages of immobility.
D2D3(4)(a) does not refer to “whichever is the lesser”, nor, for that matter, “whichever is the greater”—meaning that both are applicable.
D2D3(4)(b) provides concession for small rooms, not normally occupied,from which egress is readily achieved.
Additional requirements for some Class 9 buildings
In D2D3(4)(a), and D2D3(5) and (6), the BCA recognises that some Class 9 buildings (patient care areas, aged care buildings, early childhood centres, schools, spectator stands, storeys or mezzanines containing more than 50 people as calculated under D2D18 present difficult evacuation conditions (requiring two exits additional to any horizontal exits) because of such factors as:
Exits must be accessible—D2D3(7)
There is little point requiring exits if they are not accessible at all times. D2D3(7) requires that occupants must be able to access an exit. Where two or more exits are required, at least two exits (allowing for the fact that one of the exits may be made inaccessible by an emergency, such as a fire) should be accessible.
Such access must not be through another sole-occupancy unit because access to the unit may be locked or barred.
D2D4(2) does not apply to—
To indicate when fire-isolated stairways and ramps are required to enable safe egress in case of a fire.
D2D4 and D1P5
D2D4 comprises the Deemed-to-Satisfy Provisions for D1P5.
Purpose of fire-isolated exits
Fire-isolated exits are required in multi-storey buildings to enable people to evacuate past a storey on fire. They also help the fire brigade carry out search and rescue and fire-fighting.
Such exits minimise the distance people need to travel in a fire-affected area before accessing a “safe place”, such as a fire-isolated stairway.
Fire-isolated exits may be:
D2D4 sets out when stairways and ramps connecting storeys in a building are required to be fire-isolated. This only applies to a stairway or ramp serving as a required exit. Therefore, from the definition of “exit”, D2D4 only applies to those providing egress to a road or open space. Combined with the provisions of D2D3 that exits are required from every storey, a stairway or ramp serving as an exit will generally be connecting storeys. However, the term “exit” could also apply to a stairway or ramp from a basement that exits vertically, directly to a road or open space and thus, does not technically connect storeys.
External stairways
Under certain specified conditions, D2D13 permits the use of external stairways in place of fire-isolated stairways.
D2D4 only applies to stairways that are required exits and therefore does not apply to stairways between split levels of a single storey of a building or those leading from the front door of a building.
Class 2 buildings—D2D4(1)(a)(i)
D2D4(1)(a)(i) permits Class 2 buildings to have non-fire-isolated exits provided they do not connect, pass through or pass by more than three consecutive storeys, plus an extra storey of any classification under specified conditions. The terms “connect”, “pass through” and “pass by” include the following situations:
With regard to the allowance for 3 storeys, the BCA assumes that residents of Class 2 buildings tend to be long-term occupants, and aware of their surroundings. This makes them likely to be able to exit quickly without the need for fire- isolated exits.
An extra storey of any classification may be included under certain circumstances where the fire risk associated with the extra storey is low. The circumstances are:
Class 3 buildings—D2D4(1)(a)(ii)
D2D4(1)(a)(ii) permits Class 3 buildings to have non-fire-isolated exits provided they do not connect, pass through or pass by more than two consecutive storeys, plus an extra storey of any classification under specified conditions. The terms “connect”, “pass through” and “pass by” include the following situations:
The allowance for two storeys is based on residents of a number of Class 3 buildings being less familiar with the building layout and paths of travel to an exit than residents of a Class 2 building. The differential between Class 2 and Class 3 buildings recognises a higher potential level of risk in Class 3 buildings.
An extra storey of any classification may be included under certain circumstances where the fire risk associated with the extra storey is low. The circumstances are:
Class 9a health-care buildings—D2D4(2)(a)
Under D2D4(2)(a), required exits in Class 9a health-care buildings need to be fire-isolated if they connect, pass through or pass by more than two consecutive storeys, or the areas they connect, pass through or pass by include one or more patient care areas. The terms “connect”, “pass through” and “pass by” include the following situations:
Open spectator stands—D2D4(2)(b)
D2D4(2)(b) allows an exemption for open spectator stands because of their open nature, which means that the build up of smoke is unlikely.
Class 5–9 buildings containing sprinklers—D2D4(2)(c)
D2D4(2)(c) does not apply to:
D2D4(2)(c) permits other Class 5–9 buildings to have non-fire-isolated exits provided they do not connect, pass through or pass by more than two consecutive storeys, plus an extra storey of any classification under specified conditions. The terms “connect”, “pass through” and “pass by” include the following situations:
An extra storey of any classification may be included under certain circumstances where the fire risk associated with the extra storey is low. The circumstances are:
Class 9b early childhood centres
Where a Class 9b early childhood centre is wholly within a storey that provides direct egress to a road or open space, or where the Class 9b early childhood centre is the only use in a building with a rise in storeys not more than two, then then D4D2(2) does not apply. Accordingly, these Class 9b early childhood centres need not be provided with fire-isolated exits.
To maximise the safety of occupants by enabling them to be close enough to an exit to safely evacuate.
Travel distances
The D2D5 travel distances are based on an assumption of what is considered “reasonable” distances to be travelled by occupants in reaching an exit.
Method of measurement
The travel distances specified in D2D5 are measured in accordance with D2D20.
Class 2 and Class 3 buildings and Class 4 parts—D2D5(1) and (2)
D2D5(1) and (2) require a shorter travel distance, to a single exit, for Class 2 and Class 3 buildings and Class 4 parts than is required for Class 5 to Class 9 buildings.
The distance occupants of sole-occupancy units in Class 2 and Class 3 buildings and Class 4 parts must travel to leave
their unit is not part of the distance specified in D2D5. Accordingly, the permitted distance of travel from the point at which the occupant leaves the unit must take account of the time needed for the occupant to reach that point from within the unit.
Distance of travel must factor in the time occupants need to wake up, become alert to their predicament, and exit in a state of confusion.
This process of becoming alert will inevitably require more time to exit. Therefore, the distance of travel to an exit should be shorter.
Figure D2D5a illustrates various methods of complying with D2D5 for Class 2 and Class 3 buildings and Class 4 parts of buildings.
Class 5 to Class 9 buildings—D2D5(3)(a)
D2D5(3)(a) sets out the maximum travel distance in Class 5–9 buildings. This includes Class 9c buildings, but excludes Class 9a buildings, which must comply with D2D5(4). (See comments on D2D5(4) for the reason Class 9a buildings are treated differently). The additional travel distance allowed in Class 9c buildings recognises the effectiveness of sprinkler systems that must be installed in these buildings.
The distances specified allow people to evacuate in a reasonable time, assuming that they are not asleep.
In case a fire blocks a path of travel, D2D5(3)(a) requires that alternative routes must be available within 20 metres of the starting point, unless it is possible to reach a single exit within 20 m.
The conditional reference in D2D5(3) to sub-clauses (4), (5) and (6) refers to special provisions for particular types of buildings.
Figure D2D5b illustrates various methods of complying with D2D5 for Class 5 to 9 buildings.
Class 5 and Class 6 buildings—D2D5(3)(b)
D2D5(3)(b) provides a concession for Class 5 and Class 6 buildings served by a single exit opening onto a road or open space. The concession only applies to the storey at the level of access to a road or open space.
D2D5(3)(b) uses the phrase “at the level of access to a road or open space”. The term “level” does not require the storey to be physically level or flush with the road or open space to obtain the concession, but simply requires that the storey is at a level from which occupants finally leave the building to reach a road or open space. The concession allows a greater travel distance of 30 m in lieu of 20 m to a single exit on the basis that occupants, including customers of a shop, are:
Small shops and offices at or near ground level also tend to have an open plan layout thereby allowing the exit to be easily sighted to permit safe and speedy egress where the space is located in close proximity to the external ground surface such as a road or open space.
The concession is applicable to a number of cases such as to any Class 5 and 6 parts of a building located in a storey at the level of access to a road or open space even though the storey may be served by more than one exit, subject to that part otherwise complying with D2D5(3)(b).
The concession is also available for Class 5 or 6 parts of a building containing other classifications (refer to A1G1(3)(a)).
The conditional reference in D2D5(3) to sub-clauses (4), (5) and (6) refers to special provisions for particular types of building.
Patient care areas—D2D5(4)
Patient care areas in Class 9a buildings can present particular problems in case of emergency egress. Such areas are likely to be occupied by people who are either fully or partly non-ambulatory, and in many cases confused or incapacitated by drugs and medical and post-operative conditions.
Accordingly, the allowable distance of travel to an exit in the patient care areas of a Class 9a building is less than for Class 5–8 buildings, non-patient care areas of Class 9a buildings, and Class 9b buildings.
D2D5(4) should be read in conjunction with C3D6.
Open spectator stands—D2D5(5)
The construction of an open spectator stand is such that the build up of smoke is unlikely. Greater distances of travel to an exit are therefore permitted.
Assembly buildings—D2D5(6)
The concession available for assembly buildings is based on a specific level of fire and smoke separation being provided between the area being evacuated and the circulation space passed through to reach an exit.
To obtain the concession, D2D5(6)(c) limits the distance of travel through the room being evacuated and across the circulation space outside that room to the exit.
Figure D2D5a: Distances to exits in Class 2 and Class 3 buildings
Figure D2D5b: Distance to exits in Class 5 to Class 9 buildings
Exits that are required as alternative means of egress must be—
Exits that are required as alternative means of egress must be—
To require that if an exit is inaccessible, access to any required alternative exit must be available within a reasonable distance.
Why is this matter regulated?
Where a building requires multiple exits, the exits maximise the choices of a person evacuating, in case one exit becomes blocked.
Uniform distribution of exits—D2D6(a)
D2D6(a) requires that where multiple exits exist, they must be distributed as uniformly as practicable to improve the level of safety when evacuating.
Minimum and maximum distances are set
D2D6 specifies the minimum and maximum permitted distances between alternative exits (for example, two exits may be located next to one another, so long as they are not each other’s alternative in an emergency). Where scissor stairs are used, the shafts will be adjacent and separated by fire-resisting construction. However, the access doors to the alternative scissor stairs must comply with the minimum separation distance.
Minimum distance—D2D6(b)
The minimum distance minimises the risk of fire spreading to block the alternative exit.
Maximum distance—D2D6(c)
The maximum distance between alternative exits minimises the need to travel too far to reach an exit.
Convergence distance—D2D6(d)
If alternative paths of travel converge too closely, both paths can be blocked by the same fire. The minimum distance between the paths of travel aims to negate this.
The minimum convergence distance only comes into operation when the paths of travel have already diverged to that distance. The paths can commence more closely together than the distance specified.
Method of measurement
The travel distances specified in D2D6 are measured in accordance with D2D20.
Figure D2D6a illustrates the method of measuring the maximum and minimum distances between exits.
Figure D2D6b illustrates the convergence prohibition on alternative paths of travel.
Figure D2D6a: Plan showing method of measuring between exits
Figure D2D6b: Plan showing converging paths of travel
To require exits and paths of travel to an exit to have dimensions to allow all occupants to evacuate safely within a reasonable time.
The D2D7 requirement for a minimum unobstructed height of two metres is considered to be a reasonable minimum for most people to safely walk through to gain egress.
D2D7 relates to the unobstructed height between a floor and:
It should be noted that in addition to complying with D2D7, exits and paths of travel to exits must comply with the minimum ceiling heights in F5D2.
The reduction to a minimum of 1980 mm for doorways is to allow for a standard door frame.
To require exits and paths of travel to an exit to have dimensions to allow all occupants to evacuate safely within a reasonable time.
Width required to allow safe exit
The required exit and path of travel widths have been determined on the basis of an estimate of the width required to allow the safe exit of a given number of people expected in particular buildings.
Exit and path of travel width—D2D8(1)
D2D8(1) clarifies that the unobstructed width of any exit or path of travel to an exit is to not be less than the dimensions prescribed. These may then be added to achieve the aggregate width that is required. Ladders that comply with D2D21, D3D23 or I3D5 does not need to comply with D2D8(1).
D2D8(1)(c) applies to Class 9c buildings. The additional width at doorways is to allow for greater manoeuvrability of beds, mobile baths, wheelchairs, walking frames and other equipment throughout the resident use areas.
Figure D2D8a illustrates two examples of how compliance with the corridor width provisions in a Class 9c building may be achieved.
Storeys accommodating up to 200 people—D2D8(1) and (2)
Buildings, other than ward and treatment areas of a Class 9a building, accommodating up to 200 people (see D2D8(1) and (2)) require minimum widths of:
See Figure D2D8a.
Storeys accommodating more than 200 people—D2D8(3)
Above 200 people (see D2D8(3)), there is a division between those buildings which have a change of floor level by way of stairways or ramps with a gradient greater than 1 in 12, and those which do not have such a change in floor level. The reason for this differentiation is that the change in floor level has the potential to create problems at exits, which could cause injuries and delays. The difference can be outlined as follows, and is illustrated in Figure D2D8b:
Aggregate width of exit or path of travel—D2D8(2), (3) and (4)
D2D8(2), (3) and (4) refer to the required width of an exit or path of travel to an exit in terms of an “aggregate unobstructed width”. The exit or path may be less than the total required width (although each must achieve the minimum required width), but when the width of each exit or path is added together, the specified aggregate unobstructed width must be achieved.
See Figure D2D8b
Exceptions to the exit and path of travel width
The following exceptions apply:
Figure D2D8a: Method of measuring corridor width in a Class 9c building
Figure D2D8b: Graph showing required exit widths
In a required exit or path of travel to an exit, the unobstructed width of a doorway must be not less than—
In a required exit or path of travel to an exit, the unobstructed width of a doorway must be not less than—
In a required exit or path of travel to an exit, the unobstructed width of a doorway must be not less than—
To require exits and paths of travel to an exit to have dimensions to allow all occupants to evacuate safely within a reasonable time.
Doorway widths—D2D9
The width of a doorway must be clear of all obstructions. This includes door handles or other attachments or any part of the door leaf and any part of the door frame, including the door stop.
Patient care areas—D2D9(a) and (b)
D2D9(a) and (b) provide additional width for doorways in patient care areas to allow for the turning circle of beds, and other egress difficulties, such as those experienced by patients who require ambulatory assistance. D2D9(a) applies to doorways between a patient care area (such as ward bedroom or dining area) and a corridor.
Width of a doorway—D2D9(c)
The width of a doorway comprising part of the exit or path of travel is permitted to be 250 mm less than the width of each exit. This allows for the installation of a standard door frame.
In the case of an exit comprising multiple doorways, this concession may be applied to each individual doorway.
Figure D2D9 shows alternative examples of the exit door width for a building requiring a total exit width of three metres.
Class 9c buildings—D2D9(d)
D2D9(d) applies to Class 9c buildings. The additional width of doorways is to allow for greater manoeuvrability of beds, mobile baths, wheelchairs, walking frames and other equipment throughout resident use areas.
Minimum permitted width of a doorway—D2D9(e)
No doorway should be less than 750 mm in width, except doorways which open into toilets and bathrooms. However,
minimum width requirements do apply to doorways which provide access to facilities required for people with disabilities (see D4D3 and F2D5).
Figure D2D9: Plan showing examples of exit widths for a building requiring an exit width of 3 m
The unobstructed width of a required exit must not diminish in the direction of travel to a road or open space, except where the width is increased in accordance with D2D8(1)(b) or D2D9(a)(i).
To require exits and paths of travel to an exit to have dimensions to allow all occupants to evacuate safely within a reasonable time.
Under D2D10, the required unobstructed width of exit or path of travel must not be reduced in the direction of egress. This provision aims to avoid congestion in an exit or a path of travel to an exit.
Examples
A restaurant is located on the fifth floor of a building.
The restaurant may seat 250 people. This would require an aggregate exit width of 2.5 metres. One stairway, 2.5 metres in width, is provided to achieve the exit requirement.
The fourth floor of the same building may be used as an office, with 100 staff, requiring an aggregate exit width of only 1 metre.
The 2.5 metre wide stairway from the fifth floor cannot be reduced to 1 metre when it reaches the fourth floor. The stairway must retain its 2.5 metre width throughout its length.
The exit width is not required to increase to 3.5 metres below the 4th floor. The BCA makes the assumption that the occupants of both floors are unlikely to all be exiting through the same part of the stairway at the same time.
If the restaurant was below the office, the stairway could begin at 1 metre in width at the office, but would have to increase to 2.5 metres after it passed the restaurant.
For the purposes of D2D7 to D2D10 the following apply:
To require exits and paths of travel to an exit to have dimensions to allow all occupants to evacuate safely within a reasonable time.
Under D2D11(a)(i), the required stairway width must be measured clear of obstructions, including handrails and projecting barriers.
Under D2D11(a)(ii), the required width of a stairway must continue to a height of 2 metres above the stair. This measurement is consistent with other similar BCA requirements.
Figure D2D11 illustrates compliance with D2D11(a).
Figure D2D11: Method of measuring height and width of a stairway
To enable occupants to safely enter a fire-isolated exit which discharges to a safe location.
Access to fire-isolated exits—D2D12(1)
D2D12(1) requires that a doorway must not open into a fire-isolated exit unless it opens from a public area, a sole- occupancy unit which occupies a whole floor, or a toilet. This is to limit the number of entry points into a fire-isolated exit to retain its fire-resisting performance.
Note that D2D12(1)(a) refers to a “public corridor, public lobby, or the like”. A smoke lobby which serves at least two sole- occupancy units is a “public lobby”, and can open directly into a fire-isolated exit. Figure D2D12a illustrates permitted and prohibited entry into a fire-isolated passageway from sole-occupancy units in a shopping centre.
Discharge to areas not roads and open spaces—D2D12(2)
D2D12(2)(a) requires fire-isolated exits to discharge to roads or open spaces. However, there are some exemptions:
D2D12(2)(b) sets out the requirements for a fire-isolated exit to discharge into an area within a building (including the requirement that it be open for at least two thirds of its perimeter, to aid smoke ventilation); and
D2D12(2)(c) sets out the requirements for a fire-isolated exit to discharge into a covered area outside the building (including the requirement that it be open for at least one third of its perimeter, to aid smoke ventilation).
Figure D2D12b and Figure D2D12c illustrate some of the options available by the use of D2D12.
Travel within 6 metres of an external wall—D2D12(3)
D2D12(3) sets out the FRL and opening protection requirements where the path of travel from the point of discharge of a fire-isolated exit to a road or open space necessitates passes within six metres of any part of the external wall of the building being evacuated. The provision only applies at the level of discharge. So if the exit discharges at ground level, any first storey wall or window would not need protection. The reason is that a fire on the first floor is unlikely to affect people exiting one storey below.
Smoke lobby or pressurised system—D2D12(4)
D2D12(4) requires the use of a smoke lobby or a pressurisation system to stop the entry of smoke into the fire-isolated exit, if more than two access doorways described in D2D12(4)(a) or (b) are provided in the same storey. This provision must be read in conjunction with D2D12(1), it does not over-ride it. See Figure D2D12a.
Ramps in Class 9 buildings—D2D12(5)
D2D12(5) requires a ramp where there is any change in level in a fire-isolated passageway in a Class 9 building and that change is less than 600 mm.
Figure D2D12a: Plans showing entry into a fire-isolated passageway in a shopping centre
Figure D2D12b: Example of discharge of fire-isolated stair complying with D2D12(2)(b)
Figure D2D12c: Example of discharge of fire-isolated stair complying with D1.7(2)(c)
Figure D2D12d: Plan showing when walls and windows require protection in accordance with D2D12(3)
To detail the circumstances in which an external stairway or ramp can be provided instead of a fire-isolated stairway or fire-isolated ramp.
Alternative to required fire-isolated stairways or ramps
Compliance with D2D13 for external stairway or ramp is only required where the external stairway or ramp is proposed as an alternative to a required fire-isolated stairway or ramp. In other words, if a fire-isolated stairway or ramp is not required by the BCA, compliance is not required with D2D13.
External stairways and ramps permitted to 25 metres
The use of an external stairway or ramp is permitted instead of a fire-isolated stairway or ramp up to a height of 25 metres. The reason external stairways or ramps are not permitted above this height is because of:
Fire protection required
Fire protection from the external wall of the building near the external exit and any openings in that wall, is required under D2D13(1) and (2) to ensure that an average person using the exit is afforded adequate protection from flames and radiant heat from a fire within the building.
D2D13(3) provides two separate methods of protecting the external exit from a fire from within the building:
D2D13(4) provides requirements for the shielding construction and protection of any openings in that construction.
Figure D2D13a: Protection of the external exit using the external wall of building in accordance with D2D13(3)(a)
Figure D2D13b: Protection of the external exit using shielding construction in accordance with D2D13(3)(b)
To require that a person using a non-fire-isolated stairway or ramp be provided with a safe evacuation path.
Continuous means of travel—D2D14(1)
D2D14(1) requires that occupants in a required non-fire-isolated stairway or ramp are able to continue all the way down to the level from which egress to a road or open space is available.
D2D14(1) refers to a continuous means of travel comprising flights of stairs and landings. It would generally not be acceptable for an entire or substantial proportion of a storey to be called a “landing”.
The first diagram in Figure D2D14a illustrates non-compliance with D2D14(1) because the stair does not provide a continuous path of travel to the level providing egress to a road or open space. The second diagram in Figure D2D14a illustrates a method of compliance with D2D14(1).
Required stairways and ramps
The distances specified in D2D14 apply only to a required non-fire-isolated stairway or ramp. Figure D2D14b illustrates the method of measuring a travel distance down a stairway.
Distances for non-fire-isolated stairways—D2D14(2) and (3)
D2D14(2) and (3) provide requirements for the overall travel distances permitted on non-fire-isolated stairways. Figure D2D14c illustrates compliance with D2D14(2) and (3).
Distance from stairway to discharge point—D2D14(4) and (5)
D2D14(4) and (5) provide requirements for the travel distance permitted from the base of the non-fire-isolated stairway to the discharge point (note that this distance is part of the distances required under D2D14(2) and (3).
Figure D2D14d illustrates compliance with D2D14(4) and (5).
D2D14(6) provides the additional requirements for Class 2 and Class 3 buildings which are required to have 2 or more exits.
Figure D2D14e illustrates one method of an exit system in a Class 5–9 building complying with Section D.
Figure D2D14a: Section showing compliance with D2D14(1)
Figure D2D14b: Method of measuring travel distance down a stairway
Figure D2D14c: Method of measuring overall distance of travel via non-fire- isolated stairways
Figure D2D14d: Plans showing compliance with D2D14(4) and (5) for the discharge of non-fire-isolated stairways
Figure D2D14e: One method of compliance with Section D
whichever is the greater.
To require the safe discharge from an exit to a road or open space.
Egress not to be blocked—D2D15(1)
D2D15(1) requires that an exit must not be blocked at the point of discharge.
Barriers (such as bollards) must be installed, if they are necessary to prevent vehicles blocking access to, or discharge from, an exit.
Link between open space and a road—D2D15(2) and (3)
If an exit discharges to an open space, D2D15(2) and (3) require that a safe means of travel be provided from the open space to a road. This means that the following criteria must be satisfied:
The link between the road and open space must be open to the sky for its length.
Discharge points to be well separated—D2D15(4)
D2D15(4) requires that the discharge points of alternative exits be as far apart as possible, so that if the discharge from one of them is blocked, the other will still operate satisfactorily.
Open spectator stand—D2D15(5)
D2D15(5) requires that exits from an open spectator stand not discharge to the ground in front of the stand. There may be a large number of people viewing the event from the front of the stand, and they may obstruct the path of those evacuating.
There is also a risk that the front of the stand could be subject to severe heat radiation. Also the only egress to the road from the ground in front of the stand may be through the stand.
Auditorium—D2D15(6)
Under D2D15(6), only two thirds of the required width of exits from an auditorium, such as a theatre or hall, are to discharge into an entrance foyer where the auditorium can accommodate more than 500 people. This restriction applies because there may be a large number of people in the foyer, possibly waiting for the next show, or to gain access to another auditorium. These people would obstruct the path of the people evacuating.
To detail how the installation of horizontal exits in a building is permitted as an alternative to a conventional exit.
Difficult evacuations
Originally, provision was made for horizontal exits between fire compartments because some occupants can have difficulty evacuating, particularly those confined to bed or that have a disability.
Subsequently, it was accepted that horizontal exits would be of value in other buildings, where they could overcome problems associated with large fire compartments, e.g. excessive distances to travel to exits.
Purpose of horizontal exits
The use of horizontal exits can overcome some of the difficulties outlined above, although they need to be used in conjunction with some other form of exit.
In an emergency, the Deemed-to-Satisfy Provisions require that occupants travel for limited distances before they reach a place of safety. A “place of safety”, in the case of horizontal exits, means the connecting fire compartment to which people will flee.
For a horizontal exit to comply with the Deemed-to-Satisfy Provisions of Section D, it must meet the following criteria:
Other uses of horizontal exits
Horizontal exits may be useful as a means of evacuation from many health-care buildings. They can also be an advantage in large floor area buildings which need to be sub-divided by fire walls to reduce the size of the fire compartments. These fire walls can then be penetrated to create horizontal exits.
Figure D2D16: Plan showing doors forming a horizontal exit in a fire wall in accordance with D2D16
An escalator, moving walkway or non-required non fire-isolated stairway or pedestrian ramp—
To limit the spread of fire and smoke through unprotected openings for stairways, ramps, escalators and moving walkways.
Application
D2D17 only applies to:
What is a non-required non-fire-isolated stairway or ramp?
Builders etc may choose to interconnect two or three storeys of a building with a non-required stairway, ramp or the like in accordance with D2D17.
Examples
A two storey shop or suite of offices may be within a multi-storey building where all storeys are connected by a stairway which is both required and fire-isolated. This stairway may be external to the sole-occupancy unit which comprises the shop or office suite. For easy access within the sole-occupancy unit, another stairway may be located within the shop or office suite interconnecting the two storeys. That stairway is additional to the required stairway, and is not required to be fire-isolated.
Patient care and resident use area—D2D17(a)
D2D17(a) prohibits the use of a non-required non-fire-isolated stairway or ramp in a patient care area of a Class 9a building and a resident use area of a Class 9c building. The prohibition is because of the difficulties in evacuating bed-ridden, or otherwise mobility-impaired occupants. This prohibition applies to D2D17(d), despite that provision’s general reference to Class 9 buildings.
D2D17(b) allows any number of storeys to be connected in certain buildings as follows:
Atriums and Part G3—D2D17(b)(ii)
While D2D17(b)(ii) refers to atriums, there are additional requirements for atriums in Part G3.
Number of interconnected storeys is restricted—D2D17(c) and (d)
D2D17 restricts the number of storeys which can be interconnected by a non-required non-fire-isolated stairway, ramp or the like. This recognises that an unprotected opening for a stairway, ramp, escalator or the like can lead to the spread of fire or smoke from one floor to another.
The restriction applies if:
Neither storey is required to provide direct egress to a road or open space and there is no requirement for a sprinkler system as part of this provision. As the stairway or ramp is not required by the BCA for emergency evacuation purposes, this provision is in accord with the remainder of the BCA.
For the purposes of the Deemed-to-Satisfy Provisions, the number of persons accommodated in a storey, room or mezzanine must be determined with consideration to the purpose for which it is used and the layout of the floor area by—
Type of use | Area per person |
---|---|
Art gallery, exhibition area, museum | 4 m2 |
Bar — standing | 0.5m2 |
Bar — other | 1 m2 |
Board room | 2 m2 |
Boarding house | 15 m2 |
Cafe, church, dining room | 1 m2 |
Carpark | 30 m2 |
Computer room | 25 m2 |
Court room — judicial area | 10 m2 |
Court room — public seating | 1 m2 |
Dance floor | 0.5 m2 |
Dormitory | 5 m2 |
Early childhood centre | 4 m2 |
Factory — machine shop, fitting shop or like place for cutting, grading, finishing or fitting of metals or glass, except in the fabrication of structural steelwork or manufacture of vehicles or bulky products | 5 m2 |
Factory — areas used for fabrication and processing other than a machine shop, fitting shop or the like. | 50 m2 |
Factory — a space in which the layout and natural use of fixed plant or equipment determines the number of persons who will occupy the space during working hours | Area per person determined by the use of the plant or equipment |
Gymnasium | 3 m2 |
Hostel, hotel, motel, guest house | 15 m2 |
Indoor sports stadium—arena | 10 m2 |
Kiosk | 1 m2 |
Kitchen, laboratory, laundry | 10 m2 |
Library — reading space | 2 m2 |
Library — storage space | 30 m2 |
Office, including one for typewriting or document copying | 10 m2 |
Patient care areas | 10 m2 |
Plant room — ventilation, electrical or other service units | 30 m2 |
Plant room — boilers or power plant | 50 m2 |
Reading room | 2 m2 |
Restaurant | 1 m2 |
School — general classroom | 2 m2 |
School — multi-purpose hall | 1 m2 |
School — staff room | 10 m2 |
School — trade and practical area — primary | 4 m2 |
School — trade and practical area — secondary | As for workshop |
Shop — space for sale of goods — at a level entered direct from the open air or any lower level | 3 m2 |
Shop — space for sale of goods — all other levels | 5 m2 |
Showroom — display area, covered mall or arcade | 5 m2 |
Skating rink, based on rink area | 1.5 m2 |
Spectator stand, audience viewing area — standing viewing area | 0.3 m2 |
Spectator stand, audience viewing area — removable seating | 1 m2 |
Spectator stand, audience viewing area — fixed seating | Per number of seats |
Spectator stand, audience viewing area — bench seating | 450 mm/person |
Storage space | 30 m2 |
Swimming pool, based on pool area | 1.5 m2 |
Switch room, transformer room | 30 m2 |
Telephone exchange — private | 30 m2 |
Theatre and public hall | 1 m2 |
Theatre dressing room | 4 m2 |
Transport terminal | 2 m2 |
Workshop — for maintenance staff | 30 m2 |
Workshop — for manufacturing processes | As for factory |
Bar standing is an area used by the standing patrons and extends not less than 1.5 m wide from the outside edge of the bar top for the length of the serving area of the bar.
Type of use | Area per person |
---|---|
Art gallery, exhibition area, museum | 4 m2 |
Auditorium — bench seating | 450 mm/person |
Auditorium — fixed seating | count seats |
Auditorium — removable seating | 1 m2 |
Auditorium — standing area | 0.5 m2 |
Bar — standing | 0.5m2 |
Bar — other | 1 m2 |
Board room | 2 m2 |
Boarding house | 15 m2 |
Cafe, church, dining room | 1 m2 |
Carpark | 30 m2 |
Computer room | 25 m2 |
Court room — judicial area | 10 m2 |
Court room — public seating | 1 m2 |
Dance floor | 0.5 m2 |
Dormitory | 5 m2 |
Early childhood centre | 4 m2 |
Entertainment venue — other than auditorium | 1.2 m2 |
Factory — machine shop, fitting shop or like place for cutting, grading, finishing or fitting of metals or glass, except in the fabrication of structural steelwork or manufacture of vehicles or bulky products | 5 m2 |
Factory — areas used for fabrication and processing other than a machine shop, fitting shop or the like | 50 m2 |
Factory — a space in which the layout and natural use of fixed plant or equipment determines the number of persons who will occupy the space during working hours | Area per person determined by the use of the plant or equipment |
Gymnasium | 3 m2 |
Hostel, hotel, motel, guest house | 15 m2 |
Indoor sports stadium—arena | 10 m2 |
Kiosk | 1 m2 |
Kitchen, laboratory, laundry | 10 m2 |
Library — reading space | 2 m2 |
Library — storage space | 30 m2 |
Office, including one for typewriting or document copying | 10 m2 |
Patient care areas | 10 m2 |
Plant room —ventilation, electrical or other service units | 30 m2 |
Plant room — boilers or power plant | 50 m2 |
Reading room | 2 m2 |
Restaurant | 1 m2 |
School — general classroom | 2 m2 |
School — multi-purpose hall | 1 m2 |
School — staff room | 10 m2 |
School — trade and practical area — primary | 4 m2 |
School — trade and practical area — secondary | As for workshop |
Shop — space for sale of goods — at a level entered direct from the open air or any lower level | 3 m2 |
Shop — space for sale of goods — all other levels | 5 m2 |
Showroom — display area, covered mall or arcade | 5 m2 |
Skating rink, based on rink area | 1.5 m2 |
Small live music or arts venue – dance floor | 0.5 m2 |
Small live music or arts venue – Information and education facility | 4 m2 |
Small live music or arts venue – other | 1 m2 |
Spectator stand, audience viewing area — standing viewing area | 0.3 m2 |
Spectator stand, audience viewing area — removable seating | 1 m2 |
Spectator stand, audience viewing area — fixed seating | Per number of seats |
Spectator stand, audience viewing area — bench seating | 450 mm/person |
Storage space | 30 m2 |
Swimming pool, based on pool area | 1.5 m2 |
Switch room, transformer room | 30 m2 |
Telephone exchange — private | 30 m2 |
Theatre dressing room | 4 m2 |
Transport terminal | 2 m2 |
Workshop — for maintenance staff | 30 m2 |
Workshop — for manufacturing processes | As for factory |
Bar standing is an area used by the standing patrons and extends not less than 1.5 m wide from the outside edge of the bar top for the length of the serving area of the bar.
To establish a methodology for calculating Deemed-to-Satisfy building populations which are deemed acceptable for use in the design and checking of applications when more accurate figures are not available.
D2D18 Table D2D18 are used to calculate the anticipated number of people in particular types of building.
From these calculations, a number of BCA requirements can be determined within Sections D, E, F and J. The likely number of persons accommodated can affect determinations in relation to a number of matters in the BCA including; exit requirements, hearing augmentation, limitation of the use of stairway platform lifts, sanitary facilities, ceiling heights and the energy efficiency of mechanical ventilation systems.
D2D18 not to be used for non-BCA purposes
D2D18 and Table D2D18 are only intended for the purposes of determining BCA requirements which depend on the number of occupants likely to occupy a building or storey. D2D18 and Table D2D18 are not intended to restrict the number of occupants using a building, or to enforce any building use or licensing requirements.
Use of Table D2D18
If more accurate information is available on the expected population of a building, it should be used in preference to Table D2D18. This information may include:
Examples
It would be appropriate to use an alternative means of assessing the number of occupants when:
The area per person contained in Table D2D18 for computer rooms applies to rooms housing computer infrastructure such as computer servers and where low occupant numbers occur. These circumstances are similar to those found in switch or transformer rooms. For computer training rooms and office areas containing computers, the area per person for an office or school classroom, as appropriate, should be used.
The nearest part of an exit means in the case of—
To identify the nearest part of an exit for the purposes of measuring travel distance.
Why is this important?
D2D19 describes the point at which an exit has commenced with respect to both fire-isolated and non-fire-isolated exits. Figure D2D20a and Figure D2D20b illustrate methods of measuring the distance of travel specified in the BCA.
The following rules apply:
To specify the method of measuring the distance of travel to an exit in various situations.
Path a person would walk
The distance of travel to an exit is measured by determining the path a person would walk from the most remote area of the building to the nearest exit.
The maximum distance of travel between required alternative exits is measured by determining the path a person would travel along in a case where a fire blocks the path of travel to the nearest exit. The path of travel to the alternative exit includes passing through the point at which travel in different directions to those exits is available.
Measure around any built obstructions
It is necessary to measure around any walls, or other built obstructions (including a wall, a demountable wall, and permanent fixed seating). See D2D20(f) and (g).
Furnishings do not need to be taken into account
Generally, furniture, cars in a carpark and some non-built or non-fixed obstructions are not taken into account in the calculation of travel distance. However, there may be occasions when such matters must be taken into account.
Figure D2D20b illustrates, by example, the method of measuring the distance of travel for Class 2 and Class 3 buildings and Class 4 parts.
Figure D2D20c illustrates, by example, the method of measuring the distance of travel for Class 5–9 buildings.
Figure D2D20a: Plan showing measurement of maximum distance of travel between required alternative exits
Figure D2D20b: Plan showing one method of compliance with Section D for Class 2 and Class 3 buildings and Class 4 parts
Figure D2D20c: Plan showing one method of compliance with D2D20 for Class 5–9 buildings
To provide concessions for small plant rooms, lift motor rooms and Class 8 electricity network substations.
Why are concessions made?
Concessions (such as the use of a ladder in lieu of a stairway) are granted for small plant rooms, lift motor rooms and Class 8 electricity network substations for the following reasons:
Figure D2D21 illustrates some possible methods of using the concessions contained in D2D21.
Figure D2D21: Plans showing use of D2D21
Access to lift pits must—
To provide the requirements for access to lift pits.
D2D22 provides the requirements to access lift pits for maintenance purposes and to restrict access.
D2D23(1) recognises the difficulties associated with evacuation of primary schools. Should a primary school be proposed within a storey that does not meet the requirements of D2D23, a Performance Solution is to be used to demonstrate compliance with the relevant Performance Requirements.
To limit the height of primary schools subject to Deemed-to-Satsify Provisions relating to egress.
D2D23 limits the application of egress Deemed-to-Satisfy Provisons to primary schools with a rise in storeys of 4 or less. Accordingly, if a primary school is proposed that does not conform to the limitations of D2D23, then a Performance Solution is necessary. This clause is provided in recognition of the difficulty in evacuating a primary school.