NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
F7
NT Part F7 Sound transmission and insulationNT Part F7 Sound transmission and insulation
This Part is intended to reduce the likelihood of illness or loss of amenity as result of undue noise transmission between different parts of a building or adjoining buildings. This part contains minimum requirements for sound insulation for walls, floors and penetrations through walls and floors for services such as pipework.
Floors separating sole-occupancy units must provide insulation against the transmission of airborne and impact generated sound sufficient to prevent illness or loss of amenity to the occupants.
NT F7P1 only applies to a Class 2 or 3 building or a Class 9c building.
Walls separating—
must provide sufficient insulation against the transmission or airborne or impact generated sound sufficient to prevent illness or loss of amenity to the occupants.
NT F7P2 only applies to a Class 2 or 3 building.
The required sound insulation of floors and walls must not be compromised by the incorporation or penetration of a pipe or other service element.
NT F7P3 only applies to a Class 2 or 3 building or a Class 9c building.
must provide insulation against the transmission of airborne sound sufficient to prevent illness or loss of amenity to the occupants.
NT F7P4 only applies to a Class 9c building.
The Deemed-to-Satisfy Provisions of this Part apply to Class 2 and 3 buildings and Class 9c aged care buildings.
A form of construction required to have a certain weighted sound reduction index (RW) must—
A floor separating sole-occupancy units must have an RW not less than 45.
A wall must have an RW not less than 45 if it separates—
If a soil or waste pipe, including a pipe that is embedded in or passes through a floor, serves or passes through more than one sole-occupancy unit—
A flexible coupling must be used at the point of connection between the service pipes in a building and any circulating or other pump.
In addition to NT F7D5, a wall separating a sole-occupancy unit in a Class 9c building from a kitchen or laundry must—