NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
I6
VIC Part I6 Class 9b children’s servicesVIC Part I6 Class 9b children’s services
VIC Part I6 — Class 9b Children’s services contains an additional Performance Requirement and Deemed-to-Satisfy Provisions for Section D for Class 9b children’s services.
The number and location of doorways to a children’s room must take into account the mobility of children in the event that emergency egress or entry is required.
VIC I6P1 only applies to Class 9b children’s services.
Performance RequirementVIC I6P1 and relevant Performance Requirements in Section D are satisfied by complying with VIC I6D2 and VIC I6D3.
The Deemed-to-Satisfy Provisions of this Part apply to Class 9b children’s services.
A children’s room must have a doorway, or in the case of every such room accommodating more than 21 children at least two doorways as widely separated as possible, providing direct access to or from—