NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
12
Specification 12 Fire doors, smoke doors, fire windows and shuttersThis Specification sets out requirements for the construction of fire doors, smoke doors, fire windows and fire shutters.
To prescribe standards for the construction of fire doors, smoke doors, fire windows and fire shutters.
Specification 12 contains detailed Deemed-to-Satisfy Provisions that could form part of a solution for achieving the Performance Requirements relevant to:
To specify the fire performance of fire doors to achieve compatibility with the fire performance of the walls in which they are located.
Required fire doors must comply with AS 1905.1, which is the construction Standard for fire doors. This Standard in turn requires that fire doors be tested in accordance with AS 1530.4.
If there is any glazing in the door, the door must not fail by radiation through that glazing within the period specified in the door’s FRL criterion of integrity.
In most cases, the BCA requires a fire door to have an FRL of –/60/30. Where a fire door is located in a fire wall, a higher FRL is required.
The first criterion of zero minutes is a reference to the structural adequacy of the door. AS 1905.1 does not require a fire door to be tested for structural adequacy.
The final criterion of 30 minutes is a reference to the insulation the door must provide. It is difficult for a fire door to achieve a higher insulation criterion when tested in accordance with AS 1530.4.
Any glass panel in a fire door must not fail through heat radiation during a fire, as measured by the AS 1530.4 test, before the door fails the integrity criterion. If the glass panel fails by radiation, spread of fire could occur due to radiant heat igniting combustible materials.
Smoke doors must be constructed so that smoke will not pass from one side of the doorway to the other and, if they are glazed, there is minimal danger of a person being injured by accidentally walking into them.
To specify the smoke performance of smoke doors to achieve compatibility with the smoke performance of the walls in which they are located, by minimising the flow of smoke from one side of the door to the other.
S12C3 is a performance criterion for smoke doors. It sets the general requirement that smoke doors must prohibit the passage of smoke from one side to the other; and if glass panels are installed, minimise the risk of injury of people accidentally walking into them. For example, it would generally be acceptable for the panel to be opaque.
To comply with S12C3, a building proponent may choose to comply with S12C4.
A smoke door of one or two leaves satisfies S12C3 if it is constructed as follows:
To specify the general requirements under the Deemed-to-Satisfy Provisions for the construction of smoke doors.
Under S12C4(a), the leaves of a smoke door which is intended to achieve the requirements of S12C3 must swing in both directions, or in the direction of travel. This means that they cannot be sliding doors or roller shutters.
To make sure that a door is adequately smoke sealed during a fire:
S12C4 requires glazing in smoke doors to comply with AS 1288. The glazing must be made apparent by opaque construction if it is capable of being mistaken for an unobstructed opening as part of an exit. This is achieved by complying with the requirements of S12C4(g). The intent of S12C4(g) is to prevent the glazing in smoke doors to be entirely of clear construction.
A required fire shutter must—
To enable the fire performance of fire shutters to be compatible with the fire performance of the walls in which they are located.
Under S12C5(a)(i), required fire shutters must have the required FRL determined in accordance with Specification 1.
Specification 1 requires that a prototype of the element being tested must be subjected to the Standard Fire Test. See AS 1530.4.
In order for a fire shutter to comply with Specification 12, it must be identical to a prototype tested in accordance with AS 1530.4.
When testing the FRL of fire shutters in accordance with AS 1530.4, the structural adequacy criteria is not included. Hence, these criteria are not included in the required FRL of a fire shutter.
Under S12C5(a), non-metallic fire shutters:
The reason for the last condition is to reduce the amount of radiant heat on the non-fire side of the shutter, which could ignite combustible materials.
Under S12C5(b), metallic fire shutters can only be used if not prohibited by C4D6. Metallic fire shutters are not permitted in certain situations because of the risk that fire could spread by way of radiated heat facilitated by the metal construction of the shutter. Such radiated heat could ignite combustible materials on the non-fire side of the shutter.
If permitted, metallic fire shutters must either comply with AS 1905.2 or be in accordance with S12C5(a), in that they:
To specify the fire performance of fire windows to achieve compatibility with the fire performance of the walls in which they are located.
Required fire windows must have the required FRL determined in accordance with Specification 1.
Specification 1 requires that a prototype of the element being tested must be subjected to the Standard Fire Test. See AS 1530.4.
Therefore, in order for a fire window to comply with Specification 12, it must be identical to a prototype tested in accordance with AS 1530.4. When testing the FRL of fire windows in accordance with AS 1530.4, the structural adequacy and insulation criteria are not included. Hence these criteria are not included in the required FRL of a fire window.