NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

C2

Part C2 Fire resistance and stability

Part C2 Fire resistance and stability

SA C2D2 Type of construction required2019: C1.1

Delete subclause C2D2(1) and insert SA C2D2(1) as follows:

(1) The minimum Type of fire-resisting construction of a building must be determined in accordance with Table C2D2, except as allowed for—

  1. certain Class 2, 3 or 9c buildings, in C2D6; and
  2. a Class 4 part of a building located on the top storey, in C2D4(2); and
  3. open spectator stands and indoor sports stadiums, in C2D8; and
  4. Class 2 buildings located within 3 m of a brush fence and Class 10b brush fences located within 3 m of a Class 2 building, in SA C2D2(3) and (4); and
  5. a Class 7b bulk grain storage facility in SA C2D16.

SA C2D2 Type of construction required2019: C1.1

Insert SA subclause C2D2(3) in clause C2D2 as follows:

(3) In addition to the minimum fire-resisting construction requirements of Table C2D2 and Specification 5 a Class 2 building must not be constructed within 3 m of a Class 10b brush fence unless any part of the building within 3 m of the brush fence complies with the fire-resisting requirements of SA C2D16.

SA C2D2 Type of construction required2019: C1.1

Insert SA subclause C2D2(4) in clause C2D2 as follows:

(4) A Class 10b brush fence must not be constructed within 3 m of a Class 2 building unless any part of the building within 3 m of the brush fence complies with the fire-resisting construction requirements of SA C3D16.

SA C2D16 Class 7b bulk grain storage facilities2019: SA C1.15

Insert SA clause C2D16 in clause C2D16 as follows:

The external walls of a bulk grain storage facility need not be of fire-resisting construction if—

  1. The external walls are 3 m or more from an allotment boundary and more than 6 m from any other building on the same allotment, other than a Class 10 building; and
  2. a fire separation space of not less than 2 m is provided between cell type silos; and
  3. the external walls are—
    1. of non-combustible construction; or
    2. of Type C construction.