TAS Part I11 Foundries
Introduction to this Part
This Part contains additional requirements for foundries.
Deemed-to-Satisfy Provisions
NCC Blurbs
(1) This Part is applicable to every building or premises on which foundry operations are undertaken.
(2) Foundries must provide for the comfort and safety of workers on the premises.
NCC SPTC Current
Application of Part
NCC ID
_ca6bf620-88fe-42b3-ad61-74e86ef63a47
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
(1) Every floor in a foundry must be level and, in places other than where molten metal is poured, must be composed or similar material or wooden blocks.
(2) Every part of a foundry must be not less than 4.2 m high—
- where a ceiling is provided, measured from the floor to the ceiling; or
- where a ceiling is not provided, measured from the floor to the lowest part of the roof.
NCC ID
_faa38db7-e9ab-4155-8560-a5c09497eab6
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
(1) The floors of cupola charging platforms must be—
- of heavy timber or non-slip steel plate; and
- securely fixed in position; and
- level.
(2) All parts of the cupola charging platform must be covered by a roof not less than 3 m above the platform.
(3) A cupola charging platform must have—
- a wall, not less than 1 m high, measured from the floor of the platform, constructed to surround the platform; and
- the side between the top of the wall and the roof suitably waterproofed an ventilated.
(4) A properly constructed access stair or ramp must be provide to give access to every cupola charging platform and must comply with AS 1657.
NCC SPTC Current
Cupola charging platform
NCC ID
_75a404a0-4b99-4ace-ac0a-babe8b1fe435
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
Deep moulds or pits, for permanent use—
- must be lined with bricks, concrete, or other suitable material in such a manner as to provide adequate reinforcement and to keep the pit or mould in a dry condition; and
- must be securely fenced by means of a wall of adequate construction, railings or chains and stanchions raised, in each case, to a height not less than 1 m above the surface of the surrounding floor.
NCC SPTC Current
Deep moulds and pits
NCC ID
_aa30e449-6625-4e7e-910b-89f926bf3ab3
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
Where pot furnaces are below ground level, the pit must be covered by a substantial grating at the point at which metal is removed from the furnace, and must at all other times be securely fenced as in TAS I11D4(b)
NCC SPTC Current
Pot furnaces
NCC ID
_6449a214-271c-43bc-8be2-071c7a760f8d
Building Classes
1a,1b,10a,10b,10c