TAS Part I11 Foundries

TAS Part I11 Foundries

Introduction to this Part

This Part contains additional requirements for foundries.

Deemed-to-Satisfy Provisions

NCC Blurbs

(1) This Part is applicable to every building or premises on which foundry operations are undertaken.

(2) Foundries must provide for the comfort and safety of workers on the premises.

NCC Title

Application of Part

NCC State
TAS
NCC SPTC Current
Application of Part
NCC Blurbs

(1) Every floor in a foundry must be level and, in places other than where molten metal is poured, must be composed or similar material or wooden blocks.

(2) Every part of a foundry must be not less than 4.2 m high—

  1. where a ceiling is provided, measured from the floor to the ceiling; or
  2. where a ceiling is not provided, measured from the floor to the lowest part of the roof.
NCC Title

General

NCC State
TAS
NCC SPTC Current
General
NCC Blurbs

(1) The floors of cupola charging platforms must be—

  1. of heavy timber or non-slip steel plate; and
  2. securely fixed in position; and
  3. level.

(2) All parts of the cupola charging platform must be covered by a roof not less than 3 m above the platform.

(3) A cupola charging platform must have—

  1. a wall, not less than 1 m high, measured from the floor of the platform, constructed to surround the platform; and
  2. the side between the top of the wall and the roof suitably waterproofed an ventilated.

(4) A properly constructed access stair or ramp must be provide to give access to every cupola charging platform and must comply with AS 1657.

NCC Title

Cupola charging platform

NCC State
TAS
NCC SPTC Current
Cupola charging platform
NCC Blurbs

Deep moulds or pits, for permanent use—

  1. must be lined with bricks, concrete, or other suitable material in such a manner as to provide adequate reinforcement and to keep the pit or mould in a dry condition; and
  2. must be securely fenced by means of a wall of adequate construction, railings or chains and stanchions raised, in each case, to a height not less than 1 m above the surface of the surrounding floor.
NCC Title

Deep moulds and pits

NCC State
TAS
NCC SPTC Current
Deep moulds and pits
NCC Blurbs

Where pot furnaces are below ground level, the pit must be covered by a substantial grating at the point at which metal is removed from the furnace, and must at all other times be securely fenced as in TAS I11D4(b)

NCC Title

Pot furnaces

NCC State
TAS
NCC SPTC Current
Pot furnaces