NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
1
Specification 1 Fire-resistance of building elementsThis Specification sets out the procedures for determining the FRL of building elements.
To clarify that Specification 31 includes the requirements for fire and smoke control systems in buildings with an atrium.
Specification 31 includes the requirements for fire and smoke control systems in buildings containing an atrium.
Where a sprinkler system is required, it must be installed in the whole building, not just that part in which the atrium is located.
A building element meets the requirements of this Specification if—
Masonry type | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/60/60 | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 | |
Ashlar | - | - | - | - | 300 |
Calcium silicate | See clause S1C2(d)(iv) | ||||
Concrete | |||||
Fired clay |
For the purposes of this table, each element must meet the requirements of Specification 2.
Concrete type | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/60/60 | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 | |
No fines | - | - | - | 150 | 300 |
Prestressed | See clause S1C2(d)(iv) | ||||
Reinforced | |||||
Plain | - | - | - | 150 | 170 |
For the purposes of this table, each element must meet the requirements of Specification 2.
Gypsum type | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/60/60 | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 | |
Solid gypsum blocks | 75 | 90 | 100 | 110 | 125 |
Gypsum — perlite or gypsum vermiculite-plaster on metal lath and channel (non-loadbearing walls only) | 50 | 50 | 65 | - | - |
For the purposes of this table, each element must meet the requirements of Specification 2.
Column type | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/60/60 | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 | |
Prestressed | See clause S1C2(d)(ii) | ||||
Reinforced |
Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/60/60 | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 | |
Concrete cast in-situ — loadbearing | 25 | 30 | 40 | 55 | 75 |
Concrete cast in-situ — non-loadbearing unplastered | 25 | 30 | 40 | 50 | 75 |
Concrete cast in-situ — non-loadbearing plastered 13 mm | 25 | 25 | 30 | 40 | 50 |
Gypsum cast in-situ | - | - | - | - | 50 |
Gypsum — perlite or gypsum-vermiculite plaster—sprayed to contour | 20 | 25 | 35 | 50 | 55 |
Gypsum — perlite or gypsum-vermiculite plaster—sprayed on metal lath | 20 | 20 | 25 | 35 | 45 |
For the purposes of this table, each element must meet the requirements of Specification 2.
Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/60/60 | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 | |
Solid calcium-silicate masonry | 50 | 50 | 50 | 50 | 65 |
Solid clay masonry | 50 | 50 | 50 | 65 | 90 |
Solid concrete masonry | 50 | 50 | 50 | 65 | 90 |
Solid gypsum blocks | 50 | 50 | 50 | 50 | 65 |
Hollow terracotta blocks — plastered 13 mm | 50 | 50 | 50 | 65 | 90 |
For the purposes of this table, each element must meet the requirements of Specification 2.
Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/60/60 | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 | |
Solid calcium-silicate masonry | 50 | 50 | 50 | - | - |
Solid clay masonry | 50 | 50 | 65 | - | - |
Solid concrete masonry | 50 | 50 | 65 | - | - |
Solid gypsum blocks | 50 | 50 | 50 | - | - |
Hollow terracotta blocks — plastered 13 mm | 50 | 50 | 65 | - | - |
For the purposes of this table, each element must meet the requirements of Specification 2.
Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/–/– | 90/–/– | 120/–/– | 180/–/– | 240/–/– | |
Concrete cast in-situ — loadbearing | 25 | 40 | 45 | 65 | 90 |
Concrete cast in-situ — non-loadbearing unplastered | 35 | 30 | 40 | 50 | 65 |
Concrete cast in-situ — non-loadbearing plastered 13 mm | 25 | 25 | 30 | 40 | 50 |
Gypsum cast in-situ | - | - | - | - | 50 |
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour | 25 | 30 | 40 | 55 | 65 |
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath | 20 | 20 | 30 | 40 | 50 |
For the purposes of this table, each element must meet the requirements of Specification 2.
Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/–/– | 90/–/– | 120/–/– | 180/–/– | 240/–/– | |
Solid calcium-silicate masonry | 50 | 50 | 50 | 65 | 75 |
Solid clay masonry | 50 | 50 | 50 | 75 | 100 |
Solid concrete masonry | 50 | 50 | 50 | 75 | 100 |
Solid gypsum blocks | 50 | 50 | 50 | 65 | 75 |
Hollow terracotta blocks — plastered 13 mm | 50 | 50 | 50 | 75 | 100 |
For the purposes of this table, each element must meet the requirements of Specification 2.
Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/–/– | 90/–/– | 120/–/– | 180/–/– | 240/–/– | |
Solid calcium-silicate masonry | 50 | 50 | 50 | - | - |
Solid clay masonry | 50 | 50 | 65 | - | - |
Solid concrete masonry | 50 | 50 | 65 | - | - |
Solid gypsum blocks | 50 | 50 | 50 | - | - |
Hollow terracotta blocks — plastered 13 mm | 50 | 50 | 65 | - | - |
For the purposes of this table, each element must meet the requirements of Specification 2.
Concrete type | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/–/– | 90/–/– | 120/–/– | 180/–/– | 240/–/– | |
Prestressed | See clause S1C2(d)(ii) | ||||
Reinforced |
Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/–/– | 90/–/– | 120/–/– | 180/–/– | 240/–/– | |
Concrete — cast in-situ | 25 | 30 | 40 | 50 | 65 |
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour | 20 | 25 | 35 | 50 | 55 |
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath | 20 | 20 | 25 | 35 | 45 |
For the purposes of this table, each element must meet the requirements of Specification 2.
Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/–/– | 90/–/– | 120/–/– | 180/–/– | 240/–/– | |
Concrete — cast in-situ | 25 | 40 | 45 | 60 | 90 |
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour | 20 | 30 | 40 | 55 | 65 |
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath | 20 | 20 | 35 | 40 | 50 |
For the purposes of this table, each element must meet the requirements of Specification 2.
Floor, roof or ceiling type | Minimum thickness (mm) of principal material for FRLs | ||||
---|---|---|---|---|---|
60/60/60 | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 | |
Prestressed | See clause S1C2(d)(ii) | ||||
Reinforced |
To set out the installation requirements and delineate compliance pathways for a building element to meet this Specification.
An FRL is expressed in terms of figures that cover structural adequacy, integrity and insulation.
Examples
A loadbearing wall may require an FRL of 120/60/30 – meaning that in the Standard Fire Test, the wall must retain its:
A non-loadbearing wall, however, may require an FRL of -/120/120 – meaning that in a Standard Fire Test, the wall is not required to retain any structural adequacy criterion. However, in a Standard Fire Test, the wall must maintain its:
Some building elements have been tested and their FRLs have been determined. A number of these are included in Tables S1C2a to S1C2n. To achieve the FRLs contained in tables S1C2a, S1C2b, S1C2c, S1C2e, S1C2f, S1C2g, S1C2h, S1C2i, S1C2j, S1C2l, and S1C2m each element must comply with Specification 2.
Research results are generally available from the manufacturers who sponsor the tests.
A number of Standards Australia structural codes have provisions for the calculation of FRLs. Some more complicated building elements have many combinations and permutations, and reference to specific Australians Standards is necessary.
If the FRL of a building element is determined by calculation based on a tested prototype—
To establish methods for determining a building element's FRL by calculation using data from a similar tested prototype.
To provide further options for building element selection by providing interchangeable materials.
If the fire-resisting covering of a steel column is lightweight construction, the construction must comply with Volume One C2D9 and C4D17.
To clarify that lightweight construction used to protect steel columns must adhere to C2D9 and C4D17.
If a non-loadbearing element is able to be used for a purpose where the Deemed-to-Satisfy Provisions prescribe an FRL for structural adequacy, integrity and insulation, that non-loadbearing element need not comply with the structural adequacy criteria.
To specify that a non-loadbearing element need not meet any structural adequacy requirement.