Delete clause J5D5 and insert NSW J5D5 as follows:
(2) The requirements of (1) do not apply to—
- a window complying with AS 2047; or
- a fire door or smoke door; or
- a roller shutter door, roller shutter grille or other security door or device installed only for out-of-hours security.
(3) A seal to restrict air infiltration—
- for the bottom edge of a door, must be a draft protection device; and
- for the other edges of a door or the edges of an openable window or other such opening, may be a foam or rubber compression strip, fibrous seal or the like.
(4) An entrance to a building, if leading to a conditioned space must have an airlock, self-closing door, rapid roller door, revolving door or the like, other than—
- where the conditioned space has a floor area of not more than 50 m2; or
- where a café, restaurant, open front shop or the like has—
- a 3 m deep un-conditioned zone between the main entrance, including an open front, and the conditioned space; and
- at all other entrances to the café, restaurant, open front shop or the like, self-closing doors.
Applications
NSW J5D5(5) does not apply to a Class 2 building or a Class 4 part of a building.