(1) Artificial lighting must be provided along the external path of travel (including steps, landings, ramps or paths) to a road or open space associated with each exit from a WA public building.
(2) The artificial lighting system required by (1) must—
provide a minimum illuminance of 1 lux at ground level; and
be connected to circuits separate from those supplying lighting for foyers, entry porches, emergency escape passages or areas provided entry or egress to the WA public building; and
be connected over two circuits where two or more lights are required; and
have switches that are not able to be operated by members of the public.
NCC Title
Artificial lighting
NCC State
WA
NCC SPTC Current
Artificial lighting
NCC ID
_c2044e10-1c95-4658-8c1f-c12583dc8b49
Building Classes
1a,1b,10a,10b,10c
WA I4D7 Fixed seating
2019: WA H101.6
NCC Blurbs
Where fixed seating in a Class 9b WA public building is arranged in more than one row—
aisles must be provided on both sides of every row that contains more than 10 seats; and