NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Filter by state
  • Australian Capital Territory
  • New South Wales
  • Northern Territory
  • Queensland
  • South Australia
  • Tasmania
  • Victoria
  • Western Australia
Filter by zone
  • Climate Zone 1
  • Climate Zone 2
  • Climate Zone 3
  • Climate Zone 4
  • Climate Zone 5
  • Climate Zone 6
  • Climate Zone 7
  • Climate Zone 8
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Filter by state
  • Australian Capital Territory
  • New South Wales
  • Northern Territory
  • Queensland
  • South Australia
  • Tasmania
  • Victoria
  • Western Australia
Filter by zone
  • Climate Zone 1
  • Climate Zone 2
  • Climate Zone 3
  • Climate Zone 4
  • Climate Zone 5
  • Climate Zone 6
  • Climate Zone 7
  • Climate Zone 8
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

3

Specification 3 Fire hazard properties

Specification 3 Fire hazard properties

2019: Sch. 6: 1

To establish the tests required by Specification 3.

This specification deals with the testing to AS/NZS 1530.3 of an assembly of materials where the central core of the assembly is shielded from the effects of the fire.

Assemblies

2019: Sch. 6: 2.1

To establish the tests required by Specification 3.

S3C2 deals with the installation of an assembly of materials where the central core of the assembly is shielded from the effects of fire.

2019: Sch. 6: 2.2

To establish the tests required for early fire-hazard properties on assemblies of materials.

Specification 3 requires two tests in accordance with S3C3(a) and S3C3(b). They are respectively: AS/NZS 1530.3 for Spread-of-Flame Index and Smoke-Developed Index; and AS 1530.4 for the ability to prevent ignition and to screen the core material from free air. 

2019: Sch. 6: 2.3

To specify the details required for the test specimen.

The assembly to be tested must include all joints, perforations, recesses, and the like. These parts may affect not only its early fire-hazard properties but are also more likely to affect the passage of air and fire to the assembly’s inner core. The requirements for the test specimen apply to both tests required by S3C3.

2019: Sch. 6: 2.4

To provide a concession for the re-testing of joints, perforations, recesses, and the like which have been previously tested.

S3C5 is based on the assumption that S3C3 tests would be passed by joints, perforations and recesses, which will be smaller in the building member to be used on site than those in the member tested. The concession in S3C5 applies to both tests in S3C3.

2019: Sch. 6: 2.5

To allow smaller test specimens when testing for the ability to prevent ignition and screen the core material from free air when appropriate.

The smaller test specimen allowed by S3C6 only applies to the AS 1530.4 test required by S3C3(b). The smaller test specimen is allowed for practical reasons in the test rig. This is on the basis that the test will affect the specimen in an identical manner to the on-site building member.

The results from a smaller test specimen are limited to those specified by the testing laboratory. In accordance with Specification 3, only an Accredited Testing Laboratory may conduct the test.